DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 03/13/2025        Last Data Refresh: 03/12/2025        Report Generated from DOPPLER
 
Facility ID: 9815093
Facility Name: ASPIRE AT BRADENTON
 
09/24/2024 Enforcement Tracking Activity hernandez, emmanuel
Activity Status: Open
09/19/2024 Enforcement Referral Activity Shanberg, Vincent
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 09/24/2024
Events:
Event Type: Activity/Document was acknowledged on this date Date: 09/19/2024
Comment: Acknowledged and Assigned by Jayme Brock
Events:
Event Type: Activity has been submitted for approval Date: 09/19/2024
Comment: Submitted for approval by: Vincent Shanberg: Referral 90days
Events:
Event Type: Activity has been finished Date: 09/24/2024
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 09/24/2024
Comment: Accepted by emmanuel hernandez: Assignment accepted
Events:
Event Type: Activity has been assigned Date: 09/19/2024
Comment: Assigned to emmanuel hernandez
Comments:
Comment Date: 09/19/2024 User: SHANBERG_VJ_1
Description: Referral 90days
Attachments:
Attachment Date: 09/19/2024 User: SHANBERG_VJ_1
Description: Enforcement Referral Form SWD - 9-19-2024
View Attachment
Attachments:
Attachment Date: 09/19/2024 User: SHANBERG_VJ_1
Description: Sunbiz_ASPIRE AT BRADENTON_9815093
View Attachment
Attachments:
Attachment Date: 09/19/2024 User: SHANBERG_VJ_1
Description: MC Property Appraiser Sheet_ASPIRE AT BRADENTON_9815093
View Attachment
09/19/2024 Electronic Communication Activity Shanberg, Vincent
Activity Closed Date: 09/19/2024 Activity Status: Closed
Date: 09/19/2024
Recipient: Luis (plantops@aspirebradenton.com) and tmagid@aspirehealthgrp.com
Sender: vincent.shanberg@mymanatee.org
Subject: Manatee County Follow up on CAO_ASPIRE AT BRADENTON._9815093
Message: Good afternoon, Have these violations been addressed? Please contact me with any questions. Thanks, Vincent Shanberg Sr. Environmental Specialist Environmental Protection Division Natural Resource Department 1501 Dam Road Bradenton, FL 34212 vincent.shanberg@mymanatee.org O: 941-742-5980 ext. 1880 C: 941-290-8004
Events:
Event Type: Activity has been finished Date: 09/19/2024
Comment: Finished
09/19/2024 Electronic Communication Activity Shanberg, Vincent
Activity Closed Date: 09/19/2024 Activity Status: Closed
Date: 09/19/2024
Recipient: Luis (plantops@aspirebradenton.com) and tmagid@aspirehealthgrp.com
Sender: vincent.shanberg@mymanatee.org
Subject: Manatee County Follow up on CAO_ASPIRE AT BRADENTON._9815093
Message: SEE Email Attached
Events:
Event Type: Activity has been finished Date: 09/19/2024
Comment: Finished
Attachments:
Attachment Date: 09/19/2024 User: SHANBERG_VJ_1
Description: 9815093_ Follow up CAO Email_9-10-24
View Attachment
09/19/2024 Electronic Communication Activity Shanberg, Vincent
Activity Closed Date: 09/19/2024 Activity Status: Closed
Date: 09/19/2024
Recipient: Luis (plantops@aspirebradenton.com)
Sender: Mark Trethewey
Subject: Follow up Installation Inspection Report
Message: Good morning ,Luis, Here is a copy of the inspection performed 6/14. Most of these issues can be resolved via E-mail. After next week, please contact Vincent at Vincent.shanberg@mymanatee.com Thank you, Mark Trethewey Natural Resources Department Environmental Protection Division Senior Environmental Specialist 1501 Dam Road Bradenton, FL 34212 (941)742-5980 ext. 1880
Events:
Event Type: Activity has been finished Date: 09/19/2024
Comment: Finished
09/19/2024 Phone Conversation Activity Shanberg, Vincent
Call Type: Incoming Activity Status: Closed
Call Recipient: Luis
Phone Number: (727) 916-0726 Activity Closed Date: 09/19/2024
Subject: Would like an email of the violations and how to resolve them.
Events:
Event Type: Activity has been finished Date: 09/19/2024
Comment: Finished
06/19/2024 Attachment Trethewey, Mark B.
06/19/2024 Editable Letter Activity Trethewey, Mark B.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/19/2024
Comment: Finished
Events:
Event Type: Document has been sent Date: 06/19/2024
Comment: Sent
Attachments:
Attachment Date: 06/19/2024 User: TRETHEWEY_MB_1
Description: CAO 2023-2024.070
View Attachment
06/19/2024 Attachment Trethewey, Mark B.
06/19/2024 Attachment Trethewey, Mark B.
06/19/2024 Violation Open Trethewey, Mark B.
Significance: Minor Status: Open
Criteria ID: 7072
Rule: 62-762.601(7), 62-762.602(7)
06/19/2024 Violation Open Trethewey, Mark B.
Significance: SNC-B Status: Open
Criteria ID: 7009
Rule: 62-762.421(2), 62-762.421(3)(c)
06/19/2024 Violation Open Trethewey, Mark B.
Significance: Minor Status: Open
Criteria ID: 7041
Rule: 62-762.501(2)(e)3, 62-762.501(2)(e)3.a, 62-762.501(2)(e)3.b, 62-762.501(2)(e)4, 62-762.502(2)(e)4, 62-762.502(2)(e)4.a, 62-762.502(2)(e)4.b, 62-762.502(2)(e)5
06/19/2024 Violation Open Trethewey, Mark B.
Significance: SNC-B Status: Open
Criteria ID: 7042
Rule: 62-762.501(2)(f), 62-762.501(2)(f)1, 62-762.502(2)(f)
06/19/2024 Violation Open Trethewey, Mark B.
Significance: Minor Status: Open
Criteria ID: 7005
Rule: 62-762.411(1)(b), 62-762.411(1)(c), 62-762.411(2)(a), 62-762.411(2)(b), 62-762.411(2)(c)
06/19/2024 Violation Open Trethewey, Mark B.
Significance: Minor Status: Open
Criteria ID: 7094
Rule: 62-762.711(1)
06/19/2024 Violation Open Trethewey, Mark B.
Significance: SNC-B Status: Open
Criteria ID: 7075
Rule: 62-762.701(1), 62-762.701(1)(a), 62-762.701(1)(a)1, 62-762.701(1)(a)2, 62-762.701(1)(a)3, 62-762.702(1), 62-762.702(1)(a), 62-762.702(1)(a)1, 62-762.702(1)(a)2, 62-762.702(1)(a)3
06/19/2024 Violation Open Trethewey, Mark B.
Significance: Minor Status: Open
Criteria ID: 7002
Rule: 62-762.401(1)(b), 62-762.401(2), 62-762.401(3), 62-762.401(3)(a), 62-762.401(3)(b), 62-762.401(3)(c)
06/18/2024 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 06/14/2024
Activity Closed Date: 06/19/2024 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 06/19/2024
Comment: Finished
Comments:
Comment Date: 06/19/2024 User: TRETHEWEY_MB_1
Description: Facility ID#: 41 / 9815093 Inspection start date: 6/14/2024 Facility Name: Bay Vue Nursing (Last registered name) Installation Inspection Field Notes SITE VISITS: 6/14/2024 – Mark Trethewey on-site at 2:30PM. Installer: Unknown Activities: Upon Facility number review it was discovered that Tank #1 had been originally registered as “Hazardous Substance” and therefore did not populate to a regulated AST list. A site visit confirmed the tank was a regulated system (generator fuel). Upon arrival, it was discovered that a second gen-set had been installed. Although the install was observed by an unknown Manatee County representative, the Natural Resources Environmental Protection Division was not notified. Installations were not observed. Tank 1: Manufacturing info was not provided or available on the tank, system was registered in 2015 but appears to be older. Unknown install date. The tank appears to be UL-142 sub-base generator tank (EQ-969). There is no spill bucket attached, monitoring appears to be manual. The tank is in satisfactory condition with minor surface corrosion. Tank 2: Manufactured by: Advanced Manufacturing and Power Systems, Inc. 1965 Bennet Drive DeLand, FL 32724 386-822-5565 Model MH29522 UL D27750994 Manufacture Date: 11/6/2019. Unknown install date. 2400-gallon tank. Both are double-walled and set onto a concrete pad. Both have been put into service. Tank #2 still has vacuum on the interstice at -4. Overfill protection has not been established on either AST, if manual gauge ensure that no tank is filled beyond 90% capacity. FINANCIAL RESPONSIBILITY: Not provided. Provide Manatee County NRD with proof of Financial Responsibility indicating tank systems and Facility location. RELEASE DETECTION, as of 6/14/2024: a. Vacuum monitoring of the double-wall tank interstitial (TK2) manual monitoring (TK1). Manual overfill protection with gauged delivery on TK 1, High / low level gauge potential on TK2. b. Monthly visual inspections to be documented at least once a month not exceeding 35 days apart to include the tank exterior, spill containment and surrounding area.