Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 01/22/2025 Last Data Refresh: 01/21/2025 Report Generated from DOPPLER | |||||||||||
District | Central | Type | Retail Station | ||||||||
County | Brevard | Status | OPEN | ||||||||
ID | 8501162 | Latitude | 28° 5' 53.749 | ||||||||
Name |
RE-UP 601 S BABCOCK ST |
Longitude | 80° 37' 17.012 | ||||||||
MELBOURNE, FL 32901-1459 | LL Method | DPHO | |||||||||
Contact | MICHAELSALAFIA | LL Status | REVIEWED | ||||||||
Phone | (646) 217-1465 | Status Date | 09/19/2023 | ||||||||
Account Owner Information | |||||||||||
Name | RE-UP FL 1 LLC 601 SOUTH BABCOCK ST MELBOURNE, FL 32901 |
Effective Date | 04/22/2024 | ||||||||
Contact | MICHAEL SALAFIA | ||||||||||
Phone | (646) 217-1465 | ||||||||||
MICHAEL@REUPFUEL.COM | |||||||||||
Placard # / Date | 688571 - 06/18/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | RE-UP FL 1 LLC 601 SOUTH BABCOCK ST MELBOURNE, FL 32901 |
Effective Date | 04/22/2024 | ||||||||
Contact | MICHAEL SALAFIA | ||||||||||
Phone | (646) 217-1465 | ||||||||||
MICHAEL@REUPFUEL.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 10000 | Unleaded Gas (B) | 03/01/1993 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (N) Flow shut-Off |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 10000 | Unleaded Gas (B) | 03/01/1993 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (N) Flow shut-Off |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
8 | 10000 | Unleaded Gas (B) | 03/01/1993 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (N) Flow shut-Off |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 4000 | Unleaded Gas (B) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 4000 | Unleaded Gas (B) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 4000 | Unleaded Gas (B) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 4000 | Unleaded Gas (B) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 4000 | Unleaded Gas (B) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 09/01/2021 | 09/01/2022 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 09/01/2020 | 09/01/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 09/01/2019 | 09/01/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 09/01/2018 | 09/01/2019 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/01/2016 | 09/01/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/01/2015 | 09/01/2016 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/01/2014 | 09/01/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/01/2013 | 09/01/2014 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 12/03/2009 | 12/03/2010 | ZURICH-AMERICAN | ||||||||
INSURANCE | 12/03/2008 | 12/03/2009 | ZURICH-AMERICAN | ||||||||
INSURANCE | 09/01/1995 | 09/01/1997 | FPLIPA | ||||||||
INSURANCE | 02/19/1993 | 04/01/1995 | FPLIPA | ||||||||
INSURANCE | 01/10/1991 | 07/31/1992 | FPLIPA | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 08/10/2005 | 08/18/2005 | MINOR OUT-OF-COMPLIANCE | STEWART | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 10/08/2004 | 10/12/2004 | IN-COMPLIANCE | ULRICH | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 08/14/2003 | 08/14/2003 | MINOR OUT-OF-COMPLIANCE | STEWART | 0/3 | COMPLIANCE ASSURANCE | |||||
NCLI | 08/14/2003 | 08/14/2003 | STEWART | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCR | 08/13/2003 | 08/14/2003 | IN-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
DCCR | 05/06/2003 | 07/17/2003 | STEWART_T | 0/3 | DISCHARGE PROJECT | ||||||
RRBD | 04/10/2003 | 08/14/2003 | STEWART | 0/3 | COMPLIANCE ASSURANCE | ||||||
NCLI | 11/25/2002 | 11/25/2002 | STEWART | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCI | 11/21/2002 | 11/25/2002 | MINOR OUT-OF-COMPLIANCE | STEWART | 0/3 | COMPLIANCE ASSURANCE | |||||
IRFR | 11/21/2002 | 11/25/2002 | STEWART | 0/3 | DISCHARGE PROJECT | ||||||
Completion Notes ATG ALARM | |||||||||||
DCNC | 11/21/2002 | 11/25/2002 | STEWART | 0/3 | DISCHARGE PROJECT | ||||||
Completion Notes REPAIRED ALARM | |||||||||||
TCI | 01/25/2002 | 01/31/2002 | IN-COMPLIANCE | PURCELL | 0/3 | COMPLIANCE ASSURANCE | |||||
TCR | 05/03/2001 | 05/04/2001 | IN-COMPLIANCE | PURCELL | 0/3 | COMPLIANCE ASSURANCE | |||||
NCLI | 03/22/2001 | 03/22/2001 | PURCELL | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCI | 03/21/2001 | 03/22/2001 | SIGNIFICANT OUT-OF-COMPLIANCE | PURCELL | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 02/29/2000 | 03/01/2000 | IN-COMPLIANCE | PURCELL | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 04/27/1999 | 04/29/1999 | IN-COMPLIANCE | PURCELL_R | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 05/31/2024 | Satisfied | ULRICH_CA_1 | Compliance Assistance | |||||||
Site Inspection | 05/30/2024 | Major Out of Compliance | ULRICH_CA_1 | 0/3 | Routine Compliance | ||||||
Letter | 04/15/2022 | Satisfied | ULRICH_CA_1 | Routine Compliance | |||||||
Site Inspection | 04/04/2022 | In Compliance | ULRICH_CA_1 | 0/3 | Routine Compliance | ||||||
Incident | 02/03/2022 | Has not led to Discharge | ULRICH_CA_1 | Incident | |||||||
Letter | 02/18/2019 | Satisfied | WEST_KE_1 | Compliance Assistance | |||||||
Site Inspection | 02/18/2019 | Minor Out of Compliance | WEST_KE_1 | 0/3 | Routine Compliance | ||||||
Document Management | 02/13/2019 | Satisfied | ULRICH_CA_1 | Routine Compliance | |||||||
Document Management | 02/13/2019 | Satisfied | ULRICH_CA_1 | Routine Compliance | |||||||
Electronic Communication | 12/04/2018 | Satisfied | ULRICH_CA_1 | Routine Compliance | |||||||
Site Inspection | 05/20/2016 | In Compliance | WEST_KE_1 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 03/08/2016 | Satisfied | JOHNSON_CJ | Enforcement | |||||||
Enforcement Tracking | 03/08/2016 | Closed Without Enforcement | JOHNSON_CJ | Enforcement | |||||||
Site Inspection | 11/18/2015 | In Compliance | WEST_KE_1 | 0/3 | Discharge | ||||||
Site Inspection | 11/18/2015 | In Compliance | WEST_KE_1 | 0/3 | Closure | ||||||
Site Inspection | 11/18/2015 | In Compliance | WEST_KE_1 | 0/3 | Installation | ||||||
Discharge Reporting | 10/06/2015 | Satisfied | WEST_KE_1 | Discharge | |||||||
Document Management | 10/06/2015 | Complete | WEST_KE_1 | Discharge | |||||||
Record Document | 09/14/2015 | Satisfied | WEST_KE_1 | Closure | |||||||
Letter | 09/14/2015 | Satisfied | WEST_KE_1 | Non-Compliance | |||||||
Electronic Communication | 09/14/2015 | Satisfied | WEST_KE_1 | Closure | |||||||
Site Inspection | 09/14/2015 | Major Out of Compliance | WEST_KE_1 | 0/3 | Non-Compliance | ||||||
Electronic Communication | 09/14/2015 | Satisfied | WEST_KE_1 | Non-Compliance | |||||||
Phone Conversation | 09/11/2015 | Satisfied | WEST_KE_1 | Non-Compliance | |||||||
Phone Conversation | 09/11/2015 | Satisfied | WEST_KE_1 | Non-Compliance | |||||||
Letter | 07/30/2015 | Satisfied | MARTIN_G | Non-Compliance | |||||||
Electronic Communication | 07/27/2015 | Satisfied | WEST_KE_1 | Enforcement | |||||||
Phone Conversation | 06/30/2015 | Satisfied | MARTIN_G | Enforcement | |||||||
Electronic Communication | 06/16/2015 | Satisfied | MARTIN_G | Enforcement | |||||||
Record Document | 06/10/2015 | Satisfied | WEST_KE_1 | Non-Compliance | |||||||
Site Inspection | 05/06/2015 | Minor Out of Compliance | MARTIN_G | 0/3 | Enforcement | ||||||
Letter | 01/12/2015 | Satisfied | WEST_KE_1 | Non-Compliance | |||||||
Site Inspection | 01/12/2015 | Minor Out of Compliance | WEST_KE_1 | 0/3 | Non-Compliance | ||||||
Record Document | 01/09/2015 | Satisfied | WEST_KE_1 | Routine Compliance | |||||||
Document Management | 02/28/2014 | Complete | STEWART_TJ_1 | Routine Compliance | |||||||
Site Inspection | 02/28/2014 | Minor Out of Compliance | STEWART_TJ_1 | 0/3 | Routine Compliance | ||||||
Letter | 02/28/2014 | Satisfied | STEWART_TJ_1 | Non-Compliance | |||||||
Electronic Communication | 02/28/2014 | Satisfied | STEWART_TJ_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 02/10/2014 | Satisfied | STEWART_TJ_1 | Routine Compliance | |||||||
Letter | 04/26/2011 | Satisfied | ULRICH_CA_1 | Non-Compliance | |||||||
Site Inspection | 04/15/2011 | Major Out of Compliance | ULRICH_CA_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 04/14/2011 | Satisfied | ULRICH_CA_1 | Routine Compliance | |||||||
Site Inspection | 01/11/2010 | Minor Out of Compliance | STEWART_TJ_1 | 0/3 | Routine Compliance | ||||||
Record Document | 01/11/2010 | Satisfied | STEWART_TJ_1 | Non-Compliance | |||||||
Letter | 05/27/2009 | Satisfied | ULRICH_CA_1 | Non-Compliance | |||||||
Site Inspection | 05/27/2009 | Minor Out of Compliance | ULRICH_CA_1 | 0/3 | Routine Compliance | ||||||
Record Document | 04/03/2008 | Satisfied | MARTIN_G | Enforcement | |||||||
Site Inspection | 02/28/2008 | Minor Out of Compliance | MARTIN_G | 0/3 | Enforcement | ||||||
Enforcement Referral | 02/11/2008 | Accepted | MARTIN_G | Enforcement | |||||||
Letter | 09/06/2007 | Satisfied | STEWART_TJ_1 | Non-Compliance | |||||||
Site Inspection | 08/01/2007 | Minor Out of Compliance | STEWART_TJ_1 | 0/3 | Routine Compliance | ||||||
Issue Document | 07/05/2007 | Satisfied | STEWART_TJ_1 | Routine Compliance | |||||||
Letter | 06/29/2007 | Satisfied | ULRICH_CA_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 02/07/2007 | Satisfied | ULRICH_CA_1 | Routine Compliance | |||||||
Site Inspection | 10/03/2006 | In Compliance | ULRICH_CA_1 | 0/3 | Non-Compliance | ||||||
Emergency Preparedness Information | 09/20/2006 | Satisfied | ULRICH_CA_1 | Routine Compliance | |||||||
Site Inspection | 08/23/2006 | Minor Out of Compliance | ULRICH_CA_1 | 0/3 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
05/30/2024 | 6060 | SNC-B | 4.11 Release detection methods do not meet monitoring requirements. | Restore vacuum to the tank interstice as soon as possible. Tank currently has NO release detection. | |||||||
05/30/2024 | 6011 | SNC-B | 2.8 No financial responsibility instrument or expired instrument for < 180 days. | Tank owner / operator is required to maintain insurance on the storage tanks to cover an accidental discharge or release of product from the tanks. Provide a copy of the current insurance policy to Brevard County Natural Resources (chris.ulrich@brevardfl.gov). | |||||||
05/30/2024 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Conduct monthly visual inspections - log you findings. These do not have to be contracted out - you can do them yourself. Once a month, print a liquid status report from the Veeder-Root. This shows the sensor status in the 3 tank top sumps. Look in the fill buckets and under the dispensers once a month. Look at the three tank vacuum gauges - write down the gauge readings. Once every 6 months (or twice a year) look into the tank top sumps. | |||||||
05/30/2024 | 6051 | SNC-B | 4.5 Overfill prevention not provided or properly functioning. | Contract a tank testing company to reset the flapper capacity level to 90%. Retest flappers. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
10/02/2015 | COMPLETED | ||||||||||
05/05/2003 | COMPLETED | 7 | |||||||||
01/09/1991 | COMPLETED | ||||||||||