DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District Southeast   Type    Retail Station
 
County Miami-Dade   Status    OPEN
 
ID 8505889   Latitude    25° 56' 42.6813
 
Name OJUS AUTOMOTIVE
18310 W DIXIE HWY
Longitude    80° 8' 55.6518
  NORTH MIAMI BEACH, FL 33160-2046 LL Method    DPHO
 
Contact ELIZABETH TAHARALLY   LL Status    REVIEWED
 
Phone (305) 891-1717   Status Date    02/21/2024
 
Account Owner Information
 
Name OJUS AUTOMOTIVE
18310 W DIXIE HWY
NORTH MIAMI BEACH, FL 33160-2046
Effective Date    07/01/1985
 
Contact ELIZABETH TAHARALLY
 
Phone (305) 891-1717
 
Email LISA300E@YAHOO.COM
  Placard # / Date    702451 - 10/22/2024
Property Owner Information
 
Name OJUS AUTOMOTIVE
18310 W DIXIE HWY
NORTH MIAMI BEACH, FL 33160-2046
Effective Date    12/06/2006
 
Contact ELIZABETH TAHARALLY
 
Phone (305) 891-1717
 
Email LISA300E@YAHOO.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
15 16000 Ethanol E10 (8) 03/01/2010 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(L) Automatic tank gauging - USTs
(N) Groundwater monitoring
 
 
Tank Tank Size Content Installed Placement Status
14 16000 Unleaded Gas (B) 02/01/2010 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
 
 
 
Tank Tank Size Content Installed Placement Status
8 10000 Unleaded Gas (B) 08/01/1990 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(8) Manually sampled wells
(H) Mechanical line leak detector
(N) Groundwater monitoring
 
 
Tank Tank Size Content Installed Placement Status
9 8000 Unleaded Gas (B) 08/01/1990 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(8) Manually sampled wells
(H) Mechanical line leak detector
(N) Groundwater monitoring
 
 
Tank Tank Size Content Installed Placement Status
1 4000 Unleaded Gas (B) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
10 4000 Unknown/Not Reported (Y) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (Y) Unknown (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
11 4000 Unknown/Not Reported (Y) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
 
 
 
Tank Tank Size Content Installed Placement Status
12 550 Unknown/Not Reported (Y) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
 
 
 
Tank Tank Size Content Installed Placement Status
13 550 Unknown/Not Reported (Y) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
 
 
 
Tank Tank Size Content Installed Placement Status
2 4000 Unleaded Gas (B) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
3 4000 Leaded Gas (A) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
4 4000 Leaded Gas (A) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
5 4000 Vehicular Diesel (D) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
6 4000 Vehicular Diesel (D) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
7 4000 Unleaded Gas (B) UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass (Y) Unknown
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   05/03/2023 05/03/2024 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   05/03/2021 05/03/2022 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   05/03/2019 05/03/2020 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   05/03/2018 05/03/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   05/03/2017 05/03/2018 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   05/03/2016 05/03/2017 COMMERCE & INDUSTRY
INSURANCE   05/03/2015 05/03/2016 COMMERCE & INDUSTRY
INSURANCE   05/03/2014 05/03/2015 COMMERCE & INDUSTRY
INSURANCE   05/03/2012 05/03/2013 COMMERCE & INDUSTRY
INSURANCE   04/23/2010 04/23/2011 ZURICH-AMERICAN
INSURANCE   02/10/2008 02/10/2009 ZURICH-AMERICAN
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
RRBD 10/05/2005 10/19/2005 SHER, R 0/3 COMPLIANCE ASSURANCE
 
TCI 09/28/2005 09/30/2005 MINOR OUT-OF-COMPLIANCE SHER, R 0/2 COMPLIANCE ASSURANCE
 
TCR 11/04/2004 11/08/2004 IN-COMPLIANCE SHER, R 0/3 COMPLIANCE ASSURANCE
 
TCI 10/15/2004 10/18/2004 SIGNIFICANT OUT-OF-COMPLIANCE SHER, R 0/2 COMPLIANCE ASSURANCE
 
TIN 06/03/2004 06/04/2004 IN-COMPLIANCE SHER, R 0/2 COMPLIANCE ASSURANCE
 
TCR 01/16/2004 01/20/2004 IN-COMPLIANCE SHER, R 0/2 COMPLIANCE ASSURANCE
 
TCR 01/14/2004 01/20/2004 MINOR OUT-OF-COMPLIANCE SHER, R 0/2 COMPLIANCE ASSURANCE
 
TCI 12/30/2003 01/05/2004 MINOR OUT-OF-COMPLIANCE SHER, R 0/2 COMPLIANCE ASSURANCE
 
TCR 03/28/2003 03/31/2003 IN-COMPLIANCE SHER, R 0/1 COMPLIANCE ASSURANCE
 
TCI 03/10/2003 03/12/2003 MINOR OUT-OF-COMPLIANCE SHER, R 0/2 COMPLIANCE ASSURANCE
 
TCI 12/13/2001 12/20/2001 IN-COMPLIANCE SHER_R 0/2 COMPLIANCE ASSURANCE
 
TCI 12/15/2000 12/20/2000 IN-COMPLIANCE SHER, R 0/2 COMPLIANCE ASSURANCE
 
TCI 01/07/2000 01/31/2000 IN-COMPLIANCE SHER, R 0/2 COMPLIANCE ASSURANCE
 
TCI 06/29/1999 07/09/1999 IN-COMPLIANCE SHER_R 0/2 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 02/27/2024 Satisfied RODRIGUEZ_F Routine Compliance
 
Letter 02/27/2024 Satisfied RODRIGUEZ_F Compliance Assistance
 
Site Inspection 02/27/2024 Major Out of Compliance RODRIGUEZ_F 0/1 Routine Compliance
 
Phone Conversation 11/30/2023 Satisfied JACQUET_F_1 Compliance Assistance
 
Electronic Communication 11/27/2023 Satisfied JACQUET_F_1 Compliance Assistance
 
Site Inspection 11/27/2023 In Compliance JACQUET_F_1 0/1 Compliance Assistance
 
Letter 11/27/2023 Satisfied JACQUET_F_1 Compliance Assistance
 
Electronic Communication 11/20/2023 Satisfied JACQUET_F_1 Compliance Assistance
 
Electronic Communication 11/02/2021 Satisfied JACQUET_F_1 Compliance Assistance
 
Site Inspection 10/27/2021 Major Out of Compliance JACQUET_F_1 0/1 Routine Compliance
 
Letter 10/27/2021 Satisfied JACQUET_F_1 Compliance Assistance
 
Electronic Communication 09/20/2021 Satisfied JACQUET_F_1 Routine Compliance
 
Phone Conversation 09/03/2021 Satisfied JACQUET_F_1 Routine Compliance
 
Phone Conversation 09/03/2021 Satisfied JACQUET_F_1 Routine Compliance
 
Electronic Communication 09/03/2021 Satisfied JACQUET_F_1 Routine Compliance
 
Site Inspection 08/07/2019 In Compliance CABRERA_VE_1 0/1 Routine Compliance
 
Letter 08/07/2019 Satisfied CABRERA_VE_1 Routine Compliance
 
Electronic Communication 08/02/2019 Satisfied SANPEDRO_A_2 Routine Compliance
 
Site Inspection 01/23/2017 In Compliance DEZAYAS_A_1 0/1 Routine Compliance
 
Electronic Communication 01/23/2017 Satisfied DEZAYAS_A_1 Routine Compliance
 
Phone Conversation 01/04/2017 Satisfied DEZAYAS_A_1 Routine Compliance
 
Electronic Communication 01/04/2017 Satisfied DEZAYAS_A_1 Routine Compliance
 
Phone Conversation 10/03/2016 Satisfied DEZAYAS_A_1 Complaint
 
Site Inspection 09/28/2016 Major Out of Compliance DEZAYAS_A_1 0/1 Complaint
 
Letter 09/28/2016 Satisfied DEZAYAS_A_1 Non-Compliance
 
Document Management 09/28/2016 Satisfied DEZAYAS_A_1 Incident
 
Incident 09/28/2016 Has not led to Discharge DEZAYAS_A_1 Incident
 
Electronic Communication 05/22/2015 Satisfied DEZAYAS_A_1 Non-Compliance
 
Electronic Communication 05/22/2015 Satisfied DEZAYAS_A_1 Routine Compliance
 
Site Inspection 04/28/2015 In Compliance DEZAYAS_A_1 0/1 Non-Compliance
 
Letter 01/26/2015 Satisfied DEZAYAS_A_1 Non-Compliance
 
Site Inspection 01/20/2015 Minor Out of Compliance DEZAYAS_A_1 0/1 Routine Compliance
 
Emergency Preparedness Information 01/07/2015 Satisfied DEZAYAS_A_1 Routine Compliance
 
Phone Conversation 01/05/2015 Satisfied DEZAYAS_A_1 Routine Compliance
 
Emergency Preparedness Information 01/09/2013 Satisfied DASHTAKI_K_1 Routine Compliance
 
Site Inspection 01/09/2013 In Compliance DASHTAKI_K_1 0/1 Routine Compliance
 
Phone Conversation 01/09/2013 Satisfied DASHTAKI_K_1 Routine Compliance
 
Enforcement Tracking 10/23/2012 Closed Without Enforcement SHER_RC_1 Enforcement
 
Letter 05/04/2011 Satisfied SHER_RC_1 Non-Compliance
 
Site Inspection 04/07/2011 In Compliance SHER_RC_1 0/1 Non-Compliance
 
Site Inspection 03/23/2011 Minor Out of Compliance SHER_RC_1 0/1 Routine Compliance
 
TCAR 05/26/2010 Satisfied MAS_JR_1 Closure
 
Meeting 04/07/2010 Satisfied SHER_RC_1 Routine Compliance
 
Meeting 04/07/2010 Satisfied SHER_RC_1 Routine Compliance
 
Site Inspection 03/16/2010 In Compliance SHER_RC_1 0/1 Installation
 
Site Inspection 03/16/2010 In Compliance SHER_RC_1 0/1 Non-Compliance
 
Site Inspection 03/01/2010 In Compliance SHER_RC_1 0/1 Installation
 
Meeting 02/22/2010 Satisfied SHER_RC_1 Routine Compliance
 
Site Inspection 02/18/2010 In Compliance SHER_RC_1 0/2 Closure
 
Document Management 02/08/2010 Complete CORREA_LI_1 Routine Compliance
 
Meeting 02/04/2010 Satisfied SHER_RC_1 Routine Compliance
 
Site Inspection 02/03/2010 In Compliance PADRON_JE_1 0/2 Installation
 
Site Inspection 08/11/2009 Major Out of Compliance SHER_RC_1 0/2 Routine Compliance
 
Issue Document 08/11/2009 Satisfied SHER_RC_1 Enforcement
 
Letter 08/11/2009 Satisfied SHER_RC_1 Non-Compliance
 
Enforcement Referral 08/11/2009 Accepted SHER_RC_1 Enforcement
 
Site Inspection 09/19/2008 In Compliance SHER_RC_1 0/4 Non-Compliance
 
Site Inspection 09/16/2008 Minor Out of Compliance SHER_RC_1 0/2 Routine Compliance
 
Letter 09/16/2008 Satisfied SHER_RC_1 Non-Compliance
 
Site Inspection 10/30/2007 In Compliance SHER_RC_1 0/2 Non-Compliance
 
Site Inspection 10/05/2007 Minor Out of Compliance SHER_RC_1 0/2 Non-Compliance
 
Site Inspection 09/25/2007 Minor Out of Compliance SHER_RC_1 0/2 Non-Compliance
 
Site Inspection 08/28/2007 Minor Out of Compliance SHER_RC_1 0/2 Routine Compliance
 
Letter 08/28/2007 Satisfied SHER_RC_1 Non-Compliance
 
Emergency Preparedness Information 02/06/2007 Satisfied SHER_RC_1 Routine Compliance
 
Site Inspection 11/03/2006 In Compliance SHER_RC_1 0/2 Routine Compliance
 
Emergency Preparedness Information 09/22/2006 Satisfied SHER_RC_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/27/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove and properly dispose of liquid observed in the STP sumps.
 
02/27/2024 6061 SNC-B 4.12 Release detection devices for integral piping do not meet general standards. Provide current and passing operability test of the mechanical line leak detectors.
 
02/27/2024 6074 Minor 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. Provide monthly visual inspection logs – (visual inspection of storage tank system, includes sumps, fill ports, nozzles, leak detection, secondary containment, etc.) - 3 years’ worth of records must be available for review.
 
02/27/2024 6059 SNC-B 4.9 Release detection shall be constructed and installed so that groundwater, rainfall, or soil moisture will not render the release detection method used inoperable. Clear alarm on the Veeder-Root Panel. Currently lists Fuel Alarm on the Premium STP sensor. Provide photo of sensor status report once alarm is resolved.
 
02/27/2024 6062 Minor 2.5 Release detection devices not tested annually. Provide current and passing operability test of the release detection devices.
 
02/27/2024 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Provide current and passing operability test of the overfill protection devices.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
08/15/1994   COMPLETED 11 PETROLEUM CLEANUP PARTICIPATION PROGRAM-ELIGIBLE
 
12/01/1985   ACTIVE 11 EARLY DETECTION INCENTIVE-ELIGIBLE