DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/17/2025        Last Data Refresh: 05/16/2025        Report Generated from DOPPLER
 
District Northeast   Type    Retail Station
 
County Alachua   Status    OPEN
 
ID 8500220   Latitude    29° 39' 8.5516
 
Name WESTGATE FOOD MART
3328 W UNIVERSITY AVE
Longitude    82° 22' 19.2315
  GAINESVILLE, FL 32607-2540 LL Method    DPHO
 
Contact WENDA LEWIS   LL Status    REVIEWED
 
Phone (352) 376-3293   Status Date    03/21/2003
 
Account Owner Information
 
Name LEWIS OIL CO INC
PO BOX 141286
GAINESVILLE, FL 32614
Effective Date    07/02/2004
 
Contact WENDA LEWIS (MGR)
 
Phone (352) 376-3293
 
Email WLEWIS@LEWISOILCO.COM
  Placard # / Date    701572 - 10/02/2024
Property Owner Information
 
Name LEWIS OIL CO INC
PO BOX 141286
GAINESVILLE, FL 32614
Effective Date    07/02/2004
 
Contact WENDA LEWIS (MGR)
 
Phone (352) 376-3293
 
Email WLEWIS@LEWISOILCO.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1R1 10000 Unleaded Gas (B) 07/01/1989 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(O) Tight fill
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
2R1 10000 Unleaded Gas (B) 07/01/1989 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(O) Tight fill
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
3R1 10000 Unleaded Gas (B) 07/01/1989 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(M) Spill containment bucket
(O) Tight fill
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
1 6000 Unleaded Gas (B) 07/01/1963 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
2 4000 Leaded Gas (A) 07/01/1963 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
3 4000 Vehicular Diesel (D) 07/01/1963 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass (Y) Unknown
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   05/14/2024 05/14/2025 SCOTTSDALE INSURANCE COMPANY
INSURANCE   05/14/2023 05/14/2024 SCOTTSDALE INSURANCE COMPANY
INSURANCE   05/14/2022 05/14/2023 SCOTTSDALE INSURANCE COMPANY
INSURANCE   05/14/2021 05/14/2022 SCOTTSDALE INSURANCE COMPANY
INSURANCE   05/14/2020 05/14/2021 SCOTTSDALE INSURANCE COMPANY
INSURANCE   05/14/2019 05/14/2020 ILLINOIS UNION INSURANCE COMPANY
INSURANCE   05/14/2017 05/14/2018 ACE
INSURANCE   05/14/2016 05/14/2017 ACE
INSURANCE   01/31/2015 01/31/2016 AIG
INSURANCE   01/01/2014 01/01/2015 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/01/2013 01/01/2014 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/31/2012 01/31/2013 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/31/2011 01/31/2012 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/31/2010 01/31/2011 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/31/2009 01/31/2010 AIG
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 03/15/2006 03/16/2006 SIGNIFICANT OUT-OF-COMPLIANCE OWENS_JS 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes MLLD TEST 1/6/06, ANNUAL OPERABILITY TEST 3/15/06
 
RRBD 03/31/2005 04/07/2005 RAMSEY_T 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED LLD TEST PERFORMED ON 3/24/05
 
TCI 03/14/2005 03/15/2005 MINOR OUT-OF-COMPLIANCE OWENS_JS 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes ANNUAL OPERABILITY TEST 3/14/05
 
RRBD 02/27/2004 02/27/2004 RAMSEY_T 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED INVOICE FOR INSTALLATION OF DROP TUBES
 
TCI 01/07/2004 01/09/2004 SIGNIFICANT OUT-OF-COMPLIANCE OWENS_JS 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes LLD & ANNUAL OPERABILITY TEST 12/18/03
 
TCI 12/18/2002 12/23/2002 IN-COMPLIANCE OWENS_JS 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes LLD TEST 1/14/02, ANNUAL OPERATIONS TEST 12/18/02
 
TCI 12/06/2001 12/17/2001 IN-COMPLIANCE CHANDLER_R 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes COMPLIANCE INSPECTION, ANNUAL TESTS COMPLETED 12/12/01
 
TCI 12/12/2000 12/14/2000 IN-COMPLIANCE CHANDLER_R 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes COMPLIANCE INSPECTION
 
TCR 08/30/1999 09/01/1999 IN-COMPLIANCE CHANDLER_D 0/3 COMPLIANCE ASSURANCE
 
TCI 07/14/1999 08/03/1999 MINOR OUT-OF-COMPLIANCE CHANDLER_D 0/3 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 02/27/2025 Satisfied KEIM_MJ_1 Routine Compliance
 
Electronic Communication 02/27/2025 Satisfied KEIM_MJ_1 Routine Compliance
 
Letter 02/27/2025 Satisfied KEIM_MJ_1 Compliance Assistance
 
Site Inspection 02/27/2025 Major Out of Compliance KEIM_MJ_1 0/3 Routine Compliance
 
Letter 04/23/2024 Satisfied JACKSON_SM Enforcement
 
Enforcement Referral 03/06/2024 Accepted KEIM_MJ_1 Enforcement
 
Electronic Communication 05/15/2023 Satisfied KEIM_MJ_1 Compliance Assistance
 
Electronic Communication 05/15/2023 Satisfied KEIM_MJ_1 Compliance Assistance
 
Electronic Communication 04/29/2023 Satisfied KEIM_MJ_1 Compliance Assistance
 
Electronic Communication 01/31/2023 Satisfied KEIM_MJ_1 Routine Compliance
 
Electronic Communication 01/31/2023 Satisfied KEIM_MJ_1 Routine Compliance
 
Site Inspection 01/31/2023 Minor Out of Compliance KEIM_MJ_1 0/3 Routine Compliance
 
Letter 01/31/2023 Satisfied KEIM_MJ_1 Compliance Assistance
 
Electronic Communication 06/01/2022 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Letter 01/21/2021 Satisfied HARRIS_MJ Compliance Assistance
 
Letter 08/20/2020 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Electronic Communication 08/20/2020 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Site Inspection 08/20/2020 Minor Out of Compliance ZIMMERMAN_RA_2 0/3 Routine Compliance
 
Enforcement Tracking 08/17/2020 Closed Without Enforcement JULES_F Enforcement
 
Electronic Communication 08/03/2020 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Enforcement Referral 06/02/2020 Accepted ZIMMERMAN_RA_2 Enforcement
 
Electronic Communication 05/29/2020 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Letter 09/20/2018 Satisfied LIBBY_KK_1 Compliance Assistance
 
Phone Conversation 06/20/2018 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Electronic Communication 03/16/2018 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Site Inspection 03/16/2018 Major Out of Compliance ZIMMERMAN_RA_2 0/3 Routine Compliance
 
Letter 03/16/2018 Satisfied ZIMMERMAN_RA_2 Compliance Assistance
 
Phone Conversation 03/02/2018 Satisfied ZIMMERMAN_RA_2 Routine Compliance
 
Record Document 02/29/2016 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Phone Conversation 12/30/2015 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Electronic Communication 12/30/2015 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 12/30/2015 In Compliance HARRINGTON_RD_1 0/3 Routine Compliance
 
Site Inspection 04/17/2014 In Compliance HARRINGTON_RD_1 0/3 Routine Compliance
 
Electronic Communication 04/17/2014 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Emergency Preparedness Information 04/17/2014 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Emergency Preparedness Information 04/27/2012 Satisfied OWENS_JS_1 Routine Compliance
 
Site Inspection 04/27/2012 In Compliance OWENS_JS_1 0/3 Routine Compliance
 
Site Inspection 06/07/2011 In Compliance OWENS_JS_1 0/3 Routine Compliance
 
Emergency Preparedness Information 06/07/2011 Satisfied OWENS_JS_1 Routine Compliance
 
Emergency Preparedness Information 06/09/2010 Satisfied OWENS_JS_1 Routine Compliance
 
Site Inspection 06/09/2010 In Compliance OWENS_JS_1 0/3 Routine Compliance
 
Site Inspection 06/02/2009 In Compliance OWENS_JS_1 0/3 Routine Compliance
 
Emergency Preparedness Information 06/02/2009 Satisfied OWENS_JS_1 Routine Compliance
 
Emergency Preparedness Information 03/04/2008 Satisfied OWENS_JS_1 Routine Compliance
 
Site Inspection 03/04/2008 In Compliance OWENS_JS_1 0/3 Routine Compliance
 
Emergency Preparedness Information 05/22/2007 Satisfied OWENS_JS_1 Routine Compliance
 
Site Inspection 03/20/2007 In Compliance OWENS_JS_1 0/3 Routine Compliance
 
Emergency Preparedness Information 02/09/2007 Satisfied OWENS_JS_1 Routine Compliance
 
Emergency Preparedness Information 09/20/2006 Satisfied OWENS_JS_1 Routine Compliance
 
Site Inspection 06/23/2006 In Compliance OWENS_JS_1 0/3 Non-Compliance
 
Letter 05/01/2006 Satisfied RAMSEY_TH_1 Non-Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/27/2025 6051 SNC-B 4.5 Overfill prevention not provided or properly functioning. Have the ball float valves verified and tested or replace with another form of overfill prevention.
 
02/27/2025 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove liquid and investigate piping and shear valve repair or replace as needed. Forward the results and photographic documentation to the inspector to address this violation
 
02/27/2025 6049 SNC-B 4.15 Piping sumps not meeting performance requirements. 1) Repair or replace the inner upright section of the sump to complete a sealing surface for the inner sump lid. 2) Remove and replace the outer ring on the (RUL) spill bucket.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
11/04/1986   ACTIVE 10 EARLY DETECTION INCENTIVE-ELIGIBLE