Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 01/22/2025 Last Data Refresh: 01/21/2025 Report Generated from DOPPLER | |||||||||||
District | Southeast | Type | Retail Station | ||||||||
County | Broward | Status | OPEN | ||||||||
ID | 8501509 | Latitude | 26° 0' 8.7288 | ||||||||
Name |
IZQUIERDO DEVELOPMENT CORP 5600 WASHINGTON ST |
Longitude | 80° 11' 57.9451 | ||||||||
HOLLYWOOD, FL 33023-1478 | LL Method | DPHO | |||||||||
Contact | HENRY IZQUIERDO | LL Status | REVIEWED | ||||||||
Phone | (305) 586-9366 | Status Date | 12/11/2003 | ||||||||
Account Owner Information | |||||||||||
Name | IZQUIERDO DEVELOPMENT 5600 WASHINGTON ST Hollywood, FL 33023 |
Effective Date | 07/09/2021 | ||||||||
Contact | IZQUIERDO DEVELOPMENTS CORP | ||||||||||
Phone | (305) 586-9366 | ||||||||||
D.ROCKETFUEL@GMAIL.COM | |||||||||||
Placard # / Date | 697271 - 06/28/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | IZQUIERDO DEVELOPMENT 5600 WASHINGTON ST Hollywood, FL 33023 |
Effective Date | 07/09/2021 | ||||||||
Contact | IZQUIERDO DEVELOPMENTS CORP | ||||||||||
Phone | (305) 586-9366 | ||||||||||
D.ROCKETFUEL@GMAIL.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1R1 | 6000 | Unleaded Gas (B) | 11/01/1986 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (J) Synthetic excavation liner (M) Spill containment bucket |
(C) Fiberglass (G) Pipe trench liner (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (8) Manually sampled wells (E) Monitor UST/liner space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2R1 | 6000 | Unleaded Gas (B) | 11/01/1986 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (J) Synthetic excavation liner (M) Spill containment bucket |
(C) Fiberglass (G) Pipe trench liner (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (8) Manually sampled wells (E) Monitor UST/liner space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3R1 | 6000 | Unleaded Gas (B) | 11/01/1986 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (J) Synthetic excavation liner (M) Spill containment bucket |
(C) Fiberglass (G) Pipe trench liner (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (8) Manually sampled wells (E) Monitor UST/liner space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 4000 | Unleaded Gas (B) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (C) Fiberglass | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 4000 | Leaded Gas (A) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (D) External protective coating | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 4000 | Unleaded Gas (B) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (D) External protective coating | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 4000 | Unleaded Gas (B) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (D) External protective coating | (Y) Unknown | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 10/16/2023 | 10/16/2024 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 10/16/2021 | 10/16/2022 | ASPEN SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 02/23/2017 | 02/23/2018 | CRUM & FORSTER INDEMNITY | ||||||||
INSURANCE | 02/23/2015 | 02/23/2017 | CRUM & FORSTER INDEMNITY | ||||||||
INSURANCE | 04/21/2012 | 04/21/2013 | CHARTIS SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 04/21/2011 | 04/21/2012 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 03/22/2009 | 03/22/2010 | ZURICH-AMERICAN | ||||||||
INSURANCE | 03/22/2007 | 03/22/2008 | ZURICH-AMERICAN | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 01/23/2006 | IN-COMPLIANCE | MANGIN_T | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCR | 02/25/2005 | 02/28/2005 | IN-COMPLIANCE | MANGIN_T | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 02/08/2005 | 02/11/2005 | MINOR OUT-OF-COMPLIANCE | MANGIN_T | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 02/04/2004 | 02/09/2004 | IN-COMPLIANCE | MANGIN_T | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 01/13/2003 | 01/23/2003 | IN-COMPLIANCE | MANGIN_T | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 04/22/2002 | 04/29/2002 | IN-COMPLIANCE | MANGIN_T | 0/3 | COMPLIANCE ASSURANCE | |||||
TCR | 03/01/2001 | 03/20/2001 | IN-COMPLIANCE | MANGIN_T | 0/3 | COMPLIANCE ASSURANCE | |||||
NCLI | 01/10/2001 | 01/22/2001 | MANGIN_T | 0/3 | COMPLIANCE ASSURANCE | ||||||
TCI | 01/10/2001 | 01/22/2001 | MINOR OUT-OF-COMPLIANCE | MANGIN_T | 0/4 | COMPLIANCE ASSURANCE | |||||
TCR | 01/26/2000 | 02/04/2000 | IN-COMPLIANCE | MANGIN_T | 0/3 | COMPLIANCE ASSURANCE | |||||
TIN | 12/22/1999 | 01/10/2000 | IN-COMPLIANCE | MANGIN_T | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 12/17/1999 | 12/27/1999 | MINOR OUT-OF-COMPLIANCE | MANGIN_T | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 05/01/2024 | Satisfied | SCOTT_DC_1 | Compliance Assistance | |||||||
Site Inspection | 05/01/2024 | Major Out of Compliance | SCOTT_DC_1 | 0/3 | Routine Compliance | ||||||
Record Document | 12/01/2023 | Satisfied | KOENIG_EJ_1 | Compliance Assistance | |||||||
Enforcement Tracking | 12/01/2023 | Closed Without Enforcement | KOENIG_EJ_1 | Enforcement | |||||||
Letter | 12/01/2023 | Satisfied | KOENIG_EJ_1 | Compliance Assistance | |||||||
Enforcement Referral | 02/01/2023 | Accepted | KOENIG_EJ_1 | Enforcement | |||||||
Record Document | 06/03/2022 | Satisfied | DORNEVAL_WX_1 | Compliance Assistance | |||||||
Record Document | 06/03/2022 | Satisfied | DORNEVAL_WX_1 | Compliance Assistance | |||||||
Record Document | 06/02/2022 | Satisfied | DORNEVAL_WX_1 | Compliance Assistance | |||||||
Letter | 12/22/2021 | Satisfied | DORNEVAL_WX_1 | Compliance Assistance | |||||||
Site Inspection | 12/22/2021 | Major Out of Compliance | DORNEVAL_WX_1 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 12/02/2021 | Satisfied | DORNEVAL_WX_1 | Routine Compliance | |||||||
Letter | 10/18/2019 | Satisfied | ACOSTA_KM_1 | Compliance Assistance | |||||||
Record Document | 10/17/2019 | Satisfied | ACOSTA_KM_1 | Compliance Assistance | |||||||
Record Document | 09/23/2019 | Satisfied | ACOSTA_KM_1 | Compliance Assistance | |||||||
Record Document | 08/22/2019 | Satisfied | ACOSTA_KM_1 | Compliance Assistance | |||||||
Record Document | 08/16/2019 | Satisfied | ACOSTA_KM_1 | Compliance Assistance | |||||||
Letter | 08/08/2019 | Satisfied | ACOSTA_KM_1 | Compliance Assistance | |||||||
Site Inspection | 08/06/2019 | Minor Out of Compliance | ACOSTA_KM_1 | 0/3 | Routine Compliance | ||||||
Phone Conversation | 07/29/2019 | Satisfied | ACOSTA_KM_1 | Routine Compliance | |||||||
Site Inspection | 03/22/2017 | In Compliance | MANGIN_T_1 | 0/3 | Routine Compliance | ||||||
Phone Conversation | 02/28/2017 | Satisfied | MANGIN_T_1 | Routine Compliance | |||||||
Record Document | 04/15/2015 | Satisfied | MANGIN_T_1 | Non-Compliance | |||||||
Phone Conversation | 04/06/2015 | Satisfied | GOMEZ_AE_1 | Non-Compliance | |||||||
Letter | 02/18/2015 | Satisfied | MANGIN_T_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 02/18/2015 | Satisfied | MANGIN_T_1 | Routine Compliance | |||||||
Site Inspection | 02/18/2015 | Minor Out of Compliance | MANGIN_T_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 07/25/2012 | In Compliance | MANGIN_T_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 07/25/2012 | Satisfied | MANGIN_T_1 | Routine Compliance | |||||||
Site Inspection | 06/19/2012 | In Compliance | MANGIN_T_1 | 0/3 | Non-Compliance | ||||||
Letter | 05/09/2012 | Satisfied | MANGIN_T_1 | Non-Compliance | |||||||
Site Inspection | 05/09/2012 | Minor Out of Compliance | MANGIN_T_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 05/02/2012 | Satisfied | MANGIN_T_1 | Routine Compliance | |||||||
Site Inspection | 05/11/2011 | In Compliance | MANGIN_T_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 05/10/2011 | Satisfied | MANGIN_T_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 03/02/2010 | Satisfied | MANGIN_T_1 | Routine Compliance | |||||||
Site Inspection | 03/02/2010 | In Compliance | MANGIN_T_1 | 0/3 | Routine Compliance | ||||||
Record Document | 03/06/2009 | Satisfied | MANGIN_T_1 | Non-Compliance | |||||||
Letter | 01/28/2009 | Satisfied | MANGIN_T_1 | Non-Compliance | |||||||
Site Inspection | 01/28/2009 | Minor Out of Compliance | MANGIN_T_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 01/28/2009 | Satisfied | MANGIN_T_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 10/29/2007 | Satisfied | MANGIN_T_1 | Routine Compliance | |||||||
Letter | 10/29/2007 | Satisfied | MANGIN_T_1 | Non-Compliance | |||||||
Site Inspection | 10/22/2007 | Minor Out of Compliance | MANGIN_T_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 02/08/2007 | Satisfied | MANGIN_T_1 | Routine Compliance | |||||||
Letter | 12/18/2006 | Satisfied | MANGIN_T_1 | Non-Compliance | |||||||
Site Inspection | 12/12/2006 | Minor Out of Compliance | MANGIN_T_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 09/27/2006 | Satisfied | MANGIN_T_1 | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
04/11/2024 | 6029 | Minor | 4.1 Any component(s) of the storage tank system not installed according to manufacturer's instructions. | Install a new cap on poppet, provide confirmation to inspector when completed. | |||||||
04/10/2024 | 6059 | SNC-B | 4.9 Release detection shall be constructed and installed so that groundwater, rainfall, or soil moisture will not render the release detection method used inoperable. | Liner should be dry, confirm integrity of system by making any necessary repairs and provide confirmation to inspector when completed. | |||||||
04/10/2024 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Include confirmation that low point well is being bailed during monthly visual inspections, provide back-to-back inspections to inspector. | |||||||
04/10/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Perform hydrostatic testing on dispenser sumps, provide results to inspector for review. | |||||||
04/10/2024 | 6009 | Minor | 4.1 Incident Notification Form (INF) not received in a timely manner. | Submit INF for water inside of liner, begin investigation. | |||||||