District | Northwest | Type | Retail Station | ||||||||
County | Escambia | Status | OPEN | ||||||||
ID | 8508005 | Latitude | 30° 27' 13.5684 | ||||||||
Name |
LUCKY 7 DISCOUNT 713 MASSACHUSETTS AVE |
Longitude | 87° 15' 22.5072 | ||||||||
PENSACOLA, FL 32505-3924 | LL Method | DPHO | |||||||||
Contact | CHAU NGUYEN | LL Status | REVIEWED | ||||||||
Phone | (850) 470-0060 | Status Date | 03/25/2015 | ||||||||
Account Owner Information | |||||||||||
Name | LUCKY 7 DISCOUNT 713 MASSACHUSETTS AVE PENSACOLA, FL 32505-3924 |
Effective Date | 06/07/2005 | ||||||||
Contact | CHAU NGUYEN | ||||||||||
Phone | (850) 470-0060 | ||||||||||
CHAUNGUYEN@BELLSOUTH.NET | |||||||||||
Placard # / Date | 705212 - 02/20/2025 | ||||||||||
Property Owner Information | |||||||||||
Name | TOMMY NQUYEN 5663 CULPEPPER CIR PACE, FL 32571 |
Effective Date | 06/23/2003 | ||||||||
Contact | TOMMY NQUYEN | ||||||||||
Phone | (850) 479-0909 | ||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 10000 | Unleaded Gas (B) | 04/01/1993 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (G) Sacrificial anode CP (I) Double wall (L) Compartmented (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (I) Suction piping system (K) Dispenser liners (M) Double wall - pipe jacket |
(4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (K) Monitor dbl wall pipe space (V) Suction pump check valve |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 10000 | Leaded Gas (A) | 07/01/1976 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (C) Fiberglass | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 10000 | Gasohol (C) | 07/01/1976 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (C) Fiberglass | (Y) Unknown | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 06/08/2019 | 06/08/2021 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 06/08/2015 | 06/08/2016 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 03/26/2013 | 03/26/2015 | AMERICAN SAFETY | ||||||||
INSURANCE | 06/05/2010 | 06/05/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 06/05/2009 | 06/05/2010 | ZURICH-AMERICAN | ||||||||
INSURANCE | 06/03/2009 | 06/03/2010 | ACE | ||||||||
INSURANCE | 03/15/1994 | 03/15/1995 | FPLIPA | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 01/19/2006 | 01/24/2006 | IN-COMPLIANCE | ARTHUR B TISSINGTON | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO VIOLATIONS FOUND THIS INSPECTION | |||||||||||
TCI | 05/11/2005 | 06/02/2005 | MINOR OUT-OF-COMPLIANCE | ARTHUR B. TISSINGTON | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes THIS FACILITY IS IN ENFORCEMENT | |||||||||||
RRBD | 05/25/2004 | 05/26/2004 | COMPLIANCE ASSURANCE | ||||||||
TCR | 05/24/2004 | 05/26/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | JOHN S. STEVENSON | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 04/05/2004 | 04/06/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | JOHN S. STEVENSON | 0/1 | COMPLIANCE ASSURANCE | |||||
TCR | 06/04/2003 | 06/06/2003 | IN-COMPLIANCE | J. SCOTT HALE | 0/1 | COMPLIANCE ASSURANCE | |||||
RRBD | 12/27/2002 | 01/02/2003 | COMPLIANCE ASSURANCE | ||||||||
TCR | 12/23/2002 | 12/30/2002 | MINOR OUT-OF-COMPLIANCE | REGINALD W. BRADLEY | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 12/16/2002 | 12/23/2002 | MINOR OUT-OF-COMPLIANCE | REGINALD W. BRADLEY | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 02/22/2002 | 12/30/2002 | MINOR OUT-OF-COMPLIANCE | REGINALD W. BRADLEY | 0/1 | COMPLIANCE ASSURANCE | |||||
TCR | 01/31/2001 | 02/13/2001 | IN-COMPLIANCE | STEVENSON_JS | 0/1 | COMPLIANCE ASSURANCE | |||||
TCI | 08/07/2000 | 08/22/2000 | MINOR OUT-OF-COMPLIANCE | STEVENSON_JS | 0/1 | COMPLIANCE ASSURANCE | |||||
RRBD | 03/29/2000 | 04/12/2000 | STEVENSON_JS | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 03/20/2000 | 04/12/2000 | STEVENSON_JS | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 02/10/2000 | 03/09/2000 | SIGNIFICANT OUT-OF-COMPLIANCE | STEVENSON_JS | 0/0 | COMPLIANCE ASSURANCE | |||||
TCI | 06/16/1999 | 06/28/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | THAYER_J | 0/1 | COMPLIANCE ASSURANCE | |||||
UTCI | 02/27/1998 | 03/05/1998 | MINOR OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 02/19/2025 | Satisfied | ELLIOTT_EV_1 | Compliance Assistance | |||||||
Document Management | 02/18/2025 | Satisfied | ELLIOTT_EV_1 | Incident | |||||||
Electronic Communication | 02/17/2025 | Satisfied | ELLIOTT_EV_1 | Routine Compliance | |||||||
Site Inspection | 02/17/2025 | Major Out of Compliance | ELLIOTT_EV_1 | 0/1 | Routine Compliance | ||||||
Enforcement Referral | 05/30/2023 | Accepted | ELLIOTT_EV_1 | Enforcement | |||||||
Letter | 03/08/2023 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 03/07/2023 | Major Out of Compliance | ELLIOTT_EV_1 | 0/1 | Routine Compliance | ||||||
Phone Conversation | 10/10/2022 | Satisfied | MATHERLY_H | Enforcement | |||||||
Phone Conversation | 08/01/2022 | Satisfied | MATHERLY_H | Enforcement | |||||||
Phone Conversation | 06/14/2022 | Satisfied | MATHERLY_H | Enforcement | |||||||
Phone Conversation | 05/18/2022 | Satisfied | MATHERLY_H | Enforcement | |||||||
Phone Conversation | 04/27/2022 | Satisfied | MATHERLY_H | Enforcement | |||||||
Phone Conversation | 02/16/2022 | Satisfied | MATHERLY_H | Enforcement | |||||||
Enforcement Referral | 08/26/2021 | Accepted | BAVUSO_CX_1 | Enforcement | |||||||
Letter | 08/26/2021 | Satisfied | MATHERLY_H | Enforcement | |||||||
Electronic Communication | 07/28/2021 | Satisfied | PANGAHAS_RL_1 | Compliance Assistance | |||||||
Issue Document | 05/21/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Letter | 05/21/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Phone Conversation | 05/20/2021 | Satisfied | PANGAHAS_RL_1 | Routine Compliance | |||||||
Electronic Communication | 05/20/2021 | Satisfied | PANGAHAS_RL_1 | Routine Compliance | |||||||
Electronic Communication | 05/20/2021 | Satisfied | PANGAHAS_RL_1 | Routine Compliance | |||||||
Site Inspection | 05/20/2021 | Minor Out of Compliance | PANGAHAS_RL_1 | 0/1 | Routine Compliance | ||||||
Issue Document | 09/28/2018 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Letter | 09/28/2018 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Electronic Communication | 09/28/2018 | Satisfied | BRAGG_SD_2 | Compliance Assistance | |||||||
Electronic Communication | 09/26/2018 | Satisfied | BRAGG_SD_2 | Compliance Assistance | |||||||
Electronic Communication | 09/25/2018 | Satisfied | BRAGG_SD_2 | Compliance Assistance | |||||||
Issue Document | 08/22/2018 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Letter | 08/22/2018 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 08/22/2018 | Major Out of Compliance | BRAGG_SD_2 | 0/1 | Routine Compliance | ||||||
Phone Conversation | 07/24/2018 | Satisfied | BRAGG_SD_2 | Routine Compliance | |||||||
Site Inspection | 05/05/2016 | In Compliance | PAYNE_CL_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 05/29/2014 | In Compliance | PAYNE_CL_1 | 0/1 | Routine Compliance | ||||||
Emergency Preparedness Information | 05/27/2014 | Satisfied | PAYNE_CL_1 | Routine Compliance | |||||||
Site Inspection | 04/08/2013 | In Compliance | PAYNE_CL_1 | 0/1 | Routine Compliance | ||||||
Emergency Preparedness Information | 04/08/2013 | Satisfied | PAYNE_CL_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 03/15/2011 | Satisfied | PORTER_AJ_1 | Routine Compliance | |||||||
Site Inspection | 03/15/2011 | In Compliance | PORTER_AJ_1 | 0/1 | Routine Compliance | ||||||
Meeting | 04/13/2010 | Satisfied | PORTER_AJ_1 | Routine Compliance | |||||||
Letter | 03/10/2010 | Satisfied | PIERCE_LL_1 | Non-Compliance | |||||||
Site Inspection | 03/08/2010 | Minor Out of Compliance | PORTER_AJ_1 | 0/1 | Routine Compliance | ||||||
Enforcement Tracking | 08/14/2009 | Closed Without Enforcement | GILLMAN_M | Enforcement | |||||||
Site Inspection | 06/05/2009 | In Compliance | STEVENSON_JS | 0/1 | Routine Compliance | ||||||
Record Document | 06/23/2008 | Satisfied | STEVENSON_JS | Non-Compliance | |||||||
Letter | 05/23/2008 | Satisfied | STEVENSON_JS | Non-Compliance | |||||||
Site Inspection | 05/20/2008 | Minor Out of Compliance | STEVENSON_JS | 0/1 | Routine Compliance | ||||||
Enforcement Referral | 09/14/2007 | Accepted | GILLMAN_M | Enforcement | |||||||
Letter | 09/14/2007 | Satisfied | TISSINGTON_AB_1 | Non-Compliance | |||||||
Site Inspection | 09/07/2007 | Major Out of Compliance | TISSINGTON_AB_1 | 0/1 | Installation | ||||||
Letter | 03/01/2007 | Satisfied | STEVENSON_JS | Non-Compliance | |||||||
Emergency Preparedness Information | 02/06/2007 | Satisfied | THAYER_JD_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/25/2006 | Satisfied | STEVENSON_JS | Routine Compliance | |||||||
Site Inspection | 08/30/2006 | Major Out of Compliance | STEVENSON_JS | 0/1 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
02/17/2025 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Have a technician test the integrity of the Single Wall Spill Buckets. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov. | |||||||
02/17/2025 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Have a certified technician test the integrity of the Premium Dispenser Sump. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov | |||||||
02/17/2025 | 6043 | Minor | 4.13 Fillbox covers not marked according to requirements. | Have the Regular and Premium spill bucket lids repainted according to API standards. Email to the inspector a detailed work invoice indicating that the Regular and Premium spill bucket lids have been painted and/or a picture of the painted Premium and Regular spill bucket lids. Email: Emily.Elliott@FLHealth.gov | |||||||
02/17/2025 | 6011 | SNC-B | 2.8 No financial responsibility instrument or expired instrument for < 180 days. | Provide documentation of Financial Responsibility showing a start date of 06/08/2021. If facility does not have any Financial Responsibility, obtain retro-active coverage. Have the Retro-Active date start 06/08/2021. Submit a copy of the FDEP Financial Mechanisms Part C or Part D Form and a Part P Form to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov | |||||||
02/17/2025 | 6069 | Minor | 4.5 Cathodic protection not operated and maintained to provide continuous protection. System not inspected 6 months after installation or repair. Cathodic protection system not inspected in accordance with NACE International Standards. Impressed current system not inspected every 2 months. | Have a technician test the Cathodic Protection. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov | |||||||
02/17/2025 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Investigate the reason and source for liquid to be present in the interstitial space. Determine if the liquid contains any petroleum-based product. Contact Emily.Elliott@FLHealth.gov with results of the type of liquids present in the interstitial space and prior to conducting any repairs or replacements. | |||||||
02/17/2025 | 6002 | Minor | 2.1 Operator Training records not available. | Have the owner or operator take Class A and Class B Operator Training. Have each employee of the facility take Class C Operator Training. Email to the inspector Class A, Class B and Class C Operator Training Certificates for review. Email: Emily.Elliott@FLHealth.gov. | |||||||
02/17/2025 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Have the hose on East Dispenser replaced. Once work is completed, email a copy of the work invoice to the inspector for review to clear the violation. The work invoice must indicate that the hose has been replaced. Email: Emily.Elliott@FLHealth.gov | |||||||
02/17/2025 | 6074 | Minor | 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. | Start conducting and continue conducting monthly visual inspections. Provide the inspector at least three months of monthly visual inspections that do not exceed 35 days. The monthly inspections can’t be prefilled out for the year. Email the inspector the paperwork to clear the violation. Email: Emily.Elliott@FLHealth.gov | |||||||
03/02/2023 | 6069 | Minor | 4.5 Cathodic protection not operated and maintained to provide continuous protection. System not inspected 6 months after installation or repair. Cathodic protection system not inspected in accordance with NACE International Standards. Impressed current system not inspected every 2 months. | Have a technician test the Cathodic Protection. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov | |||||||
03/02/2023 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Have a technician test the integrity of the Single Wall Spill Buckets. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov | |||||||
03/02/2023 | 6011 | SNC-B | 2.8 No financial responsibility instrument or expired instrument for < 180 days. | Provide documentation of Financial Responsibility showing a start date of 06/08/2021. If facility does not have any Financial Responsibility, obtain retro-active coverage. Have the Retro-Active date start 06/08/2021. Submit a copy of the FDEP Financial Mechanisms Part C or Part D Form and a Part P Form to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov | |||||||
03/02/2023 | 6074 | Minor | 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. | Start conducting and continue conducting monthly visual inspections. Provide the inspector at least three months of monthly visual inspections that do not exceed 35 days. The monthly inspections can’t be prefilled out for the year. Email the inspector the paperwork to clear the violation. Email: Emily.Elliott@FLHealth.gov | |||||||
03/02/2023 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Have a technician test the Line Leak Detectors for proper operation. Once completed, send a copy of the results, that includes all test data, to the inspector for review to clear the violation. Email: Emily.Elliott@FLHealth.gov | |||||||
03/02/2023 | 6043 | Minor | 4.13 Fillbox covers not marked according to requirements. | Have the Regular and Premium spill bucket lids repainted according to API standards. Email to the inspector a detailed work invoice indicating that the Regular and Premium spill bucket lids have been painted and/or a picture of the painted Premium and Regular spill bucket lids. Email: Emily.Elliott@FLHealth.gov | |||||||
03/02/2023 | 6006 | Minor | 2.5 Placard not displayed (or available upon request). | Obtain and post/display the facility's current storage tank registration placard in plain view at the facility. Contact the inspector once the placard is posted. Email: Emily.Elliott@FLHealth.gov | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
03/30/1991 | COMPLETED | 60 | |||||||||
12/28/1988 | COMPLETED | 60 | EARLY DETECTION INCENTIVE-ELIGIBLE | ||||||||