Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Journal Report | |||||||||||
Report Run Date: 03/13/2025 Last Data Refresh: 03/12/2025 Report Generated from DOPPLER | |||||||||||
Facility ID: | 9815093 | ||||||||||
Facility Name: | ASPIRE AT BRADENTON | ||||||||||
09/24/2024 | Enforcement Tracking Activity | hernandez, emmanuel | |||||||||
Activity Status: | Open | ||||||||||
09/19/2024 | Enforcement Referral Activity | Shanberg, Vincent | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 09/24/2024 | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 09/19/2024 | ||||||||
Comment: | Acknowledged and Assigned by Jayme Brock | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 09/19/2024 | ||||||||
Comment: | Submitted for approval by: Vincent Shanberg: Referral 90days | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/24/2024 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 09/24/2024 | ||||||||
Comment: | Accepted by emmanuel hernandez: Assignment accepted | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 09/19/2024 | ||||||||
Comment: | Assigned to emmanuel hernandez | ||||||||||
Comments: | |||||||||||
Comment Date: | 09/19/2024 | User: | SHANBERG_VJ_1 | ||||||||
Description: | Referral 90days | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 09/19/2024 | User: | SHANBERG_VJ_1 | ||||||||
Description: | Enforcement Referral Form SWD - 9-19-2024 | ||||||||||
View Attachment | |||||||||||
Attachments: | |||||||||||
Attachment Date: | 09/19/2024 | User: | SHANBERG_VJ_1 | ||||||||
Description: | Sunbiz_ASPIRE AT BRADENTON_9815093 | ||||||||||
View Attachment | |||||||||||
Attachments: | |||||||||||
Attachment Date: | 09/19/2024 | User: | SHANBERG_VJ_1 | ||||||||
Description: | MC Property Appraiser Sheet_ASPIRE AT BRADENTON_9815093 | ||||||||||
View Attachment | |||||||||||
09/19/2024 | Electronic Communication Activity | Shanberg, Vincent | |||||||||
Activity Closed Date: | 09/19/2024 | Activity Status: | Closed | ||||||||
Date: | 09/19/2024 | ||||||||||
Recipient: | Luis (plantops@aspirebradenton.com) and tmagid@aspirehealthgrp.com | ||||||||||
Sender: | vincent.shanberg@mymanatee.org | ||||||||||
Subject: | Manatee County Follow up on CAO_ASPIRE AT BRADENTON._9815093 | ||||||||||
Message: | Good afternoon, Have these violations been addressed? Please contact me with any questions. Thanks, Vincent Shanberg Sr. Environmental Specialist Environmental Protection Division Natural Resource Department 1501 Dam Road Bradenton, FL 34212 vincent.shanberg@mymanatee.org O: 941-742-5980 ext. 1880 C: 941-290-8004 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/19/2024 | ||||||||
Comment: | Finished | ||||||||||
09/19/2024 | Electronic Communication Activity | Shanberg, Vincent | |||||||||
Activity Closed Date: | 09/19/2024 | Activity Status: | Closed | ||||||||
Date: | 09/19/2024 | ||||||||||
Recipient: | Luis (plantops@aspirebradenton.com) and tmagid@aspirehealthgrp.com | ||||||||||
Sender: | vincent.shanberg@mymanatee.org | ||||||||||
Subject: | Manatee County Follow up on CAO_ASPIRE AT BRADENTON._9815093 | ||||||||||
Message: | SEE Email Attached | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/19/2024 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 09/19/2024 | User: | SHANBERG_VJ_1 | ||||||||
Description: | 9815093_ Follow up CAO Email_9-10-24 | ||||||||||
View Attachment | |||||||||||
09/19/2024 | Electronic Communication Activity | Shanberg, Vincent | |||||||||
Activity Closed Date: | 09/19/2024 | Activity Status: | Closed | ||||||||
Date: | 09/19/2024 | ||||||||||
Recipient: | Luis (plantops@aspirebradenton.com) | ||||||||||
Sender: | Mark Trethewey | ||||||||||
Subject: | Follow up Installation Inspection Report | ||||||||||
Message: | Good morning ,Luis, Here is a copy of the inspection performed 6/14. Most of these issues can be resolved via E-mail. After next week, please contact Vincent at Vincent.shanberg@mymanatee.com Thank you, Mark Trethewey Natural Resources Department Environmental Protection Division Senior Environmental Specialist 1501 Dam Road Bradenton, FL 34212 (941)742-5980 ext. 1880 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/19/2024 | ||||||||
Comment: | Finished | ||||||||||
09/19/2024 | Phone Conversation Activity | Shanberg, Vincent | |||||||||
Call Type: | Incoming | Activity Status: | Closed | ||||||||
Call Recipient: | Luis | ||||||||||
Phone Number: | (727) 916-0726 | Activity Closed Date: | 09/19/2024 | ||||||||
Subject: | Would like an email of the violations and how to resolve them. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/19/2024 | ||||||||
Comment: | Finished | ||||||||||
06/19/2024 | Attachment | Trethewey, Mark B. | |||||||||
06/19/2024 | Editable Letter Activity | Trethewey, Mark B. | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/19/2024 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 06/19/2024 | ||||||||
Comment: | Sent | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 06/19/2024 | User: | TRETHEWEY_MB_1 | ||||||||
Description: | CAO 2023-2024.070 | ||||||||||
View Attachment | |||||||||||
06/19/2024 | Attachment | Trethewey, Mark B. | |||||||||
06/19/2024 | Attachment | Trethewey, Mark B. | |||||||||
06/19/2024 | Violation Open | Trethewey, Mark B. | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7072 | ||||||||||
Rule: | 62-762.601(7), 62-762.602(7) | ||||||||||
06/19/2024 | Violation Open | Trethewey, Mark B. | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 7009 | ||||||||||
Rule: | 62-762.421(2), 62-762.421(3)(c) | ||||||||||
06/19/2024 | Violation Open | Trethewey, Mark B. | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7041 | ||||||||||
Rule: | 62-762.501(2)(e)3, 62-762.501(2)(e)3.a, 62-762.501(2)(e)3.b, 62-762.501(2)(e)4, 62-762.502(2)(e)4, 62-762.502(2)(e)4.a, 62-762.502(2)(e)4.b, 62-762.502(2)(e)5 | ||||||||||
06/19/2024 | Violation Open | Trethewey, Mark B. | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 7042 | ||||||||||
Rule: | 62-762.501(2)(f), 62-762.501(2)(f)1, 62-762.502(2)(f) | ||||||||||
06/19/2024 | Violation Open | Trethewey, Mark B. | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7005 | ||||||||||
Rule: | 62-762.411(1)(b), 62-762.411(1)(c), 62-762.411(2)(a), 62-762.411(2)(b), 62-762.411(2)(c) | ||||||||||
06/19/2024 | Violation Open | Trethewey, Mark B. | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7094 | ||||||||||
Rule: | 62-762.711(1) | ||||||||||
06/19/2024 | Violation Open | Trethewey, Mark B. | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 7075 | ||||||||||
Rule: | 62-762.701(1), 62-762.701(1)(a), 62-762.701(1)(a)1, 62-762.701(1)(a)2, 62-762.701(1)(a)3, 62-762.702(1), 62-762.702(1)(a), 62-762.702(1)(a)1, 62-762.702(1)(a)2, 62-762.702(1)(a)3 | ||||||||||
06/19/2024 | Violation Open | Trethewey, Mark B. | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7002 | ||||||||||
Rule: | 62-762.401(1)(b), 62-762.401(2), 62-762.401(3), 62-762.401(3)(a), 62-762.401(3)(b), 62-762.401(3)(c) | ||||||||||
06/18/2024 | Site Inspection Activity Closed | Trethewey, Mark B. | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 06/14/2024 | ||||||||||
Activity Closed Date: | 06/19/2024 | Activity Closed By: | TRETHEWEY_MB_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/19/2024 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2024 | User: | TRETHEWEY_MB_1 | ||||||||
Description: | Facility ID#: 41 / 9815093 Inspection start date: 6/14/2024 Facility Name: Bay Vue Nursing (Last registered name) Installation Inspection Field Notes SITE VISITS: 6/14/2024 – Mark Trethewey on-site at 2:30PM. Installer: Unknown Activities: Upon Facility number review it was discovered that Tank #1 had been originally registered as “Hazardous Substance” and therefore did not populate to a regulated AST list. A site visit confirmed the tank was a regulated system (generator fuel). Upon arrival, it was discovered that a second gen-set had been installed. Although the install was observed by an unknown Manatee County representative, the Natural Resources Environmental Protection Division was not notified. Installations were not observed. Tank 1: Manufacturing info was not provided or available on the tank, system was registered in 2015 but appears to be older. Unknown install date. The tank appears to be UL-142 sub-base generator tank (EQ-969). There is no spill bucket attached, monitoring appears to be manual. The tank is in satisfactory condition with minor surface corrosion. Tank 2: Manufactured by: Advanced Manufacturing and Power Systems, Inc. 1965 Bennet Drive DeLand, FL 32724 386-822-5565 Model MH29522 UL D27750994 Manufacture Date: 11/6/2019. Unknown install date. 2400-gallon tank. Both are double-walled and set onto a concrete pad. Both have been put into service. Tank #2 still has vacuum on the interstice at -4. Overfill protection has not been established on either AST, if manual gauge ensure that no tank is filled beyond 90% capacity. FINANCIAL RESPONSIBILITY: Not provided. Provide Manatee County NRD with proof of Financial Responsibility indicating tank systems and Facility location. RELEASE DETECTION, as of 6/14/2024: a. Vacuum monitoring of the double-wall tank interstitial (TK2) manual monitoring (TK1). Manual overfill protection with gauged delivery on TK 1, High / low level gauge potential on TK2. b. Monthly visual inspections to be documented at least once a month not exceeding 35 days apart to include the tank exterior, spill containment and surrounding area. |