DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 02/02/2025        Last Data Refresh: 02/01/2025        Report Generated from DOPPLER
 
District Northwest   Type    Retail Station
 
County Escambia   Status    OPEN
 
ID 8507895   Latitude    30° 25' 40.3824
 
Name LUCKY 7 DISCOUNT #2
4121 MOBILE HWY
Longitude    87° 16' 13.3753
  PENSACOLA, FL 32506 LL Method    DPHO
 
Contact SEAN NGUYEN   LL Status    REVIEWED
 
Phone (850) 332-6026   Status Date    08/12/2013
 
Account Owner Information
 
Name PHAM, THANG THI
572 LANDER ST
CANTONMENT, FL 32533
Effective Date    10/07/2010
 
Contact CHAU NGUYEN
 
Phone (850) 470-0060
 
Email CHAUNGUYEN@BELLSOUTH.NET
  Placard # / Date    671271 - 10/21/2023
Property Owner Information
 
Name PHAM, THANG THI
572 LANDER ST
CANTONMENT, FL 32533
Effective Date    10/07/2010
 
Contact CHAU NGUYEN
 
Phone (850) 470-0060
 
Email CHAUNGUYEN@BELLSOUTH.NET
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
6 20000 Unleaded Gas (B) 06/01/2010 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(L) Compartmented
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
(R) Double wall - tank jacket
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
1 8000 Leaded Gas (A) 10/01/1969 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
  (C) Fiberglass (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
1R1 10000 Unleaded Gas (B) 04/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
2 6000 Unleaded Gas (B) 10/01/1969 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
  (C) Fiberglass (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
2R1 10000 Unleaded Gas (B) 04/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
3 8000 Unleaded Gas (B) 10/01/1969 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(B) Internal lining
(C) Steel
  (C) Fiberglass (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
3R1 10000 Unleaded Gas (B) 04/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
4 500 Waste Oil (L) 04/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (B) Steel/galvanized metal
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(8) Manually sampled wells
(H) Mechanical line leak detector
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
5 560 Kerosene (K) 07/01/1990 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(I) Not required
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
EXEMPT-NOT REQUIRED  
EXEMPT-NOT REQUIRED  
INSURANCE   08/29/2022 08/29/2023 ACE AMERICAN INSURANCE COMPANY
INSURANCE   06/08/2019 06/08/2020 CRUM & FORSTER INDEMNITY
INSURANCE   06/08/2017 06/08/2019 CRUM & FORSTER INDEMNITY
INSURANCE   06/08/2015 06/08/2016 CRUM & FORSTER INDEMNITY
INSURANCE   05/08/2015 05/08/2017 ESSEX
INSURANCE   03/26/2013 03/26/2015 AMERICAN SAFETY
INSURANCE   09/23/2010 09/23/2011 ZURICH-AMERICAN
INSURANCE   04/20/2008 04/20/2009 ILLINOIS UNION
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 11/17/2005 11/28/2005 IN-COMPLIANCE ARTHUR B. TISSINGTON 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes NO VIOLATIONS NOTED AT TIME.
 
TCI 12/15/2004 12/16/2004 IN-COMPLIANCE ARTHUR B. TISSINGTON 0/3 COMPLIANCE ASSURANCE
 
TCI 12/17/2003 12/29/2003 IN-COMPLIANCE ARTHUR B. TISSINGTON 0/3 COMPLIANCE ASSURANCE
 
RRBD 11/18/2002 12/02/2002 COMPLIANCE ASSURANCE
 
TCI 11/06/2002 11/18/2002 SIGNIFICANT OUT-OF-COMPLIANCE REGINALD W. BRADLEY 0/3 COMPLIANCE ASSURANCE
 
TCI 12/19/2001 01/14/2002 IN-COMPLIANCE REGINALD BRADLEY 0/3 COMPLIANCE ASSURANCE
 
TCR 12/11/2000 12/27/2000 IN-COMPLIANCE HUTCHERSON_VP 0/3 COMPLIANCE ASSURANCE
 
TCI 10/24/2000 11/02/2000 MINOR OUT-OF-COMPLIANCE HUTCHERSON_VP 0/3 COMPLIANCE ASSURANCE
 
RRBD 12/28/1999 01/04/2000 HUTCHERSON_VP 0/0 COMPLIANCE ASSURANCE
 
TIN 12/21/1999 01/03/2000 IN-COMPLIANCE HOLLINGSHEAD_JB 0/3 COMPLIANCE ASSURANCE
 
TCI 09/30/1999 10/07/1999 MINOR OUT-OF-COMPLIANCE HUTCHERSON_VP 0/3 COMPLIANCE ASSURANCE
 
RRBD 03/22/1999 04/02/1999 HOLLINGSHEAD_J 0/0 COMPLIANCE ASSURANCE
 
TCI 02/22/1999 03/01/1999 MINOR OUT-OF-COMPLIANCE JOHN B HOLLINGSHEAD 0/3 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 10/23/2024 Satisfied PROFFITT_B Routine Compliance
 
Enforcement Referral 03/20/2024 Accepted ELLIOTT_EV_1 Enforcement
 
Letter 12/14/2023 Satisfied BRISTOL_S Component Closure
 
TCAR 12/14/2023 Satisfied BRISTOL_S Component Closure
 
Letter 12/13/2023 Satisfied ELLIOTT_EV_1 Compliance Assistance
 
Site Inspection 12/13/2023 Major Out of Compliance ELLIOTT_EV_1 0/1 Routine Compliance
 
Electronic Communication 12/11/2023 Satisfied ELLIOTT_EV_1 Routine Compliance
 
Site Inspection 01/27/2023 Major Out of Compliance ELLIOTT_EV_1 0/1 Component Installation
 
Letter 01/27/2023 Satisfied WILSON_ML_1 Compliance Assistance
 
Enforcement Tracking 12/09/2022 Closed Without Enforcement MATHERLY_H Enforcement
 
Phone Conversation 10/26/2022 Satisfied MATHERLY_H Enforcement
 
Letter 10/13/2022 Satisfied MATHERLY_H Enforcement
 
Enforcement Referral 08/24/2022 Accepted GARTIN_D Enforcement
 
Electronic Communication 08/18/2022 Satisfied GARTIN_D Compliance Assistance
 
Letter 08/03/2022 Satisfied MATHERLY_H Enforcement
 
Enforcement Referral 07/22/2022 Accepted GARTIN_D Enforcement
 
Letter 06/10/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 06/02/2022 Major Out of Compliance GARTIN_D 0/1 Routine Compliance
 
Electronic Communication 06/02/2022 Satisfied GARTIN_D Routine Compliance
 
Issue Document 05/06/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 05/06/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 05/03/2022 Major Out of Compliance GARTIN_D 0/1 Component Installation
 
Electronic Communication 05/03/2022 Satisfied GARTIN_D Component Installation
 
Electronic Communication 05/03/2022 Satisfied GARTIN_D Component Installation
 
Enforcement Tracking 07/09/2020 Closed Without Enforcement BRISTOL_S Enforcement
 
Electronic Communication 01/17/2020 Satisfied BRAGG_SD_2 Compliance Assistance
 
Phone Conversation 12/27/2019 Satisfied BRAGG_SD_2 Compliance Assistance
 
Phone Conversation 12/27/2019 Satisfied BRAGG_SD_2 Compliance Assistance
 
Electronic Communication 12/06/2019 Satisfied BRAGG_SD_2 Compliance Assistance
 
Electronic Communication 12/06/2019 Satisfied BRAGG_SD_2 Compliance Assistance
 
Phone Conversation 12/06/2019 Satisfied BRAGG_SD_2 Compliance Assistance
 
Enforcement Referral 11/21/2019 Accepted BRAGG_SD_2 Enforcement
 
Electronic Communication 08/26/2019 Satisfied BRAGG_SD_2 Compliance Assistance
 
Letter 08/22/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Issue Document 08/22/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 08/21/2019 Minor Out of Compliance BRAGG_SD_2 0/1 Routine Compliance
 
Phone Conversation 08/07/2019 Satisfied BRAGG_SD_2 Routine Compliance
 
Record Document 05/02/2017 Satisfied BRAGG_SD_2 Non-Compliance
 
Site Inspection 03/17/2017 Minor Out of Compliance BRAGG_SD_2 0/1 Non-Compliance
 
Record Document 02/27/2017 Satisfied BRAGG_SD_2 Non-Compliance
 
Letter 02/27/2017 Satisfied WILSON_ML_1 Non-Compliance
 
Site Inspection 02/24/2017 Major Out of Compliance BRAGG_SD_2 0/1 Routine Compliance
 
Record Document 06/16/2015 Satisfied PAYNE_CL_1 Non-Compliance
 
Letter 05/18/2015 Satisfied WILSON_ML_1 Non-Compliance
 
Site Inspection 05/15/2015 Major Out of Compliance PAYNE_CL_1 0/1 Routine Compliance
 
Emergency Preparedness Information 05/04/2015 Satisfied PAYNE_CL_1 Routine Compliance
 
Site Inspection 07/18/2014 In Compliance PAYNE_CL_1 0/1 Non-Compliance
 
Record Document 07/14/2014 Satisfied PAYNE_CL_1 Non-Compliance
 
Record Document 07/14/2014 Satisfied PAYNE_CL_1 Non-Compliance
 
Letter 06/12/2014 Satisfied DAURIA_KL_1 Non-Compliance
 
Emergency Preparedness Information 06/11/2014 Satisfied PAYNE_CL_1 Routine Compliance
 
Site Inspection 06/11/2014 Minor Out of Compliance PAYNE_CL_1 0/1 Routine Compliance
 
Site Inspection 08/18/2011 In Compliance TISSINGTON_AB_1 0/1 Routine Compliance
 
Emergency Preparedness Information 08/18/2011 Satisfied TISSINGTON_AB_1 Routine Compliance
 
Site Inspection 03/08/2011 In Compliance PORTER_AJ_1 0/1 Routine Compliance
 
Site Inspection 09/02/2010 In Compliance PORTER_AJ_1 0/3 Installation
 
Site Inspection 06/10/2010 In Compliance PORTER_AJ_1 0/3 Closure
 
Meeting 04/08/2010 Satisfied PORTER_AJ_1 Routine Compliance
 
Letter 03/19/2010 Satisfied PIERCE_LL_1 Non-Compliance
 
Site Inspection 03/17/2010 Minor Out of Compliance PORTER_AJ_1 0/3 Routine Compliance
 
Phone Conversation 06/04/2009 Satisfied TISSINGTON_AB_1 Routine Compliance
 
Phone Conversation 05/12/2009 Satisfied STEVENSON_JS Non-Compliance
 
Site Inspection 05/06/2009 Major Out of Compliance STEVENSON_JS 0/3 Routine Compliance
 
Record Document 05/07/2008 Satisfied STEVENSON_JS Non-Compliance
 
Record Document 04/24/2008 Satisfied STEVENSON_JS Routine Compliance
 
Site Inspection 04/21/2008 In Compliance STEVENSON_JS 0/3 Routine Compliance
 
Site Inspection 07/18/2007 In Compliance STEVENSON_JS 0/3 Non-Compliance
 
Letter 02/20/2007 Satisfied STEVENSON_JS Non-Compliance
 
Emergency Preparedness Information 02/06/2007 Satisfied STEVENSON_JS Routine Compliance
 
Record Document 12/21/2006 Satisfied STEVENSON_JS Non-Compliance
 
Site Inspection 11/14/2006 Major Out of Compliance STEVENSON_JS 0/3 Routine Compliance
 
Emergency Preparedness Information 09/20/2006 Satisfied THAYER_JD_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
12/13/2023 6062 Minor 2.5 Release detection devices not tested annually. Have a certified technician test the ATG System for proper operation. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
12/13/2023 6046 Minor 4.14 Dispensers not installed and maintained according to standards. Have a certified contractor remove the valves beneath dispenser 5/6. Email a copy of the work invoice indicating to the inspector for review to clear the violation. The work invoice must indicate that the valves have been removed. Email: Emily.Elliott@FLHealth.gov
 
12/13/2023 6062 Minor 2.5 Release detection devices not tested annually. Have a certified technician test the Spill Bucket Gauges for proper operation. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
12/13/2023 6066 Minor 4.4 Not repaired per applicable standards. Have a certified contractor/technician repair the Premium Electrical Line in the STP Sump. Email a detailed work invoice to the inspector and a picture of the sump after work has been completed. Email: Emily.Elliott@FLHelath.gov
 
12/13/2023 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Have the liquid removed and properly disposed of from the spill containments. Email a copy of the work invoice to the inspector for review and pictures. Email: Emily.Elliott@FLHealth.gov
 
12/13/2023 6011 SNC-B 2.8 No financial responsibility instrument or expired instrument for < 180 days. Provide documentation of Financial Responsibility showing a start date of 08/29/2023. If facility does not have any Financial Responsibility, obtain retro-active coverage. Have the Retro-Active date start 08/29/2023. Submit a copy of the FDEP Financial Mechanisms Part C or Part D Form and a Part P Form to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
12/13/2023 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Start conducting and continue conducting monthly visual inspections. Provide the inspector at least three months of monthly visual inspections that do not exceed 35 days. The monthly inspections can’t be prefilled out for the year. Email the inspector the paperwork to clear the violation. Email: Emily.Elliott@FLHealth.gov
 
12/13/2023 6002 Minor 2.1 Operator Training records not available. Have the owner or operator take Class A and Class B Operator Training. Have each employee of the facility take Class C Operator Training. Email to the inspector Class A, Class B and Class C Operator Training Certificates for review. Email: Emily.Elliott@FLHealth.gov.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
01/30/1988   COMPLETED 57 EARLY DETECTION INCENTIVE-ELIGIBLE