Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Journal Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
Facility ID: | 8942860 | ||||||||||
Facility Name: | EICHER GREG | ||||||||||
06/29/2021 | Enforcement Tracking Activity | Gillman, Mark | |||||||||
Activity Status: | Open | ||||||||||
06/11/2021 | Violation Open | Wilson, Monica L | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 5042 | ||||||||||
Rule: | 62-762.501(2)(e), 62-762.501(2)(e)1., 62-762.501(2)(e)2., 62-762.501(2)(e)2.a., 62-762.501(2)(e)2.b., 62-762.501(2)(e)2.c., 62-762.501(2)(e)2.d., 62-762.501(2)(e)3. | ||||||||||
06/11/2021 | Issue Document Activity | Wilson, Monica L | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: |
rogator1064@yahoo.com; Gillman, Mark |
Activity Closed Date: | 06/11/2021 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/11/2021 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/11/2021 | User: | WILSON_ML_1 | ||||||||
Description: | Greetings, I have attached the above referenced facility’s Compliance Assistance Offer Letter and Inspection Report. Please be sure to submit the information needed to resolve the violations to this office as soon as possible to avoid possible penalties. Please feel free to contact this office should you have any questions or concerns. Kind Regards, Monica L. Wilson Planning Consultant I Florida Department of Health in Escambia County Environment Health Division 1300 W Gregory Street, Pensacola, Florida 32502 Phone: 850-595-6700 ext 2004 Cell: 850-554-4315 Fax: 850-595-6774 www.EscambiaHealth.com Follow us on Twitter: @HealthyEscambia The Department’s mission is to protect, and improve the health of all people in Florida through integrated state, county, and community efforts NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure. | ||||||||||
06/11/2021 | Editable Letter Activity | Wilson, Monica L | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 06/11/2021 | ||||||||
Comment: | Sent | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/11/2021 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 06/11/2021 | User: | WILSON_ML_1 | ||||||||
Description: | Compliance Assistance Offer Letter | ||||||||||
View Attachment | |||||||||||
06/11/2021 | Enforcement Referral Activity | Wilson, Monica L | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 06/29/2021 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 06/11/2021 | ||||||||
Comment: | Submitted for approval by: Monica L Wilson: This is an immediate referral to Enforcement for receiving fuel without a current Storage Tank Registration Placard and the Release Detection Method for 2 of the tanks (12,000 gallon and Pole Barn Tank) cannot be determined. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/29/2021 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 06/29/2021 | ||||||||
Comment: | Assigned to Mark Gillman | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 06/29/2021 | ||||||||
Comment: | Accepted by Mark Gillman: Accepted | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 06/29/2021 | ||||||||
Comment: | Acknowledged and Assigned by Mark Gillman | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/11/2021 | User: | WILSON_ML_1 | ||||||||
Description: | This is an immediate referral to Enforcement for receiving fuel without a current Storage Tank Registration Placard and the Release Detection Method for 2 of the tanks (12,000 gallon and Pole Barn Tank) cannot be determined. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/11/2021 | User: | WILSON_ML_1 | ||||||||
Description: | This is an immediate referral to Enforcement for receiving fuel without a current Storage Tank Registration Placard and the Release Detection Method for 2 of the tanks (12,000 gallon and Pole Barn Tank) cannot be determined. | ||||||||||
06/11/2021 | Enforcement Referral Activity | Wilson, Monica L | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 06/29/2021 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 06/11/2021 | ||||||||
Comment: | Submitted for approval by: Monica L Wilson: This is an immediate referral to Enforcement for receiving fuel without a current Storage Tank Registration Placard and the Release Detection Method for 2 of the tanks (12,000 gallon and Pole Barn Tank) cannot be determined. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/29/2021 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 06/29/2021 | ||||||||
Comment: | Assigned to Mark Gillman | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 06/29/2021 | ||||||||
Comment: | Accepted by Mark Gillman: Accepted | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 06/29/2021 | ||||||||
Comment: | Acknowledged and Assigned by Mark Gillman | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/11/2021 | User: | WILSON_ML_1 | ||||||||
Description: | This is an immediate referral to Enforcement for receiving fuel without a current Storage Tank Registration Placard and the Release Detection Method for 2 of the tanks (12,000 gallon and Pole Barn Tank) cannot be determined. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/11/2021 | User: | WILSON_ML_1 | ||||||||
Description: | This is an immediate referral to Enforcement for receiving fuel without a current Storage Tank Registration Placard and the Release Detection Method for 2 of the tanks (12,000 gallon and Pole Barn Tank) cannot be determined. | ||||||||||
06/11/2021 | Violation Open | Wilson, Monica L | |||||||||
Significance: | SNC-A | Status: | Open | ||||||||
Criteria ID: | 5093 | ||||||||||
Rule: | 62-762.601(1), 62-762.601(1)(a), 62-762.601(1)(b), 62-762.601(1)(c) | ||||||||||
06/11/2021 | Violation Open | Wilson, Monica L | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 5034 | ||||||||||
Rule: | 62-762.501(1)(h), 62-762.501(1)(h)1., 62-762.501(1)(h)2., 62-762.501(1)(h)3., 62-762.501(1)(h)4. | ||||||||||
06/11/2021 | Violation Open | Wilson, Monica L | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 4045 | ||||||||||
Rule: | 62-761.500(4), 62-761.500(4)(a) | ||||||||||
06/09/2021 | Violation Open | Wilson, Monica L | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 5011 | ||||||||||
Rule: | 62-762.421(2) | ||||||||||
06/09/2021 | Violation Open | Wilson, Monica L | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 5005 | ||||||||||
Rule: | 62-762.401(5) | ||||||||||
06/09/2021 | Violation Open | Wilson, Monica L | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 5027 | ||||||||||
Rule: | 62-762.501(1)(b)10., 62-762.501(1)(b)11., 62-762.501(1)(b)8., 62-762.501(1)(b)9. | ||||||||||
06/09/2021 | Violation Open | Wilson, Monica L | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 5003 | ||||||||||
Rule: | 62-762.401(3), 62-762.401(3)(a), 62-762.401(3)(b), 62-762.401(3)(c) | ||||||||||
06/09/2021 | Violation Open | Wilson, Monica L | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 5032 | ||||||||||
Rule: | 62-762.501(1)(f) | ||||||||||
06/09/2021 | Violation Open | Wilson, Monica L | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 5114 | ||||||||||
Rule: | 62-762.701(1), 62-762.701(1)(a), 62-762.701(1)(a)1., 62-762.701(1)(a)2., 62-762.701(1)(a)3. | ||||||||||
06/08/2021 | Site Inspection Activity Closed | Wilson, Monica L | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 06/08/2021 | ||||||||||
Activity Closed Date: | 06/11/2021 | Activity Closed By: | WILSON_ML_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/11/2021 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/08/2021 | User: | WILSON_ML_1 | ||||||||
Description: | A notice to verify regulated size aboveground storage tanks (AST) was brought to our department's attention by the Petroleum Cleanup Site Manager. Two tanks that were of regulated size were documented as being on site at the facility at a Petroleum Restoration Site Visit conducted on 05/20/2020. The facility is in the process of getting an Site Rehabilitation Completion Order once the Well Abandonment occurs but the registration has to be updated with the corrected address and all regulated tanks need to be registered before the order can be issued. Three regulated size ASTs were noted at the time of inspection. Two of the three tanks can be seen from the road. The third tank is within the pole barn that houses the tractors for the farm. Tanks closet to the Road: One tank appears to be about 12,000 gallons and the other appears to be 2,000 installed on a concrete slab. The 2,000 gallon tank did not appear to be in use as the piping was disconnected and there was not a pump or dispenser hose installed. The tank had a valve at the bottom to check the interstice. The tank did have surface rust starting to form. The 12,000 gallon Alabama Tank containing Red Dyed Diesel. The AST had a pump that was connected to a generator on the ground with a dispenser hose connected to the pump. The piping from the tank to the dispenser pump, closest to the elbow at the tank had 3 active leaks at 3 connection points along the piping that was dripping on the concrete slab. Product has accumulated and stained the surrounding concrete. The fill ports for both tanks were positioned on top of 5 gallon buckets. The tank is equipped with vents and emergency vents. There did not appear to be any overfill or release detection device installed on the tank. The tank is coated in rust that needs to be removed and a rust preventative paint applied to the tank. Tank at Pole Barn: Tank appears to be about 1,000 to 1,500 gallons. It is equipped with a top of tank Fill-Rite pump, Krueger Fuel Level gauge and emergency vent. There is no spill/fill containment bucket at the fill port, vent or release detection device. The tank pump is equipped to be easily hooked up with a battery when the pump is needed for use. Spoke with Mr. Wesley Wiggins regarding having the 3 ASTs registered and the address updated to reflect 1931 S Hwy 99 (Currently registered as N Hwy 99). We also discussed what needs to be done to bring the tanks into compliance. A registration form with instructions was left with Mr. Wiggins to fill out and submit back to our office for review. Once we receive the registration form back, we will submit to Tank Registration for processing. Per Mr. Wiggins, the fuel supplier is Davison Fuels. Contact: Wesley Wiggins rogator1064@yahoo.com 850-776-3001 Davison Fuels Tom Kelly tkelly@davisonfuels.com 850-380-5143 |