Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Journal Report | |||||||||||
Report Run Date: 03/13/2025 Last Data Refresh: 03/12/2025 Report Generated from DOPPLER | |||||||||||
Facility ID: | 9816870 | ||||||||||
Facility Name: | Wharf SMI OpCo | ||||||||||
09/18/2024 | Editable Letter Activity | Smith, Sara | |||||||||
Activity Title: | Warning Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/18/2024 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 05/26/2023 | ||||||||
Comment: | Sent | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 09/18/2024 | User: | SMITH_SAM | ||||||||
Description: | WL_Wharf SMI OpCo_9816870 | ||||||||||
View Attachment | |||||||||||
06/13/2023 | Enforcement Tracking Activity | Dolan, Judy F. | |||||||||
Activity Status: | Open | ||||||||||
05/23/2023 | Enforcement Referral Activity | Shanberg, Vincent J | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 06/13/2023 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/13/2023 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 06/13/2023 | ||||||||
Comment: | Accepted by Judy F. Dolan: Vincent Shanberg Case | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 06/13/2023 | ||||||||
Comment: | Acknowledged and Assigned by Judy F. Dolan | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 06/13/2023 | ||||||||
Comment: | Assigned to Judy F. Dolan | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 06/13/2023 | ||||||||
Comment: | Submitted for approval by: Vincent J Shanberg: referral | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/13/2023 | User: | SHANBERG_V | ||||||||
Description: | referral | ||||||||||
05/22/2023 | Violation Open | Shanberg, Vincent J | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7043 | ||||||||||
Rule: | 62-762.501(2)(f)2 | ||||||||||
05/15/2023 | Violation Open | Shanberg, Vincent J | |||||||||
Significance: | SNC-A | Status: | Open | ||||||||
Criteria ID: | 7010 | ||||||||||
Rule: | 62-762.421(2), 62-762.421(3)(c) | ||||||||||
05/15/2023 | Violation Open | Shanberg, Vincent J | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7041 | ||||||||||
Rule: | 62-762.501(2)(e)3, 62-762.501(2)(e)3.a, 62-762.501(2)(e)3.b, 62-762.501(2)(e)4, 62-762.502(2)(e)4, 62-762.502(2)(e)4.a, 62-762.502(2)(e)4.b, 62-762.502(2)(e)5 | ||||||||||
04/26/2023 | Site Inspection Activity Closed | Pardal, Laura | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 04/26/2023 | ||||||||||
Activity Closed Date: | 05/23/2023 | Activity Closed By: | SHANBERG_V | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/23/2023 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/15/2023 | User: | PARDAL_L | ||||||||
Description: | A Routine Compliance Inspection was conducted on April 26, 2023, with Laura Pardal, Environmental Specialist III, Vincent Shanberg, Environmental Specialist III with the Florida Department of Environmental Protection, Marathon Office, and Isaac Rodriguez General Manager at Wharf SMI OpCo, The facility has one (1) 6,000-gallon unleaded gas double-walled aboveground storage tank and one dispenser. Release detection is provided by a Kreuger Leak Gauge. No overfill protection was identified at the time of the inspection. Annual operability testing for release detection was conducted on 1/6/2021, 1/17/2022, 1/11/2023. Integrity testing of the remote fill box was conducted on 1/6/2021, 1/17/2022, 1/11/2023. Dispenser sump integrity testing was conducted on 1/6/2021. Financial Responsibility documentation was available and dated from April 1, 2023 to April 2, 2024. Three years of monthly inspections were available and dated from January 2021 to April 2023 were available. . Placard was dated from to June 1 ,2022 to June 30, 2023. The following violations were cited: Missing overfill protection annual operability testing documentation for 2021, 2022, and 2023. Failure to properly designate overfill protection device for aboveground storage tank. Missing financial responsibility documentation for 2021-2022 and 2022-2023. The facility is missing API color-symbol system on the spill bucket for the tank. A copy of the report will be sent via electronic mail to Isaac Rodriguez (isaac.rodriguez@suntex.com) and Hunter Spitler (hspitler@suntex.com). | ||||||||||
04/30/2020 | Attachment | Winkler, Michael G. | |||||||||
04/30/2020 | Editable Letter Activity | Winkler, Michael G. | |||||||||
Activity Title: | In Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/30/2020 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 04/30/2020 | ||||||||
Comment: | Sent | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 04/30/2020 | User: | WINKLER_MG_1 | ||||||||
Description: | 2020-04-30 ICL sent to Cathy Brown | ||||||||||
View Attachment | |||||||||||
04/30/2020 | Site Inspection Activity Closed | Winkler, Michael G. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 04/30/2020 | ||||||||||
Activity Closed Date: | 04/30/2020 | Activity Closed By: | WINKLER_MG_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/30/2020 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/30/2020 | User: | WINKLER_MG_1 | ||||||||
Description: | This is a 6000 gallon double walled AST servicing a single dockside dispenser. The facility has not filled the AST to date. Robert Judd will be performing monthly release detection. FR is current. No violations noted. NOTE: No signature capture due to COVID-19. | ||||||||||
01/29/2020 | Site Inspection Activity Closed | Winkler, Michael G. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 01/29/2020 | ||||||||||
Activity Closed Date: | 01/31/2020 | Activity Closed By: | WINKLER_MG_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/31/2020 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 01/31/2020 | User: | WINKLER_MG_1 | ||||||||
Description: | Ben Leigh Sales and Repair completed the installation of this PeeDee EQ 681 6000 gallon DW AST. See tank comments for all EQ numbers. RD is visual observation of AST, Krueger interstice monitor and visual of above ground piping and visual of dispenser pan. Labels were put on after the inspection and photos were emailed to the department. |