Facility ID: 8511884
Facility Name: OCEAN REEF CLUB-AIRPORT FUEL TANK
 
06/13/2023 Enforcement Tracking Activity Dolan, Judy F.
Activity Status: Open
05/24/2023 Violation Open Shanberg, Vincent J
Significance: SNC-B Status: Open
Criteria ID: 7065
Rule: 62-762.601(1)(e), 62-762.602(1)(e)
05/24/2023 Enforcement Referral Activity Shanberg, Vincent J
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 06/13/2023
Events:
Event Type: Activity has been submitted for approval Date: 06/13/2023
Comment: Submitted for approval by: Vincent J Shanberg: referral
Events:
Event Type: Activity has been assigned Date: 06/13/2023
Comment: Assigned to Judy F. Dolan
Events:
Event Type: Activity has been finished Date: 06/13/2023
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 06/13/2023
Comment: Accepted by Judy F. Dolan: Vincent site.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 06/13/2023
Comment: Acknowledged and Assigned by Judy F. Dolan
Comments:
Comment Date: 06/13/2023 User: SHANBERG_V
Description: referral
12/29/2022 Violation Open Shanberg, Vincent J
Significance: Minor Status: Open
Criteria ID: 7094
Rule: 62-762.711(1)
12/29/2022 Violation Open Shanberg, Vincent J
Significance: Minor Status: Open
Criteria ID: 7002
Rule: 62-762.401(1)(b), 62-762.401(2), 62-762.401(3), 62-762.401(3)(a), 62-762.401(3)(b), 62-762.401(3)(c)
12/29/2022 Violation Open Shanberg, Vincent J
Significance: SNC-A Status: Open
Criteria ID: 7010
Rule: 62-762.421(2), 62-762.421(3)(c)
12/29/2022 Violation Open Shanberg, Vincent J
Significance: Minor Status: Open
Criteria ID: 7072
Rule: 62-762.601(7), 62-762.602(7)
12/29/2022 Violation Open Shanberg, Vincent J
Significance: Minor Status: Open
Criteria ID: 7041
Rule: 62-762.501(2)(e)3, 62-762.501(2)(e)3.a, 62-762.501(2)(e)3.b, 62-762.501(2)(e)4, 62-762.502(2)(e)4, 62-762.502(2)(e)4.a, 62-762.502(2)(e)4.b, 62-762.502(2)(e)5
05/03/2022 Site Inspection Activity Closed Marconi, Erica L
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/03/2022
Activity Closed Date: 05/24/2023 Activity Closed By: SHANBERG_V
Events:
Event Type: Activity has been finished Date: 05/24/2023
Comment: Finished
Comments:
Comment Date: 12/29/2022 User: PARDAL_L
Description: A Routine Compliance Inspection was conducted on May 3, 2022, with Erica Marconi, Environmental Specialist III, with the Florida Department of Environmental Protection, Marathon Office, Eduardo Perez Assistant Director of Engineering at Ocean Reef Club, Erika Torres, Airport Manager at Ocean Reef Club, and Ryan Doty, Airport Operations Manager at Ocean Reef Club. Laura Pardal, Environmental Specialist II (records coordinator) with the Florida Department of Environmental Protection, Marathon Office. The facility has one (1) 12,000-gallon Jet Fuel aboveground storage tank and one (1) dispenser. Monthly visual inspection documentation was available from November 2019 to May 2022. The following violations have been cited: Missing overfill protection device annual operability testing documentation for 2020, 2021, and 2022. Missing release detection annual operability testing documentation for 2020, 2021, and 2022. Permanent records not available within 5 working days notice. Missing visual monthly monitoring documentation for 2020, 2021, and 2022. Missing financial responsibility documentation for 2020, 2021, and 2022. Failure to update registration with correct facility contact information. A copy of the report will be sent via electronic mail to Ryan Doty (rdoty@oceanreef.com), Erika Torres (ertorres@oceanreef.com), and Eduardo Perez (eperez@oceanreef.com).
06/16/2020 Attachment Winkler, Michael G.
10/02/2019 Editable Letter Activity Winkler, Michael G.
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 10/02/2019
Comment: Finished
Events:
Event Type: Document has been sent Date: 10/02/2019
Comment: Sent
Attachments:
Attachment Date: 10/02/2019 User: WINKLER_MG_1
Description: 2019-10-02 RTC sent to Ryan Doty
View Attachment
10/02/2019 Record Document Activity Winkler, Michael G.
Activity Status: Closed
Contact Name: Ryan Doty Activity Closed Date: 10/02/2019
Events:
Event Type: Activity has been finished Date: 10/02/2019
Comment: Finished
11/15/2018 Violation Closed Winkler, Michael G.
Significance: Minor Status: Closed
Criteria ID: 5114
Rule: 62-762.701(1), 62-762.701(1)(a), 62-762.701(1)(a)1., 62-762.701(1)(a)2., 62-762.701(1)(a)3.
11/15/2018 Editable Letter Activity Winkler, Michael G.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Compliance Assistance Correspondence Date: 11/16/2018
Comment: Compliance Assistance Correspondence
Events:
Event Type: Activity has been finished Date: 11/16/2018
Comment: Finished
Attachments:
Attachment Date: 11/16/2018 User: WINKLER_MG_1
Description: 2018-11-16 CAO sent to Erika Torres
View Attachment
11/14/2018 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 11/14/2018
Activity Closed Date: 11/15/2018 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 11/15/2018
Comment: Finished
Comments:
Comment Date: 11/15/2018 User: WINKLER_MG_1
Description: Met Erika Torres and walked through the system with Ryan Doty of Ocean Reef Airport Operations. This is a 12K gallon double walled AST with Jet A and aboveground piping to two tarmac dispensers. This location was affected by hurricane Irma and records prior to fall 2017 were not available. The AST is repainted and in good condition, and was checked by Abacon post-storm. The Greenleaf Solar gauge alarm test would not sound, nor were current (1 year) testing records of the device available. The facility is directed to repair or replace the device, and submit an operability test of the device indicating, at a minimum, that it operates as designed. The test should include a current "Overfill Alarm" test, and test of the tank interstice gauge. Results may be sent to Michael.Winkler@FLHealth.gov
06/09/2016 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/09/2016
Activity Closed Date: 06/09/2016 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 06/09/2016
Comment: Finished
Comments:
Comment Date: 06/09/2016 User: WINKLER_MG_1
Description: This is a 12K Gallon DW AST with Jet A for service at the Ocean Reef Airport. An ATG monitors high, low, and interstitial sensors. No violations are noted this date.
08/28/2014 Comment Winkler, Michael G.
Description: Erika Torres 305-367-3690
08/28/2014 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/28/2014
Activity Closed Date: 08/28/2014 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 08/28/2014
Comment: Finished
Comments:
Comment Date: 08/28/2014 User: WINKLER_MG_1
Description: This is a 12,000gal DW AST with Jet A. No deficiencies noted this date.
10/01/2013 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/01/2013
Activity Closed Date: 10/25/2013 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 10/25/2013
Comment: Finished
Comments:
Comment Date: 10/25/2013 User: WINKLER_MG_1
Description: The facility upgraded from an 8,000 gallon DW AST to a 12,000 gallon AST. Fuel Tech removed the previous tank. There is no evidence of staining or a previous discharge at the location. The new AST was installed in the same place the previous tank had been installed.
10/01/2013 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/01/2013
Activity Closed Date: 10/25/2013 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 10/25/2013
Comment: Finished
Comments:
Comment Date: 10/25/2013 User: WINKLER_MG_1
Description: The facility upgraded from an 8,000 gallon DW AST to a 12,000 gallon AST EQ# 352. Fuel Tech removed the previous tank and installed this one. There is no evidence of staining or a previous discharge at the location. The new AST was installed in the same place the previous tank had been installed. All EQ numbers are on page 4 of the install documents. Installed: A 12K gal DW AST for Jet A, with spill bucket, tight fill port, suction AG piping, and a Solar brand ATG for interstice and overfill monitoring. The hose reel is contained in a dispenser pan cabinet.
07/18/2012 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/18/2012
Activity Closed Date: 07/19/2012 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 07/19/2012
Comment: Finished
Comments:
Comment Date: 07/18/2012 User: WINKLER_MG_1
Description: NOTE: The annular operability test for the interstice sensor is not very clear. Please review that it is getting an annual test and the result is recorded.
10/20/2011 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/20/2011
Activity Closed Date: 10/26/2011 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 10/26/2011
Comment: Finished
Comments:
Comment Date: 10/20/2011 User: WINKLER_MG_1
Description: Fuel Tech PCC 1256831 installed an 8000 gal DW Steel Modern Welding Fireguard AST (EQ#352) with an ATG for the annular space, fuel level gauge, and overfill protection. AG SW piping and suction.
Comments:
Comment Date: 10/26/2011 User: WINKLER_MG_1
Description: NOTE: Post placard when it arrives.
10/20/2011 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/20/2011
Activity Closed Date: 10/26/2011 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 10/26/2011
Comment: Finished
Comments:
Comment Date: 10/20/2011 User: WINKLER_MG_1
Description: Fuel Tech PCC 1256831 installed an 8000 gal DW Steel Modern Welding Fireguard AST (EQ#352) with an ATG for the annular space, fuel level gauge, and overfill protection. AG SW piping and suction.
Comments:
Comment Date: 10/26/2011 User: WINKLER_MG_1
Description: NOTE: Post placard when it arrives.