Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Journal Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
Facility ID: | 9819477 | ||||||||||
Facility Name: | FLORIDA DEPT OF LAW ENFORCEMENT | ||||||||||
12/06/2024 | Electronic Communication Activity | Proffitt, Brooke | |||||||||
Activity Closed Date: | 12/06/2024 | Activity Status: | Closed | ||||||||
Date: | 12/06/2024 | ||||||||||
Recipient: | Jeff Mack | ||||||||||
Sender: | Brooke Proffitt | ||||||||||
Subject: | RE storage tank violations | ||||||||||
Message: | see attachment | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 12/06/2024 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 12/06/2024 | User: | PROFFITT_B | ||||||||
Description: | RE storage tank violations | ||||||||||
View Attachment | |||||||||||
10/15/2024 | Enforcement Tracking Activity | Gillman, Mark | |||||||||
Activity Status: | Open | ||||||||||
10/14/2024 | Enforcement Referral Activity | Elliott, Emily | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 10/15/2024 | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 10/15/2024 | ||||||||
Comment: | Accepted by Mark Gillman: Accepted | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/15/2024 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 10/15/2024 | ||||||||
Comment: | Acknowledged and Assigned by Mark Gillman | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 10/15/2024 | ||||||||
Comment: | Assigned to Mark Gillman | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 10/14/2024 | ||||||||
Comment: | Submitted for approval by: Emily Elliott: See attached for enforcement case referral and email chain. | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/14/2024 | User: | ELLIOTT_EV_1 | ||||||||
Description: | See attached for enforcement case referral and email chain. | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/14/2024 | User: | ELLIOTT_EV_1 | ||||||||
Description: | See attached for enforcement case referral and email chain. | ||||||||||
10/14/2024 | Enforcement Referral Activity | Elliott, Emily | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 10/15/2024 | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 10/15/2024 | ||||||||
Comment: | Accepted by Mark Gillman: Accepted | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/15/2024 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 10/15/2024 | ||||||||
Comment: | Acknowledged and Assigned by Mark Gillman | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 10/15/2024 | ||||||||
Comment: | Assigned to Mark Gillman | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 10/14/2024 | ||||||||
Comment: | Submitted for approval by: Emily Elliott: See attached for enforcement case referral and email chain. | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/14/2024 | User: | ELLIOTT_EV_1 | ||||||||
Description: | See attached for enforcement case referral and email chain. | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/14/2024 | User: | ELLIOTT_EV_1 | ||||||||
Description: | See attached for enforcement case referral and email chain. | ||||||||||
09/04/2024 | Record Document Activity | Elliott, Emily | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: |
Jeff Mack |
Activity Closed Date: | 09/06/2024 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/06/2024 | ||||||||
Comment: | Finished | ||||||||||
07/18/2024 | Editable Letter Activity | Elliott, Emily | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 07/18/2024 | ||||||||
Comment: | Sent | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/18/2024 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 07/18/2024 | User: | ELLIOTT_EV_1 | ||||||||
Description: | Compliance Assistance Offer Letter | ||||||||||
View Attachment | |||||||||||
07/17/2024 | Electronic Communication Activity | Elliott, Emily | |||||||||
Activity Closed Date: | 07/17/2024 | Activity Status: | Closed | ||||||||
Date: | 07/17/2024 | ||||||||||
Recipient: | BPELFREY@TEAMBECK.COM | ||||||||||
Sender: |
Elliott, Emily V |
||||||||||
Subject: | Routine Tank Compliance Inspection: (FAC ID: 9819477) Florida Dept of Law Enforcement | ||||||||||
Message: | Set TCI | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/17/2024 | ||||||||
Comment: | Finished | ||||||||||
07/16/2024 | Violation Open | Elliott, Emily | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7041 | ||||||||||
Rule: | 62-762.501(2)(e)3, 62-762.501(2)(e)3.a, 62-762.501(2)(e)3.b, 62-762.501(2)(e)4, 62-762.502(2)(e)4, 62-762.502(2)(e)4.a, 62-762.502(2)(e)4.b, 62-762.502(2)(e)5 | ||||||||||
07/16/2024 | Site Inspection Activity Closed | Elliott, Emily | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 07/16/2024 | ||||||||||
Activity Closed Date: | 07/18/2024 | Activity Closed By: | ELLIOTT_EV_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/18/2024 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 07/16/2024 | User: | ELLIOTT_EV_1 | ||||||||
Description: | Met onsite with Jeff Mack (Facilities Services Manager) for this routine tank compliance inspection. A copy of this inspection report and compliance assistance offer letter will be email to Brice Pelfrey at bpelrey@stirlingprop.com and Jeff Mack at jmack@stirlingprop.com. Tanks: Tank #1 and Tank #2 are both 3006 gallons Fidelity Manufacturing, LLC, Double-Wall Generator Base Tanks (EQ-497) containing diesel fuel to supply an emergency generator. Both tanks were installed February 2023. The exterior of the tanks appeared to be in good condition. Piping: Synthetic Fuel Supply and Return Hoses Spill Containment: Fidelity Manufacturing, 7.5 Gallon Spill Bucket for ASTs (EQ-778). Both spill containments appeared to be mostly clean and dry at the time of inspection. Overfill Prevention: FPI High Fuel Level Sensor/Alarm (EQ-817). Annual Operability Testing of the Overfill Prevention Device was unavailable at the time of inspection -Violation Issued. Release Detection: FPI High Fuel Level Sensor/Alarm (EQ-817). Annual Operability Testing of the Release Detection Device was unavailable at the time of inspection -Violation Issued. Records: No records were available to review at the time of inspection. Current Placard was not posted at the facility – Area of Concern Issued. Financial Responsibility was unavailable at the time of inspection – Violation Issued. Monthly Visual Inspections were unavailable at the time of inspection -Violation Issued. See Violation Section for Corrective Actions. | ||||||||||
07/16/2024 | Violation Open | Elliott, Emily | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7072 | ||||||||||
Rule: | 62-762.601(7), 62-762.602(7) | ||||||||||
07/16/2024 | Violation Closed | Elliott, Emily | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 7064 | ||||||||||
Rule: | 62-762.601(1)(d), 62-762.602(1)(d), 62-762.601(1)(g), 62-762.602(1)(g) | ||||||||||
07/16/2024 | Violation Closed | Elliott, Emily | |||||||||
Significance: | SNC-B | Status: | Closed | ||||||||
Criteria ID: | 7009 | ||||||||||
Rule: | 62-762.421(2), 62-762.421(3)(c) | ||||||||||
06/06/2023 | Comment | Elliott, Emily | |||||||||
Description: | TANKS: (EQ-497) Two Double-Wall Generator Base Tanks, Fidelity Manufacturing, LLC containing Vehicular Diesel to supply an emergency generator. Tank #1 and Tank #2 are both 3006 gallons Aboveground Storage Tanks. SPILL CONTAINMENT: (EQ-778) 7.5 Gallon Spill Bucket for ASTs, Fidelity Manufacturing. PIPING: Synthetic Fuel Supply and Return Hoses OVERFILL PROTECTION: (EQ-817) FPI High Fuel Level Sensor/Alarm and Rochester Fuel Level Gauge (EQ-901) which is located outside the spill box. RELEASE DETECTION: (EQ-817) FPI Interstitial Sensor/Alarm. | ||||||||||
05/05/2023 | Editable Letter Activity | Elliott, Emily | |||||||||
Activity Title: | In Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 05/05/2023 | ||||||||
Comment: | Sent | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/05/2023 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 05/05/2023 | User: | WILSON_ML_1 | ||||||||
Description: | In Compliance Letter | ||||||||||
View Attachment | |||||||||||
03/09/2023 | Site Inspection Activity Closed | Elliott, Emily | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 03/09/2023 | ||||||||||
Activity Closed Date: | 05/05/2023 | Activity Closed By: | ELLIOTT_EV_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/05/2023 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 05/05/2023 | ||||||||
Comment: | Submitted for approval by: Emily Elliott | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document has been approved | Date: | 05/05/2023 | ||||||||
Comment: | Approved by Charles L. Payne: Installation approved by Charles Payne on 5/5/2023. | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/09/2023 | User: | ELLIOTT_EV_1 | ||||||||
Description: | TYPE OF INSPECTION: Aboveground Storage Tank (AST) Installation Inspection. FACILITY OWNER: CPC LLC (david@jarviellc.com / 512-799-1955) (noto138@yahoo.com / 450-531-6657) FACILITY CONTACT: Brice Pelfrey (bpelfrey@teambeck.com / 850-477-2044) AST CONTRACTOR: Lane Armstrong, Amstrong Electric CO, Inc. (850-393-3545 / billcarroll@aeci.ws) EQUIPMENT INSTALLED: TANKS: (EQ-497) Two Double-Wall Generator Base Tanks, Fidelity Manufacturing, LLC containing Vehicular Diesel to supply an emergency generator. Tank #1 and Tank #2 are both 3006 gallons Aboveground Storage Tanks. SPILL CONTAINMENT: (EQ-778) 7.5 Gallon Spill Bucket for ASTs, Fidelity Manufacturing. PIPING: Synthetic Fuel Supply and Return Hoses OVERFILL PROTECTION: (EQ-817) FPI High Fuel Level Sensor/Alarm and Rochester Fuel Level Gauge (EQ-901) which is located outside the spill box. RELEASE DETECTION: (EQ-817) FPI Interstitial Sensor/Alarm. Prior to installation a work notification form, registration, current placard, EQ list, and site diagram were submitted to our office. Tank #1 and Tank #2 are 3006 gallons Double-Wall Generator Base Tank, Fidelity Manufacturing, LLC (EQ-497). The tanks are equipped with a FPI interstitial sensor/alarm for release detection (EQ-817). The tanks are also equipped with a FPI high fuel level alarms (EQ-817) and Rochester Fuel Level Gauges (EQ-901) for overfill protection. The AST systems are also equipped with a spill/fill box from the manufacturer (EQ-778). Furthermore, the tank is equipped with a primary emergency vent and secondary emergency vent. For piping the systems are equipped with synthetic fuel supply and return hoses that run from the tank tops to the generators itself. The tanks are bolted down to a concrete pad. All sensors were tested prior to the systems being placed into service. All components of the AST systems appear to have been installed according to manufactures instructions. |