DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Northeast   Type    Retail Station
 
County Clay   Status    OPEN
 
ID 8503289   Latitude    30° 4' 21.2158
 
Name S & N OF FLORIDA INC
2476 BLANDING BLVD
Longitude    81° 51' 54.2472
  MIDDLEBURG, FL 32068-5162 LL Method    DGPS
 
Contact STEVE TRAN   LL Status    REVIEWED
 
Phone (508) 344-4384   Status Date    11/05/2003
 
Account Owner Information
 
Name S & N OF FLORIDA LLC
2476 BLANDING BLVD
MIDDLEBURG, FL 32068
Effective Date    04/21/2014
 
Contact STEVE TRAN
 
Phone (508) 344-4384
 
Email STATIONTEXACO@YAHOO.COM
  Placard # / Date    693807 - 06/24/2024
Property Owner Information
 
Name S & N OF FLORIDA LLC
2476 BLANDING BLVD
MIDDLEBURG, FL 32068
Effective Date    04/21/2014
 
Contact STEVE TRAN
 
Phone (508) 344-4384
 
Email STATIONTEXACO@YAHOO.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
7 12000 Unleaded Gas (B) 04/01/1998 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
8 12000 Unleaded Gas (B) 04/01/1998 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 10000 Unleaded Gas (B) 11/01/1981 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
(M) Spill containment bucket
  (C) Fiberglass (T) Annual tightness test/Inventory
 
 
Tank Tank Size Content Installed Placement Status
2 10000 Unleaded Gas (B) 11/01/1981 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
(M) Spill containment bucket
  (C) Fiberglass (T) Annual tightness test/Inventory
 
 
Tank Tank Size Content Installed Placement Status
3 10000 Unleaded Gas (B) 11/01/1981 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
(M) Spill containment bucket
  (C) Fiberglass (T) Annual tightness test/Inventory
 
 
Tank Tank Size Content Installed Placement Status
4 4000 Vehicular Diesel (D) 11/01/1981 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
(M) Spill containment bucket
  (C) Fiberglass (T) Annual tightness test/Inventory
 
 
Tank Tank Size Content Installed Placement Status
5 3000 Vehicular Diesel (D) 11/01/1981 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
(M) Spill containment bucket
  (C) Fiberglass (T) Annual tightness test/Inventory
 
 
Tank Tank Size Content Installed Placement Status
6 3000 Kerosene (K) 11/01/1981 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
(M) Spill containment bucket
  (C) Fiberglass (T) Annual tightness test/Inventory
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   06/08/2021 06/08/2023 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   06/08/2020 06/08/2021 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   04/16/2017 04/16/2018 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   04/16/2016 04/16/2017 COMMERCE & INDUSTRY
INSURANCE   04/16/2015 04/16/2016 COMMERCE & INDUSTRY
INSURANCE   04/16/2014 04/16/2015 COMMERCE & INDUSTRY
INSURANCE   09/01/2011 09/01/2012 COMMERCE & INDUSTRY
INSURANCE   09/01/2010 09/01/2011 COMMERCIAL INSURANCE
INSURANCE   09/07/2009 09/07/2010 COMMERCE & INDUSTRY
INSURANCE   09/07/2008 09/07/2009 COMMERCE & INDUSTRY
INSURANCE   06/19/1992 08/01/1996 FPLIPA
INSURANCE   08/31/1989 11/01/1991 FPLIPA
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
RRBD 08/22/2005 08/22/2005 COMPLIANCE ASSURANCE
 
TCI 04/18/2005 05/02/2005 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes LD TEST 2/15/05 4/4 PASS ANNUAL OPERABILITY 2/15/05 PASS
 
RRBD 03/31/2004 04/06/2004 COMPLIANCE ASSURANCE
 
RRBD 03/30/2004 03/31/2004 COMPLIANCE ASSURANCE
 
TCI 03/15/2004 03/29/2004 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes LD TEST 2/17/04 4/4 PASS
 
PDNE 06/24/2003 06/24/2003 COMPLIANCE ASSURANCE
 
TCI 01/14/2003 01/23/2003 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes LEAK DETECTOR TEST 1/8/03 4/4 PASS MONTHLY VISUAL CHECKS INCLUDING INTERSTICE
 
TCI 12/17/2001 12/17/2001 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes MANUALLY CHECKED INTERSTICE / COAXIAL FILLS HAVE FLOW SHUTOFF / LEAK DETECTOR TEST 12/3/01 4/4 PASS
 
RRBD 12/15/2000 12/18/2000 COMPLIANCE ASSURANCE
 
TCI 11/13/2000 11/27/2000 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
RRBD 12/01/1999 12/01/1999 BARNETT_P 0/0 COMPLIANCE ASSURANCE
 
TCI 09/13/1999 09/16/1999 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 02/25/2025 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 02/25/2025 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 02/24/2025 Major Out of Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Phone Conversation 01/31/2024 Satisfied MILLS_MM Enforcement
 
Phone Conversation 01/12/2024 Satisfied MILLS_MM Enforcement
 
Phone Conversation 12/06/2023 Satisfied MILLS_MM Enforcement
 
Letter 11/02/2023 Satisfied MILLS_MM Enforcement
 
Electronic Communication 05/29/2023 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Letter 05/29/2023 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 05/26/2023 Major Out of Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Electronic Communication 05/07/2023 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Meeting 05/07/2023 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Enforcement Referral 09/08/2022 Accepted MACK_BT Enforcement
 
Enforcement Tracking 09/08/2022 Closed Without Enforcement SACCHITELLO_E Enforcement
 
Enforcement Tracking 04/22/2021 Closed Without Enforcement HILL_K Enforcement
 
Letter 02/07/2021 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Meeting 02/07/2021 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 02/07/2021 Major Out of Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Electronic Communication 02/07/2021 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Enforcement Referral 06/23/2020 Accepted HARRINGTON_RD_1 Enforcement
 
Electronic Communication 06/19/2020 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Letter 03/18/2018 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 03/05/2018 Minor Out of Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Letter 09/29/2017 Satisfied OBRIEN_S Compliance Assistance
 
Letter 09/26/2017 Satisfied OBRIEN_S Compliance Assistance
 
Letter 06/30/2017 Satisfied HILL_K Enforcement
 
Site Inspection 06/26/2017 Minor Out of Compliance OBRIEN_S 0/2 Enforcement
 
Electronic Communication 06/26/2017 Satisfied OBRIEN_S Enforcement
 
Phone Conversation 06/26/2017 Satisfied OBRIEN_S Enforcement
 
Phone Conversation 05/24/2017 Satisfied OBRIEN_S Enforcement
 
Electronic Communication 05/24/2017 Satisfied OBRIEN_S Enforcement
 
Phone Conversation 05/24/2017 Satisfied OBRIEN_S Enforcement
 
Phone Conversation 05/24/2017 Satisfied OBRIEN_S Enforcement
 
Phone Conversation 05/24/2017 Satisfied OBRIEN_S Enforcement
 
Phone Conversation 05/24/2017 Satisfied OBRIEN_S Enforcement
 
Phone Conversation 05/24/2017 Satisfied OBRIEN_S Enforcement
 
Electronic Communication 05/18/2017 Satisfied OBRIEN_S Enforcement
 
Phone Conversation 05/10/2017 Satisfied OBRIEN_S Enforcement
 
Electronic Communication 04/28/2017 Satisfied OBRIEN_S Enforcement
 
Phone Conversation 04/19/2017 Satisfied OBRIEN_S Enforcement
 
Electronic Communication 04/10/2017 Satisfied OBRIEN_S Enforcement
 
Phone Conversation 03/13/2017 Satisfied DEFALCO_L Enforcement
 
Electronic Communication 02/27/2017 Satisfied DEFALCO_L Enforcement
 
Phone Conversation 02/27/2017 Satisfied DEFALCO_L Enforcement
 
Enforcement Referral 12/29/2016 Accepted HARRINGTON_RD_1 Enforcement
 
Letter 10/10/2016 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Electronic Communication 05/18/2016 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Letter 05/18/2016 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Site Inspection 05/18/2016 Minor Out of Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Phone Conversation 09/22/2014 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Letter 04/25/2014 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Site Inspection 04/25/2014 Minor Out of Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Electronic Communication 04/25/2014 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 03/22/2012 In Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Emergency Preparedness Information 03/22/2012 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Record Document 07/05/2011 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Letter 06/21/2011 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Letter 04/01/2011 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Site Inspection 04/01/2011 Minor Out of Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Record Document 07/12/2010 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Letter 03/09/2010 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Site Inspection 03/09/2010 Minor Out of Compliance HARRINGTON_RD_1 0/2 Routine Compliance
 
Record Document 12/01/2009 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Letter 10/13/2009 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Record Document 04/30/2009 Satisfied BARNETT_PC_1 Non-Compliance
 
Letter 04/30/2009 Satisfied BARNETT_PC_1 Non-Compliance
 
Site Inspection 04/30/2009 Minor Out of Compliance BARNETT_PC_1 0/2 Routine Compliance
 
Record Document 04/30/2009 Satisfied BARNETT_PC_1 Non-Compliance
 
Letter 05/30/2008 Satisfied BARNETT_PC_1 Non-Compliance
 
Site Inspection 05/30/2008 Minor Out of Compliance BARNETT_PC_1 0/2 Routine Compliance
 
Record Document 01/11/2008 Satisfied BARNETT_PC_1 Non-Compliance
 
Letter 11/29/2007 Satisfied BARNETT_PC_1 Non-Compliance
 
Letter 06/27/2007 Satisfied BARNETT_PC_1 Non-Compliance
 
Site Inspection 06/27/2007 Minor Out of Compliance BARNETT_PC_1 0/2 Routine Compliance
 
Emergency Preparedness Information 02/13/2007 Satisfied BARNETT_PC_1 Routine Compliance
 
Emergency Preparedness Information 09/20/2006 Satisfied BARNETT_PC_1 Routine Compliance
 
Record Document 06/16/2006 Satisfied BARNETT_PC_1 Non-Compliance
 
Letter 06/02/2006 Satisfied BARNETT_PC_1 Non-Compliance
 
Site Inspection 06/02/2006 Minor Out of Compliance BARNETT_PC_1 0/2 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/24/2025 6066 Minor 4.4 Not repaired per applicable standards. Repair the damaged entry boot. Provide post-repair hydrostatic test of the sump.
 
02/24/2025 6011 SNC-B 2.8 No financial responsibility instrument or expired instrument for < 180 days. Provide Storage Tank Financial Responsibility policy and facility-completed CFR. The CFR form will be sent to the facility with this report.
 
02/07/2021 4076 Minor 4.11 Failure to conduct required periodic containment and interstitial integrity testing. Provide integrity test results as listed above.
 
02/07/2021 4001 Minor 2.2 Operator certification requirements not met. Provide verification of Tank Operator Certifications as required by the UST rule.
 
02/07/2021 4068 Minor 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. Address the 93 sump corrosion. Provide documentation. Alternately the tanks can be placed out of service or be closed.
 
02/07/2021 4077 Minor 4.12 Spill containment, sumps, and interstices not accessible. Water/regulated substances not timely removed. Petroleum contact water not properly managed. Remove the water from the 87 tank interstice. Monitor for on-going water intrusion. A tank tightness test may be required if the issue persists.
 
02/07/2021 4015 Minor 2.10 Incomplete documentation demonstrating financial responsibility. Complete and provide the CFR Form (required to be maintained with Tank Insurance).
 
02/07/2021 4059 SNC-B 4.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days.) For electronically monitored sumps, visual inspections not conducted every 6 months. This violation may lead to Placard Revocation and Delivery Prohibition. Conduct monthly tank inspections and document. Alternately, the tanks may be placed out of service or closed.
 
03/05/2018 4076 Minor 4.11 Failure to conduct required periodic containment and interstitial integrity testing. Have the spill buckets hydro tested by a third party. Provide documentation of results.
 
03/05/2018 4057 Minor 4.31 Overfill protection devices not registered or tested annually. Have the overfill prevention devices tested. Provide documentation of results. * For tank compartments that have both ball check valves and flappers for the same product, one of the devices must be removed, preferably the ball check valves.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
11/28/1988   COMPLETED 55 EARLY DETECTION INCENTIVE-ELIGIBLE