DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Northeast   Type    Retail Station
 
County Clay   Status    OPEN
 
ID 8503313   Latitude    29° 43' 15.4026
 
Name NICKS KWIK STOP
8800 HWY 21
Longitude    82° 2' 46.4432
  MELROSE, FL 32666 LL Method    DGPS
 
Contact WENDA LEWIS   LL Status    REVIEWED
 
Phone   Status Date    10/30/2003
 
Account Owner Information
 
Name LEWIS OIL CO INC
PO BOX 141286
GAINESVILLE, FL 32614
Effective Date    05/20/1994
 
Contact WENDA LEWIS (MGR)
 
Phone (352) 376-3293
 
Email WLEWIS@LEWISOILCO.COM
  Placard # / Date    701579 - 10/02/2024
Property Owner Information
 
Name LEWIS OIL CO INC
PO BOX 141286
GAINESVILLE, FL 32614
Effective Date    07/18/2002
 
Contact WENDA LEWIS (MGR)
 
Phone (352) 376-3293
 
Email WLEWIS@LEWISOILCO.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
4 16000 Unleaded Gas (B) 05/01/2002 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(L) Compartmented
(M) Spill containment bucket
(O) Tight fill
(R) Double wall - tank jacket
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
1 4000 Unleaded Gas (B) 08/01/1981 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(O) Vapor monitoring
 
 
Tank Tank Size Content Installed Placement Status
2 8000 Unleaded Gas (B) 08/01/1981 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
  (D) External protective coating
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(O) Vapor monitoring
 
 
Tank Tank Size Content Installed Placement Status
3 3000 Unleaded Gas (B) 08/01/1981 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
  (D) External protective coating
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(O) Vapor monitoring
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   05/14/2022 05/14/2024 SCOTTSDALE INSURANCE COMPANY
INSURANCE   05/14/2020 05/14/2022 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/14/2020 05/14/2022 SCOTTSDALE INSURANCE COMPANY
INSURANCE   05/14/2019 05/14/2020 ACE
INSURANCE   05/14/2018 05/14/2019 ILLINOIS UNION
INSURANCE   05/14/2017 05/14/2018 ACE
INSURANCE   05/14/2016 05/14/2017 AIG
INSURANCE   01/31/2015 01/31/2016 AIG
INSURANCE   01/31/2015 05/14/2016 ACE
INSURANCE   01/31/2014 01/31/2015 AIG
INSURANCE   01/31/2013 01/31/2014 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/31/2012 01/31/2013 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/31/2011 01/31/2012 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/31/2011 01/31/2012 CHEROKEE INSURANCE COMPANY
INSURANCE   01/31/2010 01/31/2011 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/31/2010 01/31/2011 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/31/2009 01/31/2010 AISLIC
INSURANCE   01/31/2007 01/31/2008 ZURICH-AMERICAN
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
RRBD 12/08/2005 12/09/2005 BARNETT_P 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes LD TEST 4/16/05 3/3 PASS
 
TCI 11/03/2005 11/16/2005 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes ANNUAL OPERABILITY TEST 11/3/05 ALL SENSORS PASS
 
RRBD 11/23/2004 11/23/2004 COMPLIANCE ASSURANCE
 
TCI 10/21/2004 11/04/2004 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes LEAK DETECTOR TEST 4/14/04 3/3 PASS
 
RRBD 11/20/2003 11/20/2003 COMPLIANCE ASSURANCE
 
TCI 09/04/2003 09/08/2003 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes ANNUAL OPERABILITY 9/4/03 LD TEST 4/03 3/3 PASS
 
RRBD 09/30/2002 10/23/2002 COMPLIANCE ASSURANCE
 
TCI 08/27/2002 09/11/2002 SIGNIFICANT OUT-OF-COMPLIANCE BARNETT_P 0/1 COMPLIANCE ASSURANCE
 
TIN 05/03/2002 06/04/2002 IN-COMPLIANCE BARNETT_P 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes INSTALL OF 1 DOUBLEWALL, COMPARTMENTED UST (GLASSTEEL II) PISCES PIPING/SUMPS TOTAL CONTAINMENT DISPENSER LINERS (EXISTING)
 
TXI 04/30/2002 06/04/2002 IN-COMPLIANCE BARNETT_P 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes CLOSURE OF TANKS / PIPING KEPT DISPENSER LINERS
 
TCI 08/14/2001 08/20/2001 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/3 COMPLIANCE ASSURANCE
 
TCI 08/22/2000 08/29/2000 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/3 COMPLIANCE ASSURANCE
 
TCI 08/18/1999 09/02/1999 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/3 COMPLIANCE ASSURANCE
 
PDNE 03/29/1999 03/29/1999 BARNETT_P 0/0 COMPLIANCE ASSURANCE
 
UTCI 08/17/1998 09/03/1998 MINOR OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 10/02/2024 Satisfied MCNEIL_A Enforcement
 
Enforcement Referral 08/12/2024 Accepted HARRINGTON_RD_1 Enforcement
 
Document Management 05/06/2024 Satisfied HARRINGTON_RD_1 Incident
 
Site Inspection 04/25/2024 Minor Out of Compliance HARRINGTON_RD_1 0/1 Routine Compliance
 
Electronic Communication 04/25/2024 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 04/25/2024 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 04/25/2024 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Letter 04/25/2024 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 12/12/2021 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Letter 12/12/2021 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Electronic Communication 12/12/2021 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 12/10/2021 In Compliance HARRINGTON_RD_1 0/1 Routine Compliance
 
Record Document 10/01/2019 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Letter 09/15/2019 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 09/15/2019 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 09/15/2019 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 09/10/2019 Minor Out of Compliance HARRINGTON_RD_1 0/1 Routine Compliance
 
Site Inspection 05/19/2017 In Compliance HARRINGTON_RD_1 0/1 Routine Compliance
 
Site Inspection 07/01/2014 In Compliance HARRINGTON_RD_1 0/1 Routine Compliance
 
Record Document 01/30/2013 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Emergency Preparedness Information 01/25/2013 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 01/25/2013 Minor Out of Compliance HARRINGTON_RD_1 0/1 Routine Compliance
 
Electronic Communication 01/25/2013 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Letter 01/25/2013 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Site Inspection 04/13/2011 In Compliance BARNETT_PC_1 0/1 Routine Compliance
 
Record Document 10/29/2010 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Letter 06/16/2010 Satisfied BARNETT_PC_1 Non-Compliance
 
Site Inspection 06/16/2010 Minor Out of Compliance BARNETT_PC_1 0/1 Routine Compliance
 
Record Document 10/02/2007 Satisfied BARNETT_PC_1 Non-Compliance
 
Site Inspection 09/19/2007 In Compliance BARNETT_PC_1 0/1 Routine Compliance
 
Letter 09/19/2007 Satisfied BARNETT_PC_1 Non-Compliance
 
Record Document 06/15/2007 Satisfied BARNETT_PC_1 Non-Compliance
 
Emergency Preparedness Information 02/06/2007 Satisfied BARNETT_PC_1 Routine Compliance
 
Site Inspection 11/16/2006 Minor Out of Compliance BARNETT_PC_1 0/1 Routine Compliance
 
Letter 11/16/2006 Satisfied BARNETT_PC_1 Non-Compliance
 
Emergency Preparedness Information 09/21/2006 Satisfied BARNETT_PC_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
04/25/2024 6062 Minor 2.5 Release detection devices not tested annually. Provide sensor and line leak detector test result documentation.
 
04/25/2024 6074 Minor 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. Please maintain Veeder Root sensor status reports along with the monthly visual inspection documentation. This violation will be closed by inspector.
 
04/25/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Provide overfill prevention device test results.
 
04/25/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Contact inspector for re-inspection. The dispenser liners must be accesessible.
 
04/25/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Provide the Integrity Test result documentation for the single wall spill buckets, STP sumps and dispenser liners.
 
04/22/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove fuel from the diesel STP sump. Dispose properly. Provide verification.
 
04/22/2024 6009 Minor 4.1 Incident Notification Form (INF) not received in a timely manner. File Incident Notification Form in regards to the fuel in the diesel STP sump. Investigate Incident to determine if a discharge has occurred (recommend hydro test of the sump and test of the chase pipe). Provide investigation results.
 
04/22/2024 6066 Minor 4.4 Not repaired per applicable standards. Perform hydrostatic test of the 87 spill bucket. Provide test result documentation.
 
04/22/2024 6066 Minor 4.4 Not repaired per applicable standards. Install break aways as required on dispenser hoses. Provide verification.
 
 
 
No Discharges Found