Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Journal Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
Facility ID: | 9811545 | ||||||||||
Facility Name: | FL STATE UNIV-CONFERENCE CTR | ||||||||||
01/10/2025 | Enforcement Tracking Activity | Gillman, Mark | |||||||||
Activity Status: | Open | ||||||||||
01/07/2025 | Comment | Merritt, Sara | |||||||||
Description: | POC - Renee Murray Environmental Manager, Chemical Safety Officer 850-644-7682 rrmurray@admin.fsu.edu, rrmurray@fsu.edu | ||||||||||
12/10/2024 | Enforcement Referral Activity | French, Edwin C. | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 01/10/2025 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/10/2025 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 01/10/2025 | ||||||||
Comment: | Accepted by Mark Gillman: Accept | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 01/10/2025 | ||||||||
Comment: | Assigned to Mark Gillman | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 12/10/2024 | ||||||||
Comment: | Submitted for approval by: Edwin C. French: Chronology: Inspected on 7/30/24; NCLI and report sent 7/30/24; The facility has corresponded and stated the AST is to be replaced in the spring of 2025. | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 01/10/2025 | ||||||||
Comment: | Acknowledged and Assigned by Mark Gillman | ||||||||||
Comments: | |||||||||||
Comment Date: | 12/10/2024 | User: | FRENCH_EC_1 | ||||||||
Description: | Chronology: Inspected on 7/30/24; NCLI and report sent 7/30/24; The facility has corresponded and stated the AST is to be replaced in the spring of 2025. | ||||||||||
Comments: | |||||||||||
Comment Date: | 12/10/2024 | User: | FRENCH_EC_1 | ||||||||
Description: | Chronology: Inspected on 7/30/24; NCLI and report sent 7/30/24; The facility has corresponded and stated the AST is to be replaced in the spring of 2025. | ||||||||||
12/10/2024 | Enforcement Referral Activity | French, Edwin C. | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 01/10/2025 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/10/2025 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 01/10/2025 | ||||||||
Comment: | Accepted by Mark Gillman: Accept | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 01/10/2025 | ||||||||
Comment: | Assigned to Mark Gillman | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 12/10/2024 | ||||||||
Comment: | Submitted for approval by: Edwin C. French: Chronology: Inspected on 7/30/24; NCLI and report sent 7/30/24; The facility has corresponded and stated the AST is to be replaced in the spring of 2025. | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 01/10/2025 | ||||||||
Comment: | Acknowledged and Assigned by Mark Gillman | ||||||||||
Comments: | |||||||||||
Comment Date: | 12/10/2024 | User: | FRENCH_EC_1 | ||||||||
Description: | Chronology: Inspected on 7/30/24; NCLI and report sent 7/30/24; The facility has corresponded and stated the AST is to be replaced in the spring of 2025. | ||||||||||
Comments: | |||||||||||
Comment Date: | 12/10/2024 | User: | FRENCH_EC_1 | ||||||||
Description: | Chronology: Inspected on 7/30/24; NCLI and report sent 7/30/24; The facility has corresponded and stated the AST is to be replaced in the spring of 2025. | ||||||||||
07/30/2024 | Attachment | Hatcher, Dennis J. | |||||||||
07/30/2024 | Editable Letter Activity | Hatcher, Dennis J. | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 07/30/2024 | ||||||||
Comment: | Sent | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/30/2024 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 07/30/2024 | User: | HATCHER_JD_1 | ||||||||
Description: | CA Letter | ||||||||||
View Attachment | |||||||||||
07/30/2024 | Site Inspection Activity Closed | Hatcher, Dennis J. | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 07/23/2024 | ||||||||||
Activity Closed Date: | 07/30/2024 | Activity Closed By: | HATCHER_JD_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/30/2024 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 07/30/2024 | User: | HATCHER_JD_1 | ||||||||
Description: | Inspection Performed on. 7/23/24 Placard: ok FR: Exempt. State facility. CFR: n/a Monthly visuals: Provided and current . Annual operability: Rupture basin sensor. ok Overfill: Krueger site gauge Anti-siphon: n/a Tank: ok. Generator w/base tank. Top of tank is badly corroded. Violation added. Containment area: n/a Spill bucket: ok Dispenser/Hose: n/a Leak Detection: Electronic interstitial sensor. Monthly visuals of AST system. Met with Renee Murray. Facility Contact. Site visit were performed on all FSU facilities. Major construction all over campus. Did not open each facility in First during the inspections. Noted each tank by 1-34 numbers and took pics for each and noted any violations with pics and tank number for later entry into First. No signature by Renee Murray was obtained. | ||||||||||
07/30/2024 | Violation Open | Hatcher, Dennis J. | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7030 | ||||||||||
Rule: | 62-762.501(1)(f), 62-762.502(1)(f) | ||||||||||
08/25/2021 | Site Inspection Activity Closed | Hatcher, Dennis J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/04/2021 | ||||||||||
Activity Closed Date: | 08/25/2021 | Activity Closed By: | HATCHER_JD_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/25/2021 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/25/2021 | User: | HATCHER_JD_1 | ||||||||
Description: | Inspection Performed on. 8/4/2021 Placard: ok FR: Exempt. State facility. CFR: n/a Monthly visuals: Provided and current . Annual operability: Rupture basin sensor. ok Overfill: Krueger site gauge Anti-siphon: n/a Tank: ok. Generator w/base tank Containment area: n/a Spill bucket: ok Dispenser/Hose: n/a Leak Detection: Electronic interstitial sensor. Monthly visuals of AST system. | ||||||||||
07/18/2019 | Site Inspection Activity Closed | French, Edwin C. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 07/18/2019 | ||||||||||
Activity Closed Date: | 07/24/2019 | Activity Closed By: | FRENCH_EC_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/24/2019 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 07/18/2019 | User: | FRENCH_EC_1 | ||||||||
Description: | Performed inspect on: 7/24/19 Placard: Posted & current Monthlys: Provided & current Annual Operability: Provided & current Overfill: in-place Anti-siphon: NA Tank1: OK Containment Area: NA Spill Buckets: OK Piping: OK Leak Detection: monthly visual, Electronic interstice check, DW. | ||||||||||
12/19/2017 | Site Inspection Activity Closed | Hatcher, Dennis J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 12/19/2017 | ||||||||||
Activity Closed Date: | 01/16/2018 | Activity Closed By: | HATCHER_JD_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/16/2018 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 12/19/2017 | User: | HATCHER_JD_1 | ||||||||
Description: | Inspection Performed on. 12/19/2017 Placard: ok FR: Exempt. State facility. CFR: n/a RDRL: ok Monthly visuals: Provided and current . Annual operability: Rupture basin sensor. ok Overfill: Krueger site gauge Anti-siphon: n/a Tank: ok. Generator w/base tank Containment area: n/a Spill bucket: ok Dispenser/Hose: n/a Leak Detection: Electronic interstitial sensor. Monthly visuals of AST system. | ||||||||||
07/15/2016 | Site Inspection Activity Closed | Hatcher, Dennis J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 07/15/2016 | ||||||||||
Activity Closed Date: | 07/15/2016 | Activity Closed By: | HATCHER_JD_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/15/2016 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 07/15/2016 | User: | HATCHER_JD_1 | ||||||||
Description: | Inspection Performed on. 7/15/2016 Placard: ok FR: Exempt. State facility. CFR: n/a RDRL: ok Monthly visuals: Provided and current. Annual operability: Rupture basin sensor. ok Overfill: Krueger site gauge Anti-siphon: n/a Tank: ok. Generator w/base tank Containment area: n/a Spill bucket: ok Dispenser/Hose: n/a Leak Detection: Electronic interstitial sensor. Monthly visuals of AST system. | ||||||||||
08/11/2015 | Site Inspection Activity Closed | Hatcher, Dennis J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/11/2015 | ||||||||||
Activity Closed Date: | 08/20/2015 | Activity Closed By: | HATCHER_JD_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/20/2015 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/20/2015 | User: | HATCHER_JD_1 | ||||||||
Description: | Inspection Performed on. 8/11/2015 Placard: ok . New 2015/16 not sent yet but invoice has been paid. FR: Exempt. State facility. CFR: n/a RDRL: ok Monthly visuals: Provided and current. Annual operability: Rupture basin sensor. ok Overfill: Krueger site gauge Anti-siphon: n/a Tank: ok. Generator w/base tank Containment area: n/a Spill bucket: ok Dispenser/Hose: n/a Leak Detection: Electronic interstitial sensor. Monthly visuals of AST system. | ||||||||||
08/05/2014 | Site Inspection Activity Closed | Hatcher, Dennis J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/05/2014 | ||||||||||
Activity Closed Date: | 08/05/2014 | Activity Closed By: | HATCHER_JD_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/05/2014 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/05/2014 | User: | HATCHER_JD_1 | ||||||||
Description: | Inspection Performed on. 8/5/2014 Placard: ok . New 2015 not sent yet but invoice has been paid. FR: Exempt. State facility. CFR: n/a RDRL: ok Monthly visuals: Provided and current. Annual operability: Rupture basin sensor. ok Overfill: Krueger Site gauge. Anti-siphon: n/a Tank: ok. Generator w/base tank Containment area: n/a Spill bucket: ok Dispenser/Hose: n/a Leak Detection: interstitial sensor. Monthly visuals of AST system. | ||||||||||
08/02/2013 | Site Inspection Activity Closed | Hatcher, Dennis J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 07/16/2013 | ||||||||||
Activity Closed Date: | 08/02/2013 | Activity Closed By: | HATCHER_JD_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/02/2013 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/02/2013 | User: | HATCHER_JD_1 | ||||||||
Description: | Inspection Performed on. 7/16/2013 Placard: ok FR: Exempt. State facility. CFR: n/a RDRL: ok Monthly visuals: Provided and current. Annual operability: Rupture basin sensor. ok Overfill: Sentry site gauge. Anti-siphon:n/a Tank: ok Containment area: n/a Spill bucket: ok Dispenser/Hose: n/a Leak Detection: Electronic rupture basin alarm. Monthly visuals of AST system. First computer was at DEP being repaired. Facility rep signature was not obtained at inspection. | ||||||||||
08/20/2012 | Site Inspection Activity Closed | Hatcher, Dennis J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/14/2012 | ||||||||||
Activity Closed Date: | 08/20/2012 | Activity Closed By: | HATCHER_JD_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/20/2012 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/20/2012 | User: | HATCHER_JD_1 | ||||||||
Description: | Inspection Comments Performed inspect on: 8/14/2012 Placard: ok FR: exempt CFR:exempt RDRL: OK Monthlys: ok Annual Operability: ok Overfill:Krueger Site gauge. Anti-siphon: N/A Tank1: OK Containment Area:n/a Spill Buckets: OK Dispensers/Hoses:n/a Leak Detection: Electronic rupture basin alarm and monthly visual inspections | ||||||||||
08/26/2011 | Site Inspection Activity Closed | Hatcher, Dennis J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/25/2011 | ||||||||||
Activity Closed Date: | 08/29/2011 | Activity Closed By: | HATCHER_JD_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/29/2011 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/29/2011 | User: | HATCHER_JD_1 | ||||||||
Description: | Performed inspect on: 8/25/2011 Placard: ok FR: exempt CFR: n/a RDRL: ok Monthlys: ok Annual Operability: ok Overfill: Kreuger Site gauge. Anti-siphon: N/A Tank1: Generator w/base tank. ok Containment Area: n/a Spill Buckets: ok Dispensers/Hoses: n/a Leak Detection: Electronic interstitial sensor and monthly visuals of AST system. | ||||||||||
07/29/2010 | Site Inspection Activity Closed | Hatcher, Dennis J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 07/20/2010 | ||||||||||
Activity Closed Date: | 07/29/2010 | Activity Closed By: | HATCHER_JD_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/29/2010 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 07/29/2010 | User: | HATCHER_JD_1 | ||||||||
Description: | Performed inspect on:7/20/2010 Placard:New placard not yet received. PO cut. FR:ok RDRL:ok Monthlys:ok Overfill:site gauge Tank1:Generator w/base tank. ok Tank2:n/a Piping:n/a Containment Area:n/a Spill Buckets:ok Dispensers/Hoses:n/a Leak Detection: Electronic rupture basin alarm and monthly visuals. |