DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Northwest   Type    Retail Station
 
County Escambia   Status    OPEN
 
ID 8507876   Latitude    30° 25' 3.9216
 
Name WINDY CITY PHILLYS INC
550 N NEW WARRINGTON RD
Longitude    87° 16' 30.954
  PENSACOLA, FL 32506-5859 LL Method    DPHO
 
Contact JIM DYKES   LL Status    REVIEWED
 
Phone (850) 456-3838   Status Date    03/26/2015
 
Account Owner Information
 
Name WINDY CITY PHILLYS INC
550 N NEW WARRINGTON RD
PENSACOLA, FL 32506
Effective Date    01/25/2018
 
Contact AMEER ABDELRAHMAN
 
Phone (850) 912-8030
 
Email RAMEER21@GMAIL.COM
  Placard # / Date    655930 - 06/08/2023
Property Owner Information
 
Name QUALITY ENTERPRISES OF NW FL INC
550 NEW WARRINGTON RD
PENSACOLA, FL 32505
Effective Date    06/17/2002
 
Contact JIM DYKES
 
Phone (850) 456-3838
 
Email
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
5 12000 Unleaded Gas (B) 08/01/1995 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(G) Sacrificial anode CP
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
6 8000 Unleaded Gas (B) 08/01/1995 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(G) Sacrificial anode CP
(I) Double wall
(M) Spill containment bucket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 8000 Unleaded Gas (B) 07/01/1971 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(H) Impressed current CP
  (E) Cathodic protection (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
2 6000 Unleaded Gas (B) 07/01/1971 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(H) Impressed current CP
  (E) Cathodic protection (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
3 6000 Unleaded Gas (B) 07/01/1971 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(H) Impressed current CP
  (E) Cathodic protection (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
4 1000 Waste Oil (L) 07/01/1971 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(H) Impressed current CP
  (E) Cathodic protection (8) Manually sampled wells
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
EXEMPT-NOT REQUIRED   01/11/2017
INSURANCE   02/05/2018 02/05/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   07/17/2013 07/17/2014 COMMERCE & INDUSTRY
INSURANCE   07/17/2012 07/17/2013 COMMERCE & INDUSTRY
INSURANCE   07/17/2010 07/17/2011 COMMERCE & INDUSTRY
INSURANCE   07/17/2009 07/17/2010 COMMERCE & INDUSTRY
INSURANCE   07/17/2008 07/17/2009 COMMERCE & INDUSTRY
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 12/20/2005 01/06/2006 IN-COMPLIANCE JOHN S. STEVENSON 2/0 COMPLIANCE ASSURANCE
 
 Completion Notes NO VIOLATIONS FOUND THIS INSPECTION.
 
TCI 11/17/2004 11/19/2004 IN-COMPLIANCE JOSEPH D. THAYER 2/0 COMPLIANCE ASSURANCE
 
RRBD 05/20/2004 06/03/2004 COMPLIANCE ASSURANCE
 
TCI 05/19/2004 06/02/2004 SIGNIFICANT OUT-OF-COMPLIANCE ARTHUR B. TISSINGTON 0/2 COMPLIANCE ASSURANCE
 
TCI 03/25/2003 06/02/2004 IN-COMPLIANCE JOHN S. STEVENSON 0/2 COMPLIANCE ASSURANCE
 
TCI 05/09/2002 05/23/2002 IN-COMPLIANCE JOHN S. STEVENSON 0/2 COMPLIANCE ASSURANCE
 
TCI 04/24/2001 05/01/2001 IN-COMPLIANCE STEVENSON_JS 2/0 COMPLIANCE ASSURANCE
 
TCI 02/17/2000 02/23/2000 IN-COMPLIANCE STEVENSON_JS 0/2 COMPLIANCE ASSURANCE
 
TIN 02/10/2000 02/23/2000 IN-COMPLIANCE HOLLINGSHEAD_JB 0/2 COMPLIANCE ASSURANCE
 
RRBD 08/18/1999 08/19/1999 STEVENSON_JS 0/0 COMPLIANCE ASSURANCE
 
TCI 06/22/1999 06/25/1999 SIGNIFICANT OUT-OF-COMPLIANCE STEVENSON_J 0/2 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 10/25/2024 Satisfied PROFFITT_B Routine Compliance
 
Enforcement Referral 07/23/2024 Accepted ELLIOTT_EV_1 Enforcement
 
Electronic Communication 06/03/2024 Satisfied ELLIOTT_EV_1 Compliance Assistance
 
Site Inspection 04/25/2024 Major Out of Compliance ELLIOTT_EV_1 0/2 Compliance Assistance
 
Letter 04/25/2024 Satisfied ELLIOTT_EV_1 Compliance Assistance
 
Meeting 04/22/2024 Satisfied ELLIOTT_EV_1 Compliance Assistance
 
Letter 04/03/2024 Satisfied ELLIOTT_EV_1 Compliance Assistance
 
Site Inspection 04/03/2024 Major Out of Compliance ELLIOTT_EV_1 0/2 Routine Compliance
 
Electronic Communication 04/02/2024 Satisfied ELLIOTT_EV_1 Routine Compliance
 
Record Document 07/20/2023 Satisfied MERRITT_S Enforcement
 
Record Document 07/10/2023 Satisfied MERRITT_S Enforcement
 
Electronic Communication 04/11/2023 Satisfied MERRITT_S Enforcement
 
Enforcement Referral 08/24/2022 Accepted GARTIN_D Enforcement
 
Electronic Communication 08/18/2022 Satisfied GARTIN_D Compliance Assistance
 
Electronic Communication 08/18/2022 Satisfied GARTIN_D Compliance Assistance
 
Letter 06/08/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 06/02/2022 Major Out of Compliance GARTIN_D 0/2 Routine Compliance
 
Electronic Communication 06/02/2022 Satisfied GARTIN_D Routine Compliance
 
Electronic Communication 06/02/2022 Satisfied GARTIN_D Routine Compliance
 
Document Management 03/22/2022 Satisfied MERRITT_S Enforcement
 
Document Management 12/14/2021 Satisfied MERRITT_S Enforcement
 
Document Management 07/07/2021 Satisfied MERRITT_S Enforcement
 
Electronic Communication 03/17/2021 Satisfied MERRITT_S Enforcement
 
Electronic Communication 03/02/2021 Satisfied MERRITT_S Enforcement
 
Enforcement Referral 12/26/2019 Accepted BRAGG_SD_2 Enforcement
 
Record Document 11/19/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Issue Document 11/12/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 11/12/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 11/12/2019 Major Out of Compliance BRAGG_SD_2 0/2 Routine Compliance
 
Letter 02/28/2018 Satisfied WILSON_ML_1 Compliance Assistance
 
Issue Document 02/28/2018 Satisfied WILSON_ML_1 Compliance Assistance
 
Enforcement Referral 02/26/2018 Accepted BRAGG_SD_2 Enforcement
 
Enforcement Tracking 02/26/2018 Closed Without Enforcement GILLMAN_M Enforcement
 
Site Inspection 02/23/2018 In Compliance BRAGG_SD_2 0/2 Compliance Assistance
 
Letter 07/31/2017 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 07/31/2017 Major Out of Compliance BRAGG_SD_2 0/2 Routine Compliance
 
Issue Document 07/31/2017 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 09/30/2015 In Compliance PAYNE_CL_1 0/2 Routine Compliance
 
Site Inspection 11/13/2013 In Compliance PAYNE_CL_1 0/2 Non-Compliance
 
Letter 10/30/2013 Satisfied DAURIA_KL_1 Non-Compliance
 
Site Inspection 10/29/2013 Minor Out of Compliance PAYNE_CL_1 0/2 Routine Compliance
 
Emergency Preparedness Information 10/29/2013 Satisfied PAYNE_CL_1 Routine Compliance
 
Site Inspection 06/25/2013 In Compliance PAYNE_CL_1 0/2 Non-Compliance
 
Letter 04/10/2013 Satisfied DAURIA_KL_1 Non-Compliance
 
Emergency Preparedness Information 04/09/2013 Satisfied PAYNE_CL_1 Routine Compliance
 
Site Inspection 04/09/2013 Minor Out of Compliance PAYNE_CL_1 0/2 Routine Compliance
 
Emergency Preparedness Information 03/16/2011 Satisfied TISSINGTON_AB_1 Routine Compliance
 
Site Inspection 03/16/2011 In Compliance TISSINGTON_AB_1 0/2 Routine Compliance
 
Phone Conversation 06/07/2010 Satisfied TISSINGTON_AB_1 Routine Compliance
 
Letter 05/17/2010 Satisfied PIERCE_LL_1 Non-Compliance
 
Site Inspection 05/11/2010 Minor Out of Compliance TISSINGTON_AB_1 0/2 Routine Compliance
 
Emergency Preparedness Information 05/11/2010 Satisfied TISSINGTON_AB_1 Routine Compliance
 
Phone Conversation 03/19/2009 Satisfied TISSINGTON_AB_1 Routine Compliance
 
Letter 03/12/2009 Satisfied TISSINGTON_AB_1 Non-Compliance
 
Site Inspection 03/10/2009 Minor Out of Compliance TISSINGTON_AB_1 0/2 Routine Compliance
 
Emergency Preparedness Information 03/10/2009 Satisfied TISSINGTON_AB_1 Routine Compliance
 
Phone Conversation 10/03/2008 Satisfied TISSINGTON_AB_1 Non-Compliance
 
Site Inspection 05/07/2008 Minor Out of Compliance TISSINGTON_AB_1 0/2 Routine Compliance
 
Record Document 04/18/2007 Satisfied TISSINGTON_AB_1 Non-Compliance
 
Site Inspection 03/19/2007 Minor Out of Compliance TISSINGTON_AB_1 0/2 Routine Compliance
 
Letter 03/19/2007 Satisfied TISSINGTON_AB_1 Non-Compliance
 
Emergency Preparedness Information 02/06/2007 Satisfied HALE_JS_1 Routine Compliance
 
Emergency Preparedness Information 09/20/2006 Satisfied THAYER_JD_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
04/25/2024 6062 Minor 2.5 Release detection devices not tested annually. Have a certified technician test the Spill Bucket Gauges for proper operation. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
04/25/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Have the liquid removed and properly disposed of from the Regular, Premium, and Diesel Spill Containments. Email a copy of the work invoice to the inspector for review and pictures of all Spill Buckets. Email: Emily.Elliott@FLHealth.gov
 
04/25/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Have the liquid removed and properly disposed of from Dispenser 3/4 Sump. Email a copy of the work invoice to the inspector for review and pictures of Dispenser 3/4 Sump. Email: Emily.Elliott@FLHealth.gov
 
04/25/2024 6002 Minor 2.1 Operator Training records not available. Have the owner or operator take Class A and Class B Operator Training. Have each employee of the facility take Class C Operator Training. Email to the inspector Class A, Class B and Class C Operator Training Certificates for review. Email: Emily.Elliott@FLHealth.gov.
 
04/25/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Have a certified contractor/technician installed Overfill Prevention Device for the tank. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov.
 
04/25/2024 6006 Minor 2.5 Placard not displayed (or available upon request). Obtain and post/display the facility's current storage tank registration placard in plain view at the facility. Contact the inspector once the placard is posted. Email: Emily.Elliott@FLHealth.gov
 
04/25/2024 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Start conducting and continue conducting monthly visual inspections. Provide the inspector at least three months of monthly visual inspections that do not exceed 35 days. The monthly inspections can’t be prefilled out for the year. Email the inspector the paperwork to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
04/25/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a certified technician test the integrity of the Dispenser Sumps. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
04/25/2024 6043 Minor 4.13 Fillbox covers not marked according to requirements. Have the Regular, Premium, Diesel spill bucket lids repainted according to API standards. Email to the inspector a detailed work invoice indicating that the Regular, Premium, Diesel spill bucket lids has been painted and/or a picture of the painted Regular, Premium, Diesel spill bucket lids. Email: Emily.Elliott@FLHealth.gov
 
04/25/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Have the liquid removed and properly disposed of from the Regular, Premium, and Diesel STP Sumps. Email a copy of the work invoice to the inspector for review and pictures of the Regular, Premium, and Diesel STP Sumps. Email: Emily.Elliott@FLHealth.gov.
 
04/25/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a certified technician test the integrity of the Single Wall Spill Buckets. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
04/25/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a certified technician test the integrity of the STP Sumps . Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
04/25/2024 6011 SNC-B 2.8 No financial responsibility instrument or expired instrument for < 180 days. Provide documentation of Financial Responsibility showing a start date of 02/05/2019. If facility does not have any Financial Responsibility, obtain retro-active coverage. Have the Retro-Active date start 02/05/2019. Submit a copy of the FDEP Financial Mechanisms Part C or Part D Form and a Part P Form to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
04/25/2024 6046 Minor 4.14 Dispensers not installed and maintained according to standards. Have a certified contractor remove the valves beneath dispenser 1/2. Email a copy of the work invoice indicating to the inspector for review to clear the violation. The work invoice must indicate that the valves have been removed. Email: Emily.Elliott@FLHealth.gov
 
06/02/2022 6006 Minor 2.5 Placard not displayed (or available upon request). Post the valid registration placard in the facility that is in plain view. Upon posting the registration placard in the store, send a photograph to Daniel.Gartin@flhealth.gov.
 
06/02/2022 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Monthly visual inspection must be kept by the facility for 3 years. Ensure information listed clearly states when the visual inspection occurred, tank interstitial space was checked for release detection, and the associated tank components of the double-wall USTs were inspected. Submit copies of the three years of monthly visual inspections printout for the facility's UST to Daniel.Gartin@flhealth.gov. If monthly visual inspections were not being kept, submit monthly inspections with electronic release detection results to Daniel.Gartin@flhealth.gov for the months of June, July, and August.
 
06/02/2022 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a certified contractor conduct the integrity testing for the spill buckets and submit the testing results to Daniel.Gartin@flhealth.gov.
 
06/02/2022 6011 SNC-B 2.8 No financial responsibility instrument or expired instrument for < 180 days. Have the facility's associated primary mechanism DEP Form 62-761.900(3) document and the DEP Form 62-761.900(3) Part P Storage Tank Certification of Financial Responsibility form (completed by the facility) completed and submitted to Daniel.Gartin@flhealth.gov.
 
06/02/2022 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Conduct the overfill prevention annual operability testing for the primary overfill prevention device. If any components are damaged, have a certified contractor repair or replace the overfill prevention devices. Once the work has been completed, forward documentation of passing test results to Daniel.Gartin@flhealth.gov.
 
06/02/2022 6069 Minor 4.5 Cathodic protection not operated and maintained to provide continuous protection. System not inspected 6 months after installation or repair. Cathodic protection system not inspected in accordance with NACE International Standards. Impressed current system not inspected every 2 months. Have a certified contractor conduct the associated testing for the operability and evaluation of the sacrificial anode CP system. Submit the associated testing results regarding the sacrificial anode CP system to Daniel.Gartin@flhealth.gov.
 
06/02/2022 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a certified contractor conduct the integrity testing for the STP sumps installed at the facility. Have a certified contractor repair/replace any damaged components and forward the work conducted and passing integrity testing to Daniel.Gartin@flhealth.gov.
 
06/02/2022 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a certified contractor conduct the integrity test for the dispenser sumps. Upon completion, forward documentation of the repairs and passing integrity testing results to Daniel.Gartin@flhealth.gov.
 
06/02/2022 6062 Minor 2.5 Release detection devices not tested annually. Have a certified contractor conduct the annual operability testing for the line leak detector. Submit the testing annual operability documentation to Daniel.Gartin@flhealth.gov.
 
06/02/2022 6002 Minor 2.1 Operator Training records not available. If needed, have a representative or representatives of the facility, take and pass an approved operator training certification course to obtain the Class A/B and Class C operator training certificate. Submit a copy of the Class A/B and Class C operator certification for this facility to Daniel.Gartin@flhealth.gov.
 
06/02/2022 6003 Minor 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Complete a Storage Tank Facility Registration Form to update the facility ownership and submit the completed document to tankregistration@floridadep.gov and Daniel.Gartin@flhealth.gov.
 
11/12/2019 4059 SNC-B 4.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days.) For electronically monitored sumps, visual inspections not conducted every 6 months. This violation may lead to Placard Revocation and Delivery Prohibition. Begin performing and recording monthly visual inspections. Forward copies of the visual inspection records for the next three months to the inspector; November and December of 2019, and January of 2020. Shane Bragg at Shane.Bragg@flhealth.gov, or FAX 850-595-6774.
 
11/12/2019 4067 Minor 4.2 Release detection devices not tested annually. Have a certified technician perform an Annual Operability Test, and forward a copy of the test results to the inspector. Shane Bragg at Shane.Bragg@flhealth.gov or FAX 850-595-6774.
 
11/12/2019 4014 SNC-B 2.9 Failure to maintain and demonstrate financial responsibility. This violation may lead to Placard Revocation and Delivery Prohibition. Provide proof of current financial responsibility to the inspector using the State of Florida Financial Mechanisms for Storage Tanks Form to demonstrate financial responsibility, part "P". Forward a copy of the completed form to the inspector. Shane Bragg at Shane.Bragg@flhealth.gov or FAX 850-595-6774.
 
11/12/2019 4001 Minor 2.2 Operator certification requirements not met. If needed have a representative or representatives of the facility, take and pass an approved operator training certification course to obtain the certificates. Once obtained forward a copy or copies of the operator training certificates to the inspector. Shane.Bragg@flhealth.gov or FAX 85-595-6774.
 
11/12/2019 4076 Minor 4.11 Failure to conduct required periodic containment and interstitial integrity testing. Have the sumps and spill buckets tested for integrity. Once work is completed forward copies of the testing records the inspector. Shane Bragg at Shane.Bragg@flhealth.gov or FAX 850-595-6774.
 
11/12/2019 4066 SNC-B 4.3 Integral piping release detection requirements not met. Have a certified technician perform an Annual Line Leak Detector test, and forward a copy of the test results to the inspector. Shane Bragg at Shane.Bragg@flhealth.gov or FAX 850-595-6774.
 
11/12/2019 4057 Minor 4.31 Overfill protection devices not registered or tested annually. Have the overfill devices tested for operability in accordance with the manufactures guidelines. Once testing is completed forward copies of the test results to the inspector for review. Shane Bragg at Shane.Bragg@flhealth.gov or FAX 850-595-6774.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
07/20/1995   COMPLETED 60 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE
 
11/07/1994   COMPLETED 60
 
12/20/1988   COMPLETED 60 EARLY DETECTION INCENTIVE-ELIGIBLE