Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Retail Station | ||||||||
County | Citrus | Status | OPEN | ||||||||
ID | 8503168 | Latitude | 28° 46' 52.8498 | ||||||||
Name |
CIRCLE K #2707211 5601 S FLORIDA AVE |
Longitude | 82° 17' 47.5026 | ||||||||
FLORAL CITY, FL 34436-2014 | LL Method | DPHO | |||||||||
Contact | GRAHAM BIGGS | LL Status | REVIEWED | ||||||||
Phone | (919) 774-6700 | Status Date | 02/07/2003 | ||||||||
Account Owner Information | |||||||||||
Name | CIRCLE K STORES INC 1100 Situs Ct Raleigh, NC 27606-5446 |
Effective Date | 05/20/1994 | ||||||||
Contact | IRA LEWIS | ||||||||||
Phone | (423) 400-2480 | ||||||||||
ILEWIS@CIRCLEK.COM | |||||||||||
Placard # / Date | 697453 - 06/28/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | CIRCLE K STORES INC 1100 Situs Ct Raleigh, NC 27606-5446 |
Effective Date | 07/08/2019 | ||||||||
Contact | IRA LEWIS | ||||||||||
Phone | (423) 400-2480 | ||||||||||
ILEWIS@CIRCLEK.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 10152 | Unleaded Gas (B) | 05/01/1985 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (H) Impressed current CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 10152 | Unleaded Gas (B) | 05/01/1985 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (H) Impressed current CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 10152 | Unleaded Gas (B) | 05/01/1985 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (H) Impressed current CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 8000 | Leaded Gas (A) | 07/01/1974 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (D) External protective coating | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 8000 | Unleaded Gas (B) | 07/01/1974 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (D) External protective coating | (8) Manually sampled wells | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
GUARANTEE | 04/24/2022 | 08/21/2023 | |||||||||
GUARANTEE | 04/25/2021 | 04/25/2022 | |||||||||
INSURANCE | 12/01/2020 | 12/01/2021 | NAVIGATORS SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2019 | 12/01/2020 | NAVIGATORS SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2018 | 12/01/2019 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2017 | 12/01/2018 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2016 | 12/01/2017 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2015 | 12/01/2016 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2014 | 12/01/2015 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2013 | 12/01/2014 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2011 | 12/01/2013 | CHUBB | ||||||||
INSURANCE | 12/17/2010 | 12/16/2011 | CHUBB | ||||||||
INSURANCE | 12/17/2009 | 12/17/2010 | CHUBB | ||||||||
INSURANCE | 12/17/2005 | 12/17/2009 | AMERICAN INTERNATIONAL SPECIALTY LINES | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 11/02/2005 | 11/03/2005 | IN-COMPLIANCE | HARMAN_G | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes CAP CONDUIT PIPE ON SUMP | |||||||||||
RRBD | 02/16/2005 | 02/16/2005 | MOLLI_SA | 0/0 | COMPLIANCE ASSURANCE | ||||||
CWOE | 02/16/2005 | 02/16/2005 | MOLLI_SA | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 01/04/2005 | 01/04/2005 | MOLLI_SA | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 12/28/2004 | 01/04/2005 | MINOR OUT-OF-COMPLIANCE | MOLLI_SA | 0/3 | COMPLIANCE ASSURANCE | |||||
CWOE | 11/05/2003 | 11/07/2003 | MOLLI_SA | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 11/05/2003 | 11/07/2003 | IN-COMPLIANCE | MOLLI_SA | 0/0 | COMPLIANCE ASSURANCE | |||||
TCI | 10/10/2003 | 10/21/2003 | MINOR OUT-OF-COMPLIANCE | MOLLI_SA | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PIPING IS FIBERGLASS & PRESSURIZED | |||||||||||
NCLI | 10/10/2003 | 10/21/2003 | MOLLI_SA | 0/3 | COMPLIANCE ASSURANCE | ||||||
CWOE | 09/19/2002 | 09/19/2002 | SUMNER_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 09/19/2002 | 09/19/2002 | SUMNER_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 09/06/2002 | 09/06/2002 | SUMNER_C | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 09/03/2002 | 09/06/2002 | MINOR OUT-OF-COMPLIANCE | SUMNER_C | 0/3 | COMPLIANCE ASSURANCE | |||||
DCCR | 07/16/2002 | 07/31/2002 | SUMNER_C | 0/0 | DISCHARGE PROJECT | ||||||
DRFR | 07/05/2002 | 07/31/2002 | SUMNER_C | 0/0 | DISCHARGE PROJECT | ||||||
TIN | 06/19/2002 | 01/13/2003 | IN-COMPLIANCE | SUMNER_C | 0/3 | COMPLIANCE ASSURANCE | |||||
IRFR | 04/17/2002 | 04/17/2002 | SUMNER_C | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes CONSECUTIVE INCONCLUSIVES OR FAILED SIR ON REGULAR UNLEADED | |||||||||||
IRFR | 01/22/2002 | 01/22/2002 | SIMNER_C | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes SIR INVENTORY DISCREPANCY | |||||||||||
TCI | 09/07/2001 | 09/07/2001 | IN-COMPLIANCE | SUMNER_C | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 09/19/2000 | 09/29/2000 | IN-COMPLIANCE | SUMNER_C | 0/3 | COMPLIANCE ASSURANCE | |||||
DCNC | 06/23/2000 | 06/23/2000 | SUMNER_C | 0/0 | DISCHARGE PROJECT | ||||||
DSNR | 06/16/2000 | 06/16/2000 | SUMNER_C | 0/0 | DISCHARGE PROJECT | ||||||
TCI | 01/24/2000 | 01/31/2000 | IN-COMPLIANCE | SUMNER_C | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 08/28/2024 | Satisfied | WIMBERLY_E | Enforcement | |||||||
Enforcement Referral | 06/19/2024 | Accepted | MULLIGAN_PC_1 | Enforcement | |||||||
Electronic Communication | 11/14/2023 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Electronic Communication | 11/14/2023 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Electronic Communication | 10/31/2023 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Electronic Communication | 09/25/2023 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Letter | 08/18/2023 | Satisfied | LEE_MC_1 | Compliance Assistance | |||||||
Site Inspection | 08/18/2023 | Major Out of Compliance | LEE_MC_1 | 0/3 | Routine Compliance | ||||||
Letter | 09/06/2022 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Record Document | 09/06/2022 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Record Document | 08/29/2022 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Record Document | 08/15/2022 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Record Document | 07/27/2022 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Letter | 03/29/2022 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Site Inspection | 03/29/2022 | Major Out of Compliance | MULLIGAN_PC_1 | 0/3 | Routine Compliance | ||||||
Record Document | 09/30/2020 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Letter | 09/30/2020 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Incident | 09/22/2020 | Has not led to Discharge | MULLIGAN_PC_1 | Incident | |||||||
Record Document | 09/22/2020 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Incident | 09/22/2020 | Has not led to Discharge | MULLIGAN_PC_1 | Incident | |||||||
Document Management | 07/27/2020 | Satisfied | MULLIGAN_PC_1 | Incident | |||||||
Document Management | 07/07/2020 | Satisfied | MULLIGAN_PC_1 | Incident | |||||||
Letter | 07/07/2020 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Site Inspection | 07/07/2020 | Major Out of Compliance | MULLIGAN_PC_1 | 0/3 | Routine Compliance | ||||||
Document Management | 07/16/2019 | Satisfied | MULLIGAN_PC_1 | Incident | |||||||
Incident | 07/16/2019 | Has not led to Discharge | MULLIGAN_PC_1 | Incident | |||||||
Record Document | 09/17/2018 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Letter | 09/17/2018 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Document Management | 08/14/2018 | Satisfied | MULLIGAN_PC_1 | Incident | |||||||
Incident | 08/14/2018 | Has not led to Discharge | MULLIGAN_PC_1 | Incident | |||||||
Incident | 08/14/2018 | Has not led to Discharge | MULLIGAN_PC_1 | Incident | |||||||
Document Management | 08/14/2018 | Satisfied | MULLIGAN_PC_1 | Incident | |||||||
Record Document | 08/14/2018 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Site Inspection | 08/01/2018 | Minor Out of Compliance | MULLIGAN_PC_1 | 0/3 | Routine Compliance | ||||||
Letter | 08/01/2018 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||||||
Electronic Communication | 07/31/2018 | Satisfied | MULLIGAN_PC_1 | Routine Compliance | |||||||
Letter | 01/08/2018 | Satisfied | HECKMAN_DA_1 | Compliance Assistance | |||||||
Record Document | 12/04/2017 | Satisfied | ANTON_TM_1 | Compliance Assistance | |||||||
Incident | 05/11/2017 | Has not led to Discharge | ANTON_TM_1 | Incident | |||||||
Document Management | 05/11/2017 | Satisfied | ANTON_TM_1 | Incident | |||||||
Electronic Communication | 05/11/2017 | Satisfied | ANTON_TM_1 | Non-Compliance | |||||||
Electronic Communication | 05/11/2017 | Satisfied | ANTON_TM_1 | Non-Compliance | |||||||
Letter | 05/05/2017 | Satisfied | ANTON_TM_1 | Non-Compliance | |||||||
Site Inspection | 03/30/2017 | Minor Out of Compliance | ANTON_TM_1 | 0/3 | Routine Compliance | ||||||
Letter | 03/30/2017 | Satisfied | ANTON_TM_1 | Non-Compliance | |||||||
Incident | 05/20/2016 | Has not led to Discharge | HECKMAN_DA_1 | Incident | |||||||
Document Management | 10/05/2015 | Complete | HECKMAN_DA_1 | Incident | |||||||
Site Inspection | 05/14/2015 | In Compliance | HECKMAN_DA_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 08/01/2013 | In Compliance | COLSON_NJ_1 | 0/3 | Non-Compliance | ||||||
Site Inspection | 07/12/2013 | Minor Out of Compliance | COLSON_NJ_1 | 0/3 | Routine Compliance | ||||||
Letter | 07/12/2013 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
TCAR | 08/30/2011 | Satisfied | COLSON_NJ_1 | Closure | |||||||
Record Document | 08/29/2011 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Site Inspection | 07/18/2011 | Minor Out of Compliance | COLSON_NJ_1 | 0/3 | Routine Compliance | ||||||
Letter | 07/18/2011 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Record Document | 10/11/2010 | Satisfied | OSTENSEN_SA_1 | Routine Compliance | |||||||
Site Inspection | 10/06/2010 | In Compliance | OSTENSEN_SA_1 | 0/3 | Non-Compliance | ||||||
Letter | 09/24/2010 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Site Inspection | 09/24/2010 | Minor Out of Compliance | JUARISTIC_GK_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 06/07/2010 | In Compliance | COLSON_NJ_1 | 0/3 | Non-Compliance | ||||||
Letter | 05/19/2010 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Site Inspection | 05/19/2010 | Minor Out of Compliance | COLSON_NJ_1 | 0/3 | Non-Compliance | ||||||
Site Inspection | 05/06/2010 | Minor Out of Compliance | COLSON_NJ_1 | 0/3 | Non-Compliance | ||||||
Letter | 05/06/2010 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Letter | 04/20/2010 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Site Inspection | 04/20/2010 | Minor Out of Compliance | COLSON_NJ_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 04/13/2010 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Record Document | 06/22/2009 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Letter | 05/11/2009 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Site Inspection | 05/11/2009 | Major Out of Compliance | COLSON_NJ_1 | 0/3 | Non-Compliance | ||||||
Letter | 03/31/2009 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Site Inspection | 03/31/2009 | Minor Out of Compliance | COLSON_NJ_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 03/23/2009 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Record Document | 10/09/2008 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Record Document | 10/03/2008 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Site Inspection | 07/07/2008 | Minor Out of Compliance | OSTENSEN_SA_1 | 0/3 | Installation | ||||||
Letter | 07/07/2008 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Letter | 07/03/2008 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Site Inspection | 07/03/2008 | Minor Out of Compliance | OSTENSEN_SA_1 | 0/3 | Closure | ||||||
Record Document | 07/03/2008 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Record Document | 11/07/2007 | Satisfied | BAUER_DR_1 | Non-Compliance | |||||||
Letter | 10/31/2007 | Satisfied | BAUER_DR_1 | Non-Compliance | |||||||
Site Inspection | 10/30/2007 | Minor Out of Compliance | BAUER_DR_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 09/13/2007 | Satisfied | BAUER_DR_1 | Routine Compliance | |||||||
Letter | 08/21/2007 | Satisfied | HARMAN_GR | Non-Compliance | |||||||
Emergency Preparedness Information | 02/09/2007 | Satisfied | HARMAN_GR | Routine Compliance | |||||||
Site Inspection | 12/08/2006 | Minor Out of Compliance | HARMAN_GR | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 09/27/2006 | Satisfied | OSTENSEN_SA_1 | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
08/18/2023 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Scrape/sand/recoat all corrosion on the RUL STP head, repair/replace damaged wiring or conduit and submit pictures or a work order to Citrus County Environmental Health. | |||||||
08/18/2023 | 6015 | Minor | 4.3 Incident investigation not completed within 14 days, and/or no DRF or written confirmation received at the end of the 14-day investigation period. | Any failure of an integrity test should be investigated as an incident. Begin an incident investigation into how liquid is escaping the sump and perform integrity testing. Submit investigation and test results to Citrus County Environmental Health. | |||||||
08/18/2023 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | repair/replace the RUL #1 STP sump and perform an integrity test and provide documentation to Citrus County Environmental health. | |||||||
08/18/2023 | 6015 | Minor | 4.3 Incident investigation not completed within 14 days, and/or no DRF or written confirmation received at the end of the 14-day investigation period. | Any positive response of a leak detection device should be investigated as an incident. Begin an incident investigation into how liquid is entering the tank interstices and perform integrity testing . Submit investigation and test results to Citrus County Environmental Health. | |||||||
08/18/2023 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | . Remove the PUL EMCO sensor and repair/replace then retest. If liquid is found in secondary then a vacuum test will need to be performed. Submit all repair or testing documentation to Citrus County Environmental Health. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
06/19/2002 | COMPLETED | ||||||||||
03/16/1998 | COMPLETED | ||||||||||
12/26/1990 | COMPLETED | 75 | PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE | ||||||||