Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Journal Report | |||||||||||
Report Run Date: 03/13/2025 Last Data Refresh: 03/12/2025 Report Generated from DOPPLER | |||||||||||
Facility ID: | 9819169 | ||||||||||
Facility Name: | 360 FUELS | ||||||||||
01/15/2025 | Enforcement Tracking Activity | Gillman, Mark | |||||||||
Activity Status: | Open | ||||||||||
01/07/2025 | Enforcement Referral Activity | Gartin, Daniel Q | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 01/15/2025 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 01/07/2025 | ||||||||
Comment: | Submitted for approval by: Daniel Q Gartin: See attached Enforcement Referral Memo | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/15/2025 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 01/15/2025 | ||||||||
Comment: | Accepted by Mark Gillman: Accepted | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 01/15/2025 | ||||||||
Comment: | Acknowledged and Assigned by Mark Gillman | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 01/15/2025 | ||||||||
Comment: | Assigned to Mark Gillman | ||||||||||
Comments: | |||||||||||
Comment Date: | 01/07/2025 | User: | GARTIN_D | ||||||||
Description: | See attached Enforcement Referral Memo | ||||||||||
12/13/2024 | Record Document Activity | Gartin, Daniel Q | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: |
Angela Kelly |
Activity Closed Date: | 01/07/2025 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/07/2025 | ||||||||
Comment: | Finished | ||||||||||
10/17/2024 | Attachment | Gartin, Daniel Q | |||||||||
10/17/2024 | Editable Letter Activity | Gartin, Daniel Q | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Description: | 2021/09/23, E-mail | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 10/17/2024 | ||||||||
Comment: | Sent | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/17/2024 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 10/17/2024 | User: | MCLEOD_SL_1 | ||||||||
Description: | Compliance Assistance Offer Letter | ||||||||||
View Attachment | |||||||||||
10/17/2024 | Attachment | Gartin, Daniel Q | |||||||||
10/08/2024 | Electronic Communication Activity | Gartin, Daniel Q | |||||||||
Activity Closed Date: | 10/08/2024 | Activity Status: | Closed | ||||||||
Date: | 10/08/2024 | ||||||||||
Recipient: |
Angela Kelly |
||||||||||
Sender: |
Gartin, Daniel Q |
||||||||||
Subject: | RE: State Inspections | ||||||||||
Message: | Follow up email for issues noted during routine inspection. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/08/2024 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 10/08/2024 | User: | GARTIN_D | ||||||||
Description: | Follow up e mail for routine inspection. | ||||||||||
View Attachment | |||||||||||
10/08/2024 | Electronic Communication Activity | Gartin, Daniel Q | |||||||||
Activity Closed Date: | 10/08/2024 | Activity Status: | Closed | ||||||||
Date: | 10/08/2024 | ||||||||||
Recipient: |
Angela Kelly |
||||||||||
Sender: |
Gartin, Daniel Q |
||||||||||
Subject: | RE: State Inspections | ||||||||||
Message: | Associated scheduling email for inspections with AET that was set by Angel Kelly for October 4th, 2024. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/08/2024 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 10/08/2024 | User: | GARTIN_D | ||||||||
Description: | 8500403 scheduling email for routine inspection | ||||||||||
View Attachment | |||||||||||
10/04/2024 | Violation Open | Gartin, Daniel Q | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 6063 | ||||||||||
Rule: | 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1, 62-761.700(1)(a)2 | ||||||||||
10/04/2024 | Site Inspection Activity Closed | Gartin, Daniel Q | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 10/04/2024 | ||||||||||
Activity Closed Date: | 10/17/2024 | Activity Closed By: | GARTIN_D | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/17/2024 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/04/2024 | User: | GARTIN_D | ||||||||
Description: | TANKS: Tank 1 and tank 2 are compartmented, double wall underground storage tank systems that were installed in August of 2021. These systems are Plasteel Elutron tank (EQ-333) with tank 1 containing a capacity of 10000 gallons divided between 5000 gallon diesel compartment and a 5000 gallon non-ethanol compartment. Tank 2 is compartmented with regular and premium fuel to a capacity of 25000 gallons total. Both use pressurized piping system to transport fuel from the tank through double wall piping to dispensers. The tank's registration notes steel construction and requires correcting or cathodic protection if the tanks are composed of solely steel - violation was issued. STP SUMPS: The regular STP sump appears to have a leak at the mechanical line leak detector device area. The source of the leak needs to be determine and addressed - violation issued. SPILL CONTAINMENT: The spill containment buckets were clean and dry at the time of inspection. Associated gauges showed no liquid present at the time of inspection. The spill containment buckets for the regular, premium and non-ethanol, along with the vapor recovery buckets are not in 2020 API requirements - violation issued. OVERFILL PREVENTION: The facility uses flapper valves for overfill prevention monitoring. DISPENSERS: The dispensers sumps were clean and dry at the time of inspection. Dispenser hoses and nozzles appeared to be maintained in good condition at the time of inspection. RELEASE DETECTION: The facility uses a Veeder Root TLS 450 Plus system to monitor the interstitial space of the tanks and the STP sumps. All functions were normal at the time of inspection. RECORDS: The following facility records were received, including the Operator Training Certifications, Placard posted in facility, associated tank component testing, monthly visual inspection with electronic release detection ATG printouts, and financial responsibility forms. CONTACT INFORMATION: RUKJS INVESTMENTS LLC, Jay Patel, RUKJS.INVESTMENT@GMAIL.COM Angela Kelly, akelly@aetllc.com | ||||||||||
10/04/2024 | Violation Closed | Gartin, Daniel Q | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 6043 | ||||||||||
Rule: | 62-761.500(4)(b) | ||||||||||
10/04/2024 | Violation Closed | Gartin, Daniel Q | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 6013 | ||||||||||
Rule: | 62-761.420(3), 62-761.420(4), 62-761.420(8) | ||||||||||
10/04/2024 | Violation Closed | Gartin, Daniel Q | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 6003 | ||||||||||
Rule: | 62-761.400(1)(b), 62-761.400(2), 62-761.400(2)(a), 62-761.400(3), 62-761.400(3)(a), 62-761.400(3)(b), 62-761.400(3)(c) | ||||||||||
03/01/2023 | Comment | Khan, Muhammad Rafique | |||||||||
Description: | Equipment Installed: Tanks: (2) Double Wall Plasteel Elutron Tank, Metal Products Company (EQ-333) Facility ID: 9819169 Activity Opened : 10/07/2022 Page 2 of 12 Muhammad Rafique Khan Tank 1 is a 10,000 gallon compartmented Underground Storage Tank (UST) containing 5,000 gallons Diesel and 5,000 gallons Non-Ethanol. Tank 2 is a 25,000 gallon Underground Storage Tank (UST) containing Regular Unleaded. Piping: OPW Flexworks Piping Model C15A (EQ-772) Line Leak Detectors: Red Jacket Mechanical Line Leak Detectors (EQ-373) STP Sumps: Petroleum Containment, Inc.. Containment Sump Model 4500 (EQ-203) Dispenser Sumps: OPW Flexworks Dispenser Liners (EQ-318) Spill Buckets: OPW Double Wall Spill Buckets (EQ-224) Overfill: EMCO Wheaton Guardian Dual Point Overfill Prevention Valve Model A1100EVR (EQ#414) Release Detection: Veeder-Root, TLS-350 Automatic Tank Gauge (EQ-197). The STP sumps and UST(s) interstitials have sensors connected to the ATG (EQ-596). All equipment appears to have been installed per manufactures instructions and all sumps were hydrostatic tested and verified as passing by our department. | ||||||||||
02/10/2023 | Comment | Khan, Muhammad Rafique | |||||||||
Description: | Contractor submitted the following documents prior to installation: installation notification form, certified contractors form, site diagram, equipment list with EQ numbers and well proximity letter. Equipment Installed: Tanks: (2) Double Wall Plasteel Elutron Tank, Metal Products Company (EQ-333) Tank 1 is a 10,000 gallon compartmented Underground Storage Tank (UST) containing 5,000 gallons Diesel and 5,000 gallons Non-Ethanol. Tank 2 is a 25,000 gallon Underground Storage Tank (UST) containing Regular Unleaded. Piping: OPW Flexworks Piping Model C15A (EQ-772) Line Leak Detectors: Red Jacket Mechanical Line Leak Detectors (EQ-373) STP Sumps: Petroleum Containment, Inc.. Containment Sump Model 4500 (EQ-203) Dispenser Sumps: OPW Flexworks Dispenser Liners (EQ-318) Spill Buckets: OPW Double Wall Spill Buckets (EQ-224) Overfill: EMCO Wheaton Guardian Dual Point Overfill Prevention Valve Model A1100EVR (EQ#414) Release Detection: Veeder-Root, TLS-350 Automatic Tank Gauge (EQ-197). The STP sumps and UST(s) interstitials have sensors connected to the ATG (EQ-596). All equipment appears to have been installed per manufactures instructions and all sumps were hydrostatic tested and verified as passing by our department. | ||||||||||
02/10/2023 | Editable Letter Activity | Khan, Muhammad Rafique | |||||||||
Activity Title: | In Compliance Letter | Activity Status: | Closed | ||||||||
Description: | RCL | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 02/10/2023 | ||||||||
Comment: | Sent | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/10/2023 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/10/2023 | User: | WILSON_ML_1 | ||||||||
Description: | In Compliance Letter | ||||||||||
View Attachment | |||||||||||
01/19/2023 | Attachment | Wilson, Monica L | |||||||||
01/19/2023 | Attachment | Wilson, Monica L | |||||||||
10/07/2022 | Site Inspection Activity Closed | Khan, Muhammad Rafique | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 10/07/2022 | ||||||||||
Activity Closed Date: | 02/10/2023 | Activity Closed By: | KHAN_MR_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/10/2023 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 01/19/2023 | User: | WILSON_ML_1 | ||||||||
Description: | Type of Inspection: UST System Installation Location: 360 Fuels, 1404 Georgia Avenue, Lynn Haven, FL 32444 PSSC Contractor: A. Phelps Petroleum, 850-265-1207 / info@aphelpspetroleum.com PSSC# 050798 Owner: RUKJS Investments 3 LLC Owner Contact: Jay Patel, RUJKS.Investments@gmail.com Contractor submitted the following documents prior to installation: installation notification form, certified contractors form, site diagram, equipment list with EQ numbers and well proximity letter. Equipment Installed: Tanks: (2) Double Wall Plasteel Elutron Tank, Metal Products Company (EQ-333) Tank 1 is a 10,000 gallon compartmented Underground Storage Tank (UST) containing 5,000 gallons Diesel and 5,000 gallons Non-Ethanol. Tank 2 is a 25,000 gallon Underground Storage Tank (UST) containing Regular Unleaded. Piping: OPW Flexworks Piping Model C15A (EQ-772) Line Leak Detectors: Red Jacket Mechanical Line Leak Detectors (EQ-373) STP Sumps: Petroleum Containment, Inc.. Containment Sump Model 4500 (EQ-203) Dispenser Sumps: OPW Flexworks Dispenser Liners (EQ-318) Spill Buckets: OPW Double Wall Spill Buckets (EQ-224) Overfill: EMCO Wheaton Guardian Dual Point Overfill Prevention Valve Model A1100EVR (EQ#414) Release Detection: Veeder-Root, TLS-350 Automatic Tank Gauge (EQ-197). The STP sumps and UST(s) interstitials have sensors connected to the ATG (EQ-596). All equipment appears to have been installed per manufactures instructions and all sumps were hydrostatic tested and verified as passing by our department. |