DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
Facility ID: 9818710
Facility Name: NATIONWIDE PLUMBING SRVCS
 
09/17/2024 Enforcement Tracking Activity Dolan, Judy F.
Activity Status: Open
08/20/2024 Enforcement Referral Activity Portanyi, Elsa-Marie
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 09/17/2024
Events:
Event Type: Activity has been finished Date: 09/17/2024
Comment: Finished
Events:
Event Type: Activity has been assigned Date: 09/17/2024
Comment: Assigned to Judy F. Dolan
Events:
Event Type: Activity/Document was acknowledged on this date Date: 09/17/2024
Comment: Acknowledged and Assigned by Judy F. Dolan
Events:
Event Type: Activity has been submitted for approval Date: 09/17/2024
Comment: Submitted for approval by: Zachary Barrett: Referring for enforcement on behalf of Elsa for Judy to approve.
Events:
Event Type: Activity/Document was accepted on this date Date: 09/17/2024
Comment: Accepted by Judy F. Dolan: Assigned to Elsa. Jd
Comments:
Comment Date: 09/17/2024 User: BARRETT_Z
Description: Referring for enforcement on behalf of Elsa for Judy to approve.
11/21/2023 Violation Open Portanyi, Elsa-Marie
Significance: Minor Status: Open
Criteria ID: 7041
Rule: 62-762.501(2)(e)3, 62-762.501(2)(e)3.a, 62-762.501(2)(e)3.b, 62-762.501(2)(e)4, 62-762.502(2)(e)4, 62-762.502(2)(e)4.a, 62-762.502(2)(e)4.b, 62-762.502(2)(e)5
11/21/2023 Violation Open Portanyi, Elsa-Marie
Significance: SNC-B Status: Open
Criteria ID: 7065
Rule: 62-762.601(1)(e), 62-762.602(1)(e)
11/21/2023 Violation Closed Portanyi, Elsa-Marie
Significance: Minor Status: Closed
Criteria ID: 7001
Rule: 62-762.101(5)
11/21/2023 Violation Closed Portanyi, Elsa-Marie
Significance: SNC-B Status: Closed
Criteria ID: 7042
Rule: 62-762.501(2)(f), 62-762.501(2)(f)1, 62-762.502(2)(f)
Attachments:
Attachment Date: 11/21/2023 User: PORTANYI_E
Description: 9818710 Fill Port without Spill bucket 11-09-23
View Attachment
Attachments:
Attachment Date: 02/14/2024 User: PORTANYI_E
Description: 9818710 Spill bucket installed
View Attachment
11/21/2023 Violation Open Portanyi, Elsa-Marie
Significance: SNC-B Status: Open
Criteria ID: 7068
Rule: 62-762.601(1)(h), 62-762.602(1)(h)
11/21/2023 Violation Open Portanyi, Elsa-Marie
Significance: Minor Status: Open
Criteria ID: 7090
Rule: 62-762.701(4)(b), 62-762.701(4)(b)1, 62-762.701(4)(b)2, 62-762.702(4)(b), 62-762.702(4)(b)1, 62-762.702(4)(b)2
Comments:
Comment Date: 06/25/2024 User: PORTANYI_E
Description: The facility provided a "Uniform Waste Transporters Manifest" by EMC oil dated 12-28-23.
11/21/2023 Violation Open Portanyi, Elsa-Marie
Significance: Minor Status: Open
Criteria ID: 7007
Rule: 62-762.411(4)
11/21/2023 Violation Closed Portanyi, Elsa-Marie
Significance: Minor Status: Closed
Criteria ID: 7043
Rule: 62-762.501(2)(f)2
Attachments:
Attachment Date: 02/14/2024 User: PORTANYI_E
Description: API for diesel
View Attachment
11/21/2023 Violation Open Portanyi, Elsa-Marie
Significance: SNC-A Status: Open
Criteria ID: 7010
Rule: 62-762.421(2), 62-762.421(3)(c)
Comments:
Comment Date: 02/14/2024 User: PORTANYI_E
Description: The facility submitted financial responsibility policy provided by ACE American Insurance Company and dated 12-21-23 to 12-21-24 via email on 2-2-24. The facility stated that they did not have financial responsibility prior to the 12-21-23 to 12-21-24 policy.
Attachments:
Attachment Date: 02/14/2024 User: PORTANYI_E
Description: 9818710 policy 12/21/23- 12/21/24
View Attachment
11/09/2023 Violation Open Portanyi, Elsa-Marie
Significance: SNC-B Status: Open
Criteria ID: 7042
Rule: 62-762.501(2)(f), 62-762.501(2)(f)1, 62-762.502(2)(f)
11/09/2023 Site Inspection Activity Closed Portanyi, Elsa-Marie
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 11/09/2023
Activity Closed Date: 08/20/2024 Activity Closed By: PORTANYI_E
Events:
Event Type: Activity has been finished Date: 08/20/2024
Comment: Finished
Comments:
Comment Date: 11/21/2023 User: PORTANYI_E
Description: A routine Compliance Inspection was conducted on November 09, 2023, with Elsa Portanyi, Environmental Specialist II with the Florida Department of Environmental Protection, Marathon Office, and Leandro Lamelas, Facility Representative, of Nationwide Plumbing Services. The facility operates as a plumbing service. TANK: The facility has one (1) 1,000-gallon Vehicular Diesel, double walled (DW), compartmentalized, regulated above ground storage tank (AST). The tank is used for fleet vehicles. The gated area where the tank is kept is also used as a storage area for portable toilets and associated tubing, making the tank difficult to access. It's unclear if the tank's registration is accurate regarding the design as compartmented. SPILL AND DISPENSER CONTAINMENT: The facility had one (1) fill port and no spill bucket at the fill port. The facility uses a garden hose to dispense fuel directly from the tank into the fleet vehicles. The dispenser is stored in the opening of a plastic drum. Liquid greater than one inch was present inside of the drum. The grass around the drum was dead and the hose was tangled, touching soil, and presented a tripping hazard. The decals on tank were faded and API label was missing on the fillport. OVERFILL PROTECTION: Overfill protection is provided Krueger gauge. SUMPS: The facility does not have sumps in relation to the regulated storage tank. RELEASE DETECTION: The facility did not have release detection on the regulated storage tank. DOCUMENT REVIEW: PLACARD: The placard was posted on tank at the time of the inspection was expired and dated 09/01/21 – 06/30/22. Updated placard provided via email on 11/21/23. FINANCIAL RESPONSIBILITY: Financial responsibility not provided at the time of the inspection. The facility provided financial responsibility coverage by ACE American Insurance Company dated 12/21/23 to 12/21/24 to the Department on 2/2/24. The facility is not able to provide historical records prior to 12/21/23. MONTHLY INSPECTIONS: The facility did not have monthly monitoring records since the tank's installation on 8/1/21. ANNUAL OPERABILITY TESTING (AOT): The facility did not have AOT records for overfill protection since the tank's installation on 8/1/21. Please see inspection report for full list of violations. A copy of this report will be sent via electronic mail to Ray Rey (Ray@nwpflkeys.com), Chris Rey (chris@nwpflkeys.com), and Linda Rein (Linda@nwpflkeys.com).