Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District Central   Type    Retail Station
 
County Brevard   Status    OPEN
 
ID 8501288   Latitude    28° 11' 43.5895
 
Name CHARLIES AUTO REPAIR
690 S PATRICK DR
Longitude    80° 36' 24.7328
  SATELLITE BEACH, FL 32937-3873 LL Method    DPHO
 
Contact CHARLES THOMAS   LL Status    REVIEWED
 
Phone (321) 777-5371   Status Date    07/27/2018
 
Account Owner Information
 
Name THOMAS, CHARLES
690 S PATRICK DR
SATELLITE BEACH, FL 32937
Effective Date    11/15/2001
 
Contact CHARLES THOMAS
 
Phone (321) 777-5371
 
Email CHARLESAMOCO@GMAIL.COM
  Placard # / Date    702397 - 10/21/2024
Property Owner Information
 
Name THOMAS, CHARLES
690 S PATRICK DR
SATELLITE BEACH, FL 32937
Effective Date    02/01/2011
 
Contact CHARLES THOMAS
 
Phone (321) 777-5371
 
Email CHARLESAMOCO@GMAIL.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
10 150 New/Lube Oil (O) ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel   (A) Abv, no soil contact (S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
11 12000 Unleaded Gas (B) 02/01/2011 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
(Q) DEP approved protection
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(R) Monitor tank bottom space
 
 
Tank Tank Size Content Installed Placement Status
7 150 New/Lube Oil (O) ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel   (A) Abv, no soil contact (I) Not required
 
 
Tank Tank Size Content Installed Placement Status
8 150 Kerosene (K) ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel   (A) Abv, no soil contact (I) Not required
 
 
Tank Tank Size Content Installed Placement Status
9 150 Waste Oil (L) ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(D) Unknown   (Y) Unknown (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
1 4000 Unleaded Gas (B) 07/01/1965 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
(H) Impressed current CP
(M) Spill containment bucket
(N) Flow shut-Off
  (C) Fiberglass
(J) Pressurized piping system
(M) Double wall - pipe jacket
(8) Manually sampled wells
(H) Mechanical line leak detector
(J) Monitor piping/liner space
(M) Manual tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
2 4000 Unleaded Gas (B) 07/01/1965 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
(H) Impressed current CP
(M) Spill containment bucket
(N) Flow shut-Off
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(2) Visual inspect pipe sumps
(H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
3 4000 Unleaded Gas (B) 07/01/1965 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
(H) Impressed current CP
(M) Spill containment bucket
(N) Flow shut-Off
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(2) Visual inspect pipe sumps
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
4 4000 Vehicular Diesel (D) 07/01/1965 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
(H) Impressed current CP
(M) Spill containment bucket
(N) Flow shut-Off
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(2) Visual inspect pipe sumps
(H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
5 10000 Unleaded Gas (B) 12/01/1985 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(H) Impressed current CP
(M) Spill containment bucket
(N) Flow shut-Off
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
6 1000 Kerosene (K) 02/01/1984 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(I) Suction piping system
(8) Manually sampled wells
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   07/20/2021 07/20/2022 ACE AMERICAN INSURANCE COMPANY
INSURANCE   02/08/2018 02/08/2019 ACE AMERICAN INSURANCE COMPANY
INSURANCE   02/08/2017 02/08/2018 ACE AMERICAN INSURANCE COMPANY
INSURANCE   02/08/2016 02/08/2017 ACE AMERICAN INSURANCE COMPANY
INSURANCE   02/08/2015 02/08/2016 ACE
INSURANCE   02/08/2013 02/08/2014 NATIONAL UNION FIRE
INSURANCE   02/08/2012 02/08/2013 ZURICH-AMERICAN
INSURANCE   02/08/2011 02/08/2012 ZURICH-AMERICAN
INSURANCE   03/01/2008 03/01/2009 ZURICH-AMERICAN
INSURANCE   12/31/1994 05/09/1995 FPLIPA
INSURANCE   04/26/1991 09/12/1995 FPLIPA
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 08/11/2005 08/18/2005 MINOR OUT-OF-COMPLIANCE STEWART 0/4 COMPLIANCE ASSURANCE
 
TCI 08/09/2004 08/12/2004 IN-COMPLIANCE ULRICH 0/4 COMPLIANCE ASSURANCE
 
TCR 08/28/2003 08/29/2003 IN-COMPLIANCE STEWART 0/4 COMPLIANCE ASSURANCE
 
NCLI 08/12/2003 08/12/2003 STEWART 0/4 COMPLIANCE ASSURANCE
 
TCI 08/07/2003 08/12/2003 MINOR OUT-OF-COMPLIANCE STEWART 0/4 COMPLIANCE ASSURANCE
 
TCR 08/06/2003 08/12/2003 IN-COMPLIANCE STEWART 0/4 COMPLIANCE ASSURANCE
 
TCI 03/20/2003 03/25/2003 MINOR OUT-OF-COMPLIANCE STEWART 0/4 COMPLIANCE ASSURANCE
 
TCI 11/05/2001 11/07/2001 IN-COMPLIANCE PURCELL 0/4 COMPLIANCE ASSURANCE
 
TCI 11/17/2000 11/27/2000 IN-COMPLIANCE PURCELL 0/4 COMPLIANCE ASSURANCE
 
TCI 03/28/2000 03/29/2000 IN-COMPLIANCE PURCELL 0/4 COMPLIANCE ASSURANCE
 
CWOE 06/04/1999 06/09/1999 PURCELL_R 0/0 COMPLIANCE ASSURANCE
 
RRBD 06/04/1999 06/09/1999 PURCELL_R 0/0 COMPLIANCE ASSURANCE
 
NCLI 04/23/1999 04/26/1999 PURCELL_R 0/0 COMPLIANCE ASSURANCE
 
TCI 04/23/1999 04/26/1999 SIGNIFICANT OUT-OF-COMPLIANCE PURCELL_R 0/4 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 03/13/2023 Satisfied GRANTHAM_JW_1 Routine Compliance
 
Phone Conversation 03/13/2023 Satisfied GRANTHAM_JW_1 Routine Compliance
 
Letter 09/20/2021 Satisfied GRANTHAM_JW_1 Compliance Assistance
 
Site Inspection 09/15/2021 Major Out of Compliance GRANTHAM_JW_1 1/0 Routine Compliance
 
Letter 01/31/2019 Satisfied ULRICH_CA_1 Routine Compliance
 
Site Inspection 01/31/2019 In Compliance ULRICH_CA_1 1/0 Routine Compliance
 
Electronic Communication 01/08/2019 Satisfied ULRICH_CA_1 Routine Compliance
 
Site Inspection 04/06/2016 In Compliance WEST_KE_1 1/0 Routine Compliance
 
Electronic Communication 06/12/2015 Satisfied MARTIN_G Closure
 
Site Inspection 05/14/2015 In Compliance MARTIN_G 0/4 Enforcement
 
Enforcement Tracking 05/07/2015 Closed Without Enforcement MARTIN_G Enforcement
 
Document Management 04/01/2015 Complete WEST_KE_1 Closure
 
Record Document 04/01/2015 Satisfied WEST_KE_1 Closure
 
Record Document 04/01/2015 Satisfied WEST_KE_1 Routine Compliance
 
Site Inspection 04/01/2015 In Compliance WEST_KE_1 0/4 Closure
 
Record Document 03/20/2015 Satisfied WEST_KE_1 Closure
 
Electronic Communication 02/26/2015 Satisfied MARTIN_G Enforcement
 
Letter 12/02/2014 Satisfied MARTIN_G Non-Compliance
 
Site Inspection 10/16/2014 Major Out of Compliance MARTIN_G 0/4 Enforcement
 
Phone Conversation 05/07/2014 Satisfied MARTIN_G Enforcement
 
Phone Conversation 04/30/2014 Satisfied MARTIN_G Enforcement
 
Enforcement Referral 04/30/2014 Accepted MARTIN_G Enforcement
 
Site Inspection 04/29/2014 Major Out of Compliance STEWART_TJ_1 1/4 Installation
 
Electronic Communication 11/12/2013 Satisfied STEWART_TJ_1 Non-Compliance
 
Site Inspection 11/12/2013 Major Out of Compliance STEWART_TJ_1 1/4 Routine Compliance
 
Letter 11/12/2013 Satisfied STEWART_TJ_1 Non-Compliance
 
Emergency Preparedness Information 02/05/2013 Satisfied ULRICH_CA_1 Routine Compliance
 
Site Inspection 02/05/2013 In Compliance ULRICH_CA_1 1/4 Routine Compliance
 
Site Inspection 07/09/2012 In Compliance STEWART_TJ_1 1/0 Complaint
 
Complaint 07/09/2012 Inspection Required STEWART_TJ_1 Complaint
 
Site Inspection 12/02/2011 Major Out of Compliance STEWART_TJ_1 1/4 Routine Compliance
 
Letter 12/02/2011 Satisfied STEWART_TJ_1 Non-Compliance
 
Site Inspection 03/03/2011 In Compliance ULRICH_CA_1 1/4 Installation
 
Site Inspection 09/07/2010 In Compliance ULRICH_CA_1 0/4 Routine Compliance
 
Meeting 04/01/2010 Satisfied ULRICH_CA_1 Non-Compliance
 
Record Document 10/05/2009 Satisfied STEWART_TJ_1 Non-Compliance
 
Site Inspection 09/30/2009 Major Out of Compliance STEWART_TJ_1 0/4 Routine Compliance
 
Letter 09/30/2009 Satisfied STEWART_TJ_1 Non-Compliance
 
Record Document 10/30/2008 Satisfied ULRICH_CA_1 Routine Compliance
 
Site Inspection 10/27/2008 Minor Out of Compliance ULRICH_CA_1 0/4 Routine Compliance
 
Letter 10/27/2008 Satisfied ULRICH_CA_1 Non-Compliance
 
Site Inspection 10/29/2007 In Compliance STEWART_TJ_1 0/4 Non-Compliance
 
Letter 08/30/2007 Satisfied STEWART_TJ_1 Non-Compliance
 
Site Inspection 08/28/2007 Minor Out of Compliance STEWART_TJ_1 0/4 Routine Compliance
 
Issue Document 08/15/2007 Satisfied STEWART_TJ_1 Routine Compliance
 
Emergency Preparedness Information 02/14/2007 Satisfied ULRICH_CA_1 Routine Compliance
 
Emergency Preparedness Information 09/26/2006 Satisfied ULRICH_CA_1 Routine Compliance
 
Site Inspection 09/12/2006 In Compliance ULRICH_CA_1 0/4 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
09/15/2021 7090 Minor 3.15 Spill containment, dispenser liners and piping sumps not accessible; water and regulated substances not removed. Water in excess of one inch in depth, or any regulated substances collected in secondary containment or in sumps shall be removed within 72 hours of discovery and be either reused or properly disposed. Fix any dispensers that are dripping. Perform a hydrostatic test all dispenser and piping transition sumps to determine if the sumps are tight. The sumps must be tested by January 21, 2022 since it will be three years since the last test. Provide updated tests and pictures to this office.
 
09/15/2021 7075 SNC-B 3.1 Not repaired component or piping which has not caused a discharge or release. Replace the premium overfill alarm box. Repairs shall be performed if any component of a storage tank system has: An operational or structural problem that could potentially result in a release or discharge, or lead to the presence of water in the interstice of a storage tank or integral piping other than condensate.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
02/17/1988   ACTIVE 10 EARLY DETECTION INCENTIVE-ELIGIBLE