Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 01/22/2025 Last Data Refresh: 01/21/2025 Report Generated from DOPPLER | |||||||||||
District | Central | Type | Retail Station | ||||||||
County | Lake | Status | OPEN | ||||||||
ID | 8510008 | Latitude | 28° 50' 30.1135 | ||||||||
Name |
BAY STREET FOOD MART 1212 S BAY ST |
Longitude | 81° 41' 8.9884 | ||||||||
EUSTIS, FL 32726-5549 | LL Method | DPHO | |||||||||
Contact | KUNJAL PATEL | LL Status | REVIEWED | ||||||||
Phone | (347) 526-8775 | Status Date | 10/01/2003 | ||||||||
Account Owner Information | |||||||||||
Name | SHREE KASHTABHANJANDEV INC 1212 S BAY ST EUSTIS, FL 32726 |
Effective Date | 08/16/2020 | ||||||||
Contact | GOMTIBEN PATEL | ||||||||||
Phone | (646) 243-1768 | ||||||||||
DJ_VENAD@YAHOO.COM | |||||||||||
Placard # / Date | 683418 - 06/05/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | CHRISTOPHER VRNTURES INC 1212 S BAY ST EUSTIS, FL 32726-5549 |
Effective Date | 04/21/2008 | ||||||||
Contact | FARES F ANIS | ||||||||||
Phone | (352) 483-3778 | ||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 12000 | Unleaded Gas (B) | 02/01/2008 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 12000 | Unleaded Gas (B) | 02/01/2008 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 8000 | Unleaded Gas (B) | 07/01/1973 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 8000 | Unleaded Gas (B) | 07/01/1973 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 2000 | Vehicular Diesel (D) | 05/01/1990 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 12/10/2023 | 12/10/2024 | LLOYDS OF LONDON | ||||||||
INSURANCE | 12/10/2021 | 12/10/2022 | TOKIO MARINE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 12/10/2018 | 12/10/2019 | TOKIO MARINE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 12/10/2016 | 12/10/2017 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 12/02/2014 | 12/02/2015 | ACE | ||||||||
INSURANCE | 12/02/2013 | 12/02/2014 | ACE | ||||||||
INSURANCE | 11/26/2013 | 11/26/2014 | ACE | ||||||||
INSURANCE | 12/05/2011 | 12/05/2012 | ZURICH-AMERICAN | ||||||||
INSURANCE | 12/05/2010 | 12/05/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 12/05/2009 | 12/05/2010 | ZURICH-AMERICAN | ||||||||
INSURANCE | 12/05/2008 | 12/05/2009 | ZURICH-AMERICAN | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCR | 03/14/2006 | 03/14/2006 | IN-COMPLIANCE | COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes SPILL BUCKETS CLEANED OUT. | |||||||||||
TCI | 01/26/2006 | 01/30/2006 | MINOR OUT-OF-COMPLIANCE | COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes RECORDS OK, SIRS, MONTHLY VISUALS. NEEDS TO CLEAN OUT SPILL BUCKETS. LOOKING AT UPGRADING. | |||||||||||
TCI | 01/25/2005 | 01/28/2005 | IN-COMPLIANCE | COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes MLLD TEST DUE 2/11/05 | |||||||||||
LTR | 02/20/2004 | 02/20/2004 | BOWERS | 0/3 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED TEST RESULTS. | |||||||||||
TCI | 01/23/2004 | 02/06/2004 | MINOR OUT-OF-COMPLIANCE | BOWERS/COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes MLLD-2/11/04, 3YRTTT W/SIR'S-2/11/04. | |||||||||||
TCR | 02/14/2003 | 02/21/2003 | IN-COMPLIANCE | BOWERS/COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PCW LIQUID REMOVED. | |||||||||||
TCI | 01/14/2003 | 01/17/2003 | MINOR OUT-OF-COMPLIANCE | BOWERS | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes ANNUAL COMPLIANCE. MLLD 2/25/03, 3YRTTT W/SIR 6/20/00 | |||||||||||
TCR | 03/01/2002 | 03/26/2002 | IN-COMPLIANCE | BOWERS/COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes REINSPECTION. | |||||||||||
TCI | 01/28/2002 | 02/04/2002 | MINOR OUT-OF-COMPLIANCE | BOWERS | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes ANNUAL COMPLIANCE. 3YRTTT W/SIR 6/20/00, MLLD DONE 2/6/02,10 YR. INTERNAL INSPECTION DONE 6/6/00. | |||||||||||
SCOI | 11/08/2000 | 11/15/2000 | GEORGIA.TRIANTAFYLLOU | 0/3 | COMPLIANCE ASSURANCE | ||||||
RRBD | 08/09/2000 | 08/09/2000 | GEORGIA.TRIANTAFYLLOU | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED LEAK DETECTOR TEST AND 10-YEAR INTERNAL LINING TEST. | |||||||||||
CCD | 08/09/2000 | 08/09/2000 | GEROGIA.TRIANTAFYLLOU | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 08/03/2000 | 08/04/2000 | MINOR OUT-OF-COMPLIANCE | BOWERS/COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes ANNUAL COMPLIANCE | |||||||||||
CASV | 06/06/2000 | 06/07/2000 | GEORGIA.TRIANTAFYLLOU | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes GT WITNESSED VIDEO TESTING/CHECK OF THE INTERNAL LINING. TIGHTNESS TESTING TO BE DONE 6/8/00 | |||||||||||
TCI | 04/28/2000 | 05/01/2000 | SIGNIFICANT OUT-OF-COMPLIANCE | BOWERS/COX | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes ANNUAL COMPLIANCE | |||||||||||
CRO | 04/25/2000 | 04/26/2000 | TRIANTAFYL_G | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes CR SENT TO OGC | |||||||||||
CRO | 04/14/2000 | 04/18/2000 | TRIANTAFYL_G | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes CASE REPORT DRAFTED FOR REVIEW | |||||||||||
CALL | 04/04/2000 | 04/05/2000 | TRIANTAFYL_G | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes TALKED TO MR MANSOUR, WHO PROMISED COPY OF SIGNED CONTRACT TO BE FAXED TO DEP FOR UPGRADE, WORK TO BEGIN "PROBABLY NEXT WEEK." IF NOT RECEIVED BY 4/7, CASE REPORT. | |||||||||||
CALL | 03/17/2000 | 03/17/2000 | TRIANTAFYL_G | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes CALLED AND LEFT MSG FOR GEORGE MANSOUR RE: SIGNED CONTRACT HE WAS SUPPOSED TO FAX GT FOR PROPER UPGRADE. ALSO LEFT MESSAGE ON 3/9, 10, 15, 16. IF NO RESPONSE BY 3.21, CASE REPORT | |||||||||||
TCR | 03/01/2000 | 03/10/2000 | SIGNIFICANT OUT-OF-COMPLIANCE | TRIANTAFYLLOU, GEORGIA | 0/0 | COMPLIANCE ASSURANCE | |||||
Completion Notes TO CHECK ON STATUS OF ENFORCEMENT ISSUES | |||||||||||
UTCI | 12/04/1998 | 12/23/1998 | SIGNIFICANT OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Referral | 08/29/2024 | Accepted | RIVERA_JX_2 | Enforcement | |||||||
Electronic Communication | 08/19/2024 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Phone Conversation | 08/19/2024 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Letter | 07/19/2024 | Satisfied | GREGORY_JW_1 | Compliance Assistance | |||||||
Site Inspection | 03/05/2024 | Minor Out of Compliance | COX_CD_1 | 0/2 | Routine Compliance | ||||||
Letter | 03/05/2024 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Phone Conversation | 02/23/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 02/19/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Phone Conversation | 02/19/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 02/19/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Phone Conversation | 02/06/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Meeting | 02/06/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Phone Conversation | 02/05/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Phone Conversation | 02/05/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 01/29/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Letter | 12/07/2022 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 12/07/2022 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 11/23/2022 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 07/21/2022 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 01/21/2022 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Site Inspection | 01/13/2022 | Minor Out of Compliance | COX_CD_1 | 0/2 | Routine Compliance | ||||||
Letter | 01/13/2022 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Phone Conversation | 01/03/2022 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Phone Conversation | 12/30/2021 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Phone Conversation | 12/30/2021 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 03/27/2020 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Letter | 03/27/2020 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 03/16/2020 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 03/02/2020 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Document Management | 03/02/2020 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 02/25/2020 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 02/25/2020 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Phone Conversation | 02/14/2020 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 02/14/2020 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 11/25/2019 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 10/08/2019 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Electronic Communication | 10/08/2019 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Site Inspection | 10/04/2019 | Minor Out of Compliance | COX_CD_1 | 0/2 | Routine Compliance | ||||||
Letter | 10/04/2019 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Phone Conversation | 09/12/2019 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 09/11/2019 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 06/01/2018 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Site Inspection | 12/01/2017 | In Compliance | COX_CD_1 | 0/2 | Compliance Assistance | ||||||
Electronic Communication | 12/01/2017 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Letter | 12/01/2017 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Letter | 11/30/2017 | Satisfied | RAUENZAHN_RA_1 | Compliance Assistance | |||||||
Electronic Communication | 10/02/2017 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Letter | 09/07/2017 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Phone Conversation | 09/01/2017 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Site Inspection | 08/30/2017 | Minor Out of Compliance | COX_CD_1 | 0/2 | Routine Compliance | ||||||
Phone Conversation | 08/25/2017 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Document Management | 10/07/2015 | Complete | RAUENZAHN_RA_1 | Complaint | |||||||
Letter | 10/01/2015 | Satisfied | COX_CD_1 | Non-Compliance | |||||||
Complaint | 09/29/2015 | Satisfied | COX_CD_1 | Complaint | |||||||
Site Inspection | 09/29/2015 | In Compliance | COX_CD_1 | 0/2 | Complaint | ||||||
Site Inspection | 09/22/2015 | Minor Out of Compliance | COX_CD_1 | 0/2 | Routine Compliance | ||||||
Phone Conversation | 09/15/2015 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Meeting | 07/09/2014 | Satisfied | COX_CD_1 | Non-Compliance | |||||||
Letter | 07/01/2014 | Satisfied | COX_CD_1 | Non-Compliance | |||||||
Site Inspection | 06/17/2014 | Minor Out of Compliance | COX_CD_1 | 0/2 | Non-Compliance | ||||||
Letter | 03/29/2014 | Satisfied | COX_CD_1 | Non-Compliance | |||||||
Site Inspection | 03/11/2014 | Major Out of Compliance | COX_CD_1 | 0/2 | Non-Compliance | ||||||
Electronic Communication | 11/27/2013 | Satisfied | COX_CD_1 | Non-Compliance | |||||||
Site Inspection | 11/26/2013 | Major Out of Compliance | COX_CD_1 | 0/2 | Routine Compliance | ||||||
Letter | 11/26/2013 | Satisfied | COX_CD_1 | Non-Compliance | |||||||
Site Inspection | 01/31/2012 | In Compliance | ZIMMERMAN_RA_1 | 0/2 | Non-Compliance | ||||||
Site Inspection | 12/05/2011 | Minor Out of Compliance | ZIMMERMAN_RA_1 | 0/2 | Routine Compliance | ||||||
Letter | 12/05/2011 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Site Inspection | 12/22/2010 | In Compliance | ZIMMERMAN_RA_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 12/08/2009 | In Compliance | ZIMMERMAN_RA_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 12/12/2008 | In Compliance | COX_CD_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 05/23/2008 | In Compliance | COX_CD_1 | 0/3 | Installation | ||||||
TCAR | 05/23/2008 | Satisfied | COX_CD_1 | Closure | |||||||
Letter | 05/23/2008 | Satisfied | COX_CD_1 | Closure | |||||||
Site Inspection | 02/13/2008 | Major Out of Compliance | COX_CD_1 | 0/3 | Closure | ||||||
Site Inspection | 12/18/2007 | Major Out of Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Letter | 12/18/2007 | Satisfied | ZIMMERMAN_RA_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 02/15/2007 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Site Inspection | 12/28/2006 | In Compliance | ZIMMERMAN_RA_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 09/27/2006 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
03/05/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Test the diesel STP sump and the diesel double wall bucket for integrity. | |||||||
03/05/2024 | 6066 | Minor | 4.4 Not repaired per applicable standards. | Repair/replace the spill bucket to have a sealed interstice where water won't infiltrate. | |||||||
03/05/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | All release detection testing must be done annually until a tank is taken "out of service". | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
12/28/1988 | COMPLETED | ||||||||||