DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 02/23/2025        Last Data Refresh: 02/22/2025        Report Generated from DOPPLER
 
District Northwest   Type    Retail Station
 
County Bay   Status    OPEN
 
ID 8500405   Latitude    30° 9' 9.5976
 
Name MURPHY EXPRESS #8875
280 TYNDALL PKWY N
Longitude    85° 35' 26.8944
  PANAMA CITY, FL 32404 LL Method    DPHO
 
Contact BRAD WEINISCHKE   LL Status    REVIEWED
 
Phone (870) 875-7741   Status Date    01/26/2009
 
Account Owner Information
 
Name MURPHY OIL USA INC
200 PEACH ST
El Dorado, AR 71730
Effective Date    05/22/2019
 
Contact KRYSTAL TERRELL /JENNIFER BRIDGES /BRAD WEINISCHKE
 
Phone (870) 677-6116
 
Email KRYSTAL.TERRELL@MURPHYUSA.COM
  Placard # / Date    679900 - 06/05/2024
Property Owner Information
 
Name MURPHY OIL USA INC
200 PEACH ST
El Dorado, AR 71730
Effective Date    05/22/2019
 
Contact KRYSTAL TERRELL /JENNIFER BRIDGES /BRAD WEINISCHKE
 
Phone (870) 677-6116
 
Email KRYSTAL.TERRELL@MURPHYUSA.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
4 25000 Unleaded Gas (B) 06/01/2019 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
5 26000 Vehicular Diesel (D) 06/01/2019 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(5) Electronic monitor dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 11763 Unleaded Gas (B) 03/01/1983 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(E) Fiberglass   (C) Fiberglass
(J) Pressurized piping system
(8) Manually sampled wells
(M) Manual tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
2 11763 Unleaded Gas (B) 03/01/1983 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(E) Fiberglass   (C) Fiberglass
(J) Pressurized piping system
(8) Manually sampled wells
(M) Manual tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
3 11763 Unleaded Gas (B) 03/01/1983 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(E) Fiberglass   (C) Fiberglass
(J) Pressurized piping system
(8) Manually sampled wells
(M) Manual tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   01/01/2024 04/30/2025
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   01/01/2022 04/30/2023
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   01/01/2020 04/30/2021
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   05/01/2019 04/30/2020
INSURANCE   04/23/1993 04/23/1994 FPLIPA
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 02/19/2025 Accepted GARTIN_D Enforcement
 
Electronic Communication 01/08/2025 Satisfied GARTIN_D Compliance Assistance
 
Letter 10/24/2024 Satisfied GARTIN_D Compliance Assistance
 
Electronic Communication 10/22/2024 Satisfied GARTIN_D Routine Compliance
 
Site Inspection 10/22/2024 Minor Out of Compliance GARTIN_D 0/2 Routine Compliance
 
Electronic Communication 10/22/2024 Satisfied GARTIN_D Routine Compliance
 
Letter 01/25/2023 Satisfied WILSON_ML_1 Routine Compliance
 
Site Inspection 01/20/2023 In Compliance KHAN_MR_1 0/2 Routine Compliance
 
Enforcement Tracking 08/18/2021 Closed Without Enforcement GILLMAN_M Enforcement
 
Letter 05/20/2021 Satisfied GILLMAN_M Enforcement
 
Enforcement Referral 04/28/2021 Accepted KHAN_MR_1 Enforcement
 
Issue Document 01/27/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 01/27/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 01/26/2021 Major Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Phone Conversation 01/25/2021 Satisfied KHAN_MR_1 Routine Compliance
 
Site Inspection 01/02/2020 In Compliance KHAN_MR_1 0/2 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
10/22/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a certified contractor conduct the integrity test for the dispenser sumps and STP sumps if needed. Forward documentation of the integrity testing results to Daniel.Gartin@flhealth.gov. If any components are damaged, a certified contractor will need to conduct repairs or replaces to the dispenser sumps.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
12/13/1987   COMBINED 30 EARLY DETECTION INCENTIVE-ELIGIBLE
 
10/08/1986   ACTIVE 30 EARLY DETECTION INCENTIVE-ELIGIBLE