Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 01/22/2025 Last Data Refresh: 01/21/2025 Report Generated from DOPPLER | |||||||||||
District | Northwest | Type | Marine/Coastal Fuel Storage | ||||||||
County | Bay | Status | OPEN | ||||||||
ID | 8500655 | Latitude | 30° 7' 5.059 | ||||||||
Name |
PIER 98 MARINA LLC 5904 E HWY 98 |
Longitude | 85° 35' 46.74 | ||||||||
PANAMA CITY, FL 32404-7425 | LL Method | DPHO | |||||||||
Contact | Paul (Buck) Buholz | LL Status | REVIEWED | ||||||||
Phone | (850) 874-8723 | Status Date | 10/15/2003 | ||||||||
Account Owner Information | |||||||||||
Name | SBR Industries, Inc. 6721 Precourt Drive Orlando, FL 32809 |
Effective Date | 12/28/2021 | ||||||||
Contact | Paul Buholz | ||||||||||
Phone | (334) 441-0037 | ||||||||||
pier98marina@aol.com | |||||||||||
Placard # / Date | 694024 - 06/24/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | SBR Industries, Inc. 6721 Precourt Drive Orlando, FL 32809 |
Effective Date | 12/28/2021 | ||||||||
Contact | Paul Buholz | ||||||||||
Phone | (334) 441-0037 | ||||||||||
pier98marina@aol.com | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 12000 | Unleaded Gas (B) | 12/01/2000 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (M) Spill containment bucket (N) Flow shut-Off (P) Level gauges/alarms (R) Double wall - tank jacket |
(F) Double wall (J) Pressurized piping system (K) Dispenser liners (N) Approved synthetic material |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 12000 | Unleaded Gas (B) | 12/01/2000 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (M) Spill containment bucket (N) Flow shut-Off (P) Level gauges/alarms (R) Double wall - tank jacket |
(F) Double wall (J) Pressurized piping system (K) Dispenser liners (N) Approved synthetic material |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 12000 | Vehicular Diesel (D) | 12/01/2000 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (P) Level gauges/alarms (R) Double wall - tank jacket |
(F) Double wall (J) Pressurized piping system (K) Dispenser liners (N) Approved synthetic material |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 2000 | Leaded Gas (A) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (D) External protective coating | (H) Mechanical line leak detector | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 02/07/2022 | 02/07/2023 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 10/24/2020 | 10/24/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/24/2019 | 10/24/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/24/2018 | 10/24/2019 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/24/2015 | 10/24/2016 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/24/2013 | 10/24/2014 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 06/13/2012 | 06/13/2013 | COMMERCIAL INSURANCE | ||||||||
INSURANCE | 06/13/2012 | 06/13/2013 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 06/09/2010 | 06/09/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 06/09/2010 | 06/09/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 06/09/2009 | 06/09/2010 | AIG | ||||||||
INSURANCE | 06/06/2008 | 06/06/2009 | COMMERCE & INDUSTRY | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
DPRI | 03/07/2006 | 03/10/2006 | IN-COMPLIANCE | KHAN | 0/3 | TERMINAL FACILITY PROJECT | |||||
Completion Notes DPRC # 099959 | |||||||||||
TCI | 03/07/2006 | 03/10/2006 | MINOR OUT-OF-COMPLIANCE | KHAN | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes DPRC #099959 | |||||||||||
TCI | 07/11/2005 | 07/18/2005 | IN-COMPLIANCE | BRAZILE | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes POST HURRICANE DENNIS INSPECTION, PIPING SUMPS HAVE WATER/SHEEN, ELECTRIC TRANSFORMER IN DOCK HOUSE NOT FUNCTIONAL | |||||||||||
RRBD | 06/20/2005 | 06/22/2005 | COMPLIANCE ASSURANCE | ||||||||
TCI | 03/29/2005 | 03/31/2005 | MINOR OUT-OF-COMPLIANCE | KHAN | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes DPRC #099951 | |||||||||||
DPRI | 03/29/2005 | 03/31/2005 | IN-COMPLIANCE | KHAN | 0/3 | TERMINAL FACILITY PROJECT | |||||
Completion Notes DPRC #099951 | |||||||||||
TCI | 09/24/2004 | 09/28/2004 | IN-COMPLIANCE | PINKOVSKY | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes POST HURRICANE IVAN INSPECTION | |||||||||||
TCI | 04/12/2004 | 04/12/2004 | IN-COMPLIANCE | PINKOVSKY | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PIPING: APT DOUBLEWALLED, DPRC #099937 | |||||||||||
DPRI | 04/12/2004 | 04/12/2004 | IN-COMPLIANCE | PINKOVSKY | 0/0 | TERMINAL FACILITY PROJECT | |||||
Completion Notes DPRIC #099937 | |||||||||||
DSNR | 09/16/2003 | 09/16/2003 | PINKOVSKY | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes DSNR FOR PASSING PREMIUM TANK SUMP HYDROTEST. | |||||||||||
RRBD | 09/16/2003 | 09/18/2003 | COMPLIANCE ASSURANCE | ||||||||
RRBD | 08/19/2003 | 08/20/2003 | PINKOVSKY | 0/0 | COMPLIANCE ASSURANCE | ||||||
DPRI | 06/16/2003 | 06/18/2003 | IN-COMPLIANCE | PINKOVSKY | 0/3 | TERMINAL FACILITY PROJECT | |||||
Completion Notes PIPING: DOUBLEWALLED APT, CERT # 099916 | |||||||||||
TCR | 06/16/2003 | 06/18/2003 | MINOR OUT-OF-COMPLIANCE | PINKOVSKY | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes DOUBLEWALLED APT; DPRI CERT # 099916 | |||||||||||
IRFR | 06/16/2003 | 06/18/2003 | PINKOVSKY | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes INF FOR FUEL IN PREMIUM TANK SUMP. | |||||||||||
LTR | 06/11/2003 | 06/11/2003 | PINKOVSKY | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes APPOINTMENT LETTER FOR RE-INSPECTION | |||||||||||
TCI | 04/09/2003 | 04/11/2003 | MINOR OUT-OF-COMPLIANCE | PINKOVSKY | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PIPING: DOUBLEWALLED APT 1.5" AND 3." DIAMETER | |||||||||||
TCR | 07/15/2002 | 07/15/2002 | IN-COMPLIANCE | PINKOVSKY | 0/3 | COMPLIANCE ASSURANCE | |||||
TCR | 05/29/2002 | 05/30/2002 | MINOR OUT-OF-COMPLIANCE | PINKOVSKY | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 03/21/2002 | 03/22/2002 | MINOR OUT-OF-COMPLIANCE | PINKOVSKY | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes DPRI CERTIFICATE 099966 | |||||||||||
DPRI | 03/21/2002 | 03/22/2002 | IN-COMPLIANCE | PINKOVSKY | 0/3 | TERMINAL FACILITY PROJECT | |||||
Completion Notes CERTIFICATE #099966 | |||||||||||
WLI | 02/11/2002 | 02/11/2002 | PINKOVSKY | 0/3 | COMPLIANCE ASSURANCE | ||||||
Completion Notes DPRP NEEDS COMPLETION | |||||||||||
TIN | 10/05/2001 | 10/08/2001 | IN-COMPLIANCE | PINKOVSKY | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 05/31/2024 | Major Out of Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Letter | 05/31/2024 | Satisfied | KHAN_MR_1 | Compliance Assistance | |||||||
Phone Conversation | 05/22/2024 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Enforcement Tracking | 02/14/2024 | Closed Without Enforcement | GILLMAN_M | Enforcement | |||||||
Enforcement Referral | 07/22/2022 | Accepted | WILSON_ML_1 | Enforcement | |||||||
Letter | 06/22/2022 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 06/10/2022 | Minor Out of Compliance | KHAN_MR_1 | 0/3 | Component Installation | ||||||
Letter | 04/19/2022 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Issue Document | 04/19/2022 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 04/15/2022 | Minor Out of Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Enforcement Tracking | 03/15/2022 | Closed Without Enforcement | MATHERLY_H | Enforcement | |||||||
Letter | 12/29/2021 | Satisfied | MATHERLY_H | Enforcement | |||||||
Enforcement Referral | 12/15/2021 | Accepted | KHAN_MR_1 | Enforcement | |||||||
Site Inspection | 08/31/2021 | Major Out of Compliance | KHAN_MR_1 | 0/3 | Complaint | ||||||
Issue Document | 08/31/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Letter | 08/31/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Electronic Communication | 09/08/2020 | Satisfied | MERRITT_S | Enforcement | |||||||
Enforcement Tracking | 09/08/2020 | Closed Without Enforcement | MERRITT_S | Enforcement | |||||||
Enforcement Referral | 09/16/2019 | Accepted | KHAN_MR_1 | Enforcement | |||||||
Issue Document | 08/01/2019 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Electronic Communication | 08/01/2019 | Satisfied | WILSON_ML_1 | Installation | |||||||
Letter | 08/01/2019 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 07/31/2019 | Major Out of Compliance | KHAN_MR_1 | 0/3 | Installation | ||||||
Site Inspection | 05/06/2019 | Major Out of Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Issue Document | 05/06/2019 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Letter | 05/06/2019 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Phone Conversation | 05/06/2019 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Site Inspection | 10/22/2018 | In Compliance | WILSON_ML_1 | 0/3 | Complaint | ||||||
Enforcement Tracking | 11/08/2017 | Closed Without Enforcement | MERRITT_S | Enforcement | |||||||
Letter | 09/01/2017 | Satisfied | MERRITT_S | Compliance Assistance | |||||||
Site Inspection | 05/05/2017 | Minor Out of Compliance | MERRITT_S | 0/3 | Enforcement | ||||||
Enforcement Referral | 12/13/2016 | Accepted | BRAZILE_DO_1 | Enforcement | |||||||
Letter | 07/13/2016 | Satisfied | WILSON_ML_1 | Non-Compliance | |||||||
Letter | 06/07/2016 | Satisfied | WILSON_ML_1 | Non-Compliance | |||||||
Site Inspection | 06/06/2016 | Minor Out of Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 06/20/2014 | In Compliance | KHAN_MR_1 | 0/3 | Non-Compliance | ||||||
Record Document | 05/19/2014 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Phone Conversation | 05/19/2014 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Letter | 04/16/2014 | Satisfied | DAURIA_KL_1 | Non-Compliance | |||||||
Site Inspection | 04/15/2014 | Minor Out of Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 01/29/2013 | In Compliance | KHAN_MR_1 | 0/3 | Installation | ||||||
Site Inspection | 01/29/2013 | In Compliance | KHAN_MR_1 | 0/3 | Closure | ||||||
Site Inspection | 11/09/2012 | In Compliance | KHAN_MR_1 | 0/3 | Closure | ||||||
Site Inspection | 08/21/2012 | In Compliance | KHAN_MR_1 | 0/3 | Installation | ||||||
Site Inspection | 08/20/2012 | In Compliance | KHAN_MR_1 | 0/3 | Non-Compliance | ||||||
Phone Conversation | 08/06/2012 | Satisfied | KHAN_MR_1 | Installation | |||||||
Incident | 08/03/2012 | Has not led to Discharge | KHAN_MR_1 | Incident | |||||||
Record Document | 08/03/2012 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Document Management | 08/03/2012 | Complete | KHAN_MR_1 | Incident | |||||||
Phone Conversation | 08/03/2012 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Incident | 07/31/2012 | Has not led to Discharge | KHAN_MR_1 | Incident | |||||||
Record Document | 07/31/2012 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Letter | 06/20/2012 | Satisfied | PURDY_EM_1 | Non-Compliance | |||||||
Phone Conversation | 06/12/2012 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Site Inspection | 06/11/2012 | Major Out of Compliance | KHAN_MR_1 | 0/3 | Non-Compliance | ||||||
Letter | 05/30/2012 | Satisfied | PURDY_EM_1 | Non-Compliance | |||||||
Site Inspection | 05/25/2012 | Major Out of Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 06/09/2011 | In Compliance | KHAN_MR_1 | 0/3 | Non-Compliance | ||||||
Letter | 01/13/2011 | Satisfied | PIERCE_LL_1 | Non-Compliance | |||||||
Site Inspection | 01/07/2011 | Minor Out of Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Record Document | 05/20/2010 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Phone Conversation | 03/30/2010 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Letter | 01/08/2010 | Minor Out of Compliance | PIERCE_LL_1 | Non-Compliance | |||||||
Site Inspection | 01/06/2010 | Minor Out of Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 02/26/2009 | In Compliance | KHAN_MR_1 | 0/4 | Non-Compliance | ||||||
Letter | 02/18/2009 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Site Inspection | 02/17/2009 | Minor Out of Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Record Document | 08/04/2008 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Record Document | 06/11/2008 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Phone Conversation | 05/29/2008 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Letter | 05/08/2008 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Site Inspection | 05/06/2008 | Major Out of Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Record Document | 06/29/2007 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Phone Conversation | 06/05/2007 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Phone Conversation | 05/29/2007 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Letter | 04/23/2007 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Site Inspection | 04/23/2007 | Minor Out of Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 02/23/2007 | In Compliance | BRAZILE_DO_1 | 0/3 | Non-Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
05/31/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Fix the alarms on ATG -VEEDER ROOT send invoice or pictures to this office when job is completed. | |||||||
05/31/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Provide current Annual operability testing of release detection systems (inline leak detectors) to this office | |||||||
05/31/2024 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Provide the primary overfill protection devices testing to this office. | |||||||
05/31/2024 | 6001 | Minor | 2.1 No reasonable access provided. | Provide access to components mentioned above by your representative, schedule with inspector by calling 8502588546 | |||||||
05/31/2024 | 6011 | SNC-B | 2.8 No financial responsibility instrument or expired instrument for < 180 days. | Provide tank insurance including form Cor D and Form P to this office. email to muhammad.khan@flhealth.gov | |||||||
05/31/2024 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Provide monthly visual inspection log and release detection (VEEDER ROOT) print outs from 4/2022 till now to this office | |||||||
05/31/2024 | 6024 | Minor | 2.2 Integrity test not performed on storage tank, integral piping, single-walled spill containment system, double-walled spill containment system, or doubled-walled sump prior to placing into service. | Provide current/Valid integrity test for Spill buckets, Transition sumps and Dispenser liners to this office | |||||||
05/31/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Provide current Annual operability testing of release detection systems (ATG) to this office, | |||||||
05/31/2024 | 6002 | Minor | 2.1 Operator Training records not available. | Provide copies of ABC, operator training for the cashiers who work at the facility, to this office. | |||||||
No Discharges Found |