DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Central   Type    Retail Station
 
County Lake   Status    OPEN
 
ID 8510084   Latitude    28° 48' 27.1506
 
Name SQRL SERVICE STATION
3105 N HIGHWAY 19A
Longitude    81° 40' 33.9515
  MOUNT DORA, FL 32757-3420 LL Method    DPHO
 
Contact LEVI RATLIFF   LL Status    REVIEWED
 
Phone (352) 430-6058   Status Date    10/01/2003
 
Account Owner Information
 
Name SQRL HOLDINGS LLC
27 RAHLING CIRCLE, SU#C
Little Rock, AR 72223
Effective Date    12/28/2022
 
Contact MATT BONAMINIO / EMILY JERNIGAN
 
Phone (501) 319-5315
 
Email MATT@SQRLHOLDINGS.COM
  Placard # / Date    661513 - 06/20/2023
Property Owner Information
 
Name SQRL HOLDINGS LLC
27 RAHLING CIRCLE, SU#C
Little Rock, AR 72223
Effective Date    12/28/2022
 
Contact MATT BONAMINIO / EMILY JERNIGAN
 
Phone (501) 319-5315
 
Email MATT@SQRLHOLDINGS.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
3 20000 Unleaded Gas (B) 06/01/2000 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(L) Compartmented
(M) Spill containment bucket
(R) Double wall - tank jacket
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(P) Internal pipe/internal sump riser
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
1 8000 Unleaded Gas (B) 05/01/1974 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(I) Suction piping system
(K) Dispenser liners
(8) Manually sampled wells
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
2 8000 Unleaded Gas (B) 05/01/1974 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(I) Suction piping system
(K) Dispenser liners
(8) Manually sampled wells
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   07/14/2023 07/14/2024 LIBERTY SURPLUS INSURANCE CORPORATION
INSURANCE   02/14/2023 07/14/2023 LIBERTY SURPLUS INSURANCE CORPORATION
INSURANCE   12/16/2022 07/14/2023 LIBERTY SURPLUS INSURANCE CORPORATION
INSURANCE   03/13/2021 03/13/2022 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   03/13/2020 03/13/2021 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   03/13/2019 03/13/2020 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   03/13/2018 03/13/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   03/13/2016 03/13/2017 COMMERCE & INDUSTRY
INSURANCE   03/13/2015 03/13/2016 COMMERCE & INDUSTRY
INSURANCE   03/13/2014 03/13/2015 COMMERCE & INDUSTRY
INSURANCE   03/13/2013 03/13/2014 COMMERCE & INDUSTRY
INSURANCE   03/13/2012 03/13/2013 ZURICH-AMERICAN
INSURANCE   03/13/2011 03/13/2012 ZURICH-AMERICAN
INSURANCE   03/13/2010 03/13/2011 ZURICH-AMERICAN
INSURANCE   03/13/2009 03/13/2010 ZURICH-AMERICAN
INSURANCE   07/11/1995 07/11/1998 FPLIPA
INSURANCE   02/07/1992 02/07/1995 FPLIPA
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 03/28/2006 04/03/2006 MINOR OUT-OF-COMPLIANCE COX 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes NEED TO TIGHTEN HOSE CLAMP ON SOUTHERN MOST ENTRY BOOT IN DISP. 5/6. MLLDS TESTED 3/7/06, 2 MONTHS LATE (PREV. TEST 12/28/04).
 
TCR 04/08/2005 04/13/2005 IN-COMPLIANCE COX 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes INSURANCE RECEIVED, DIESEL STP SUMP DRY.
 
TCI 03/08/2005 03/11/2005 SIGNIFICANT OUT-OF-COMPLIANCE COX 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes INSURANCE EXPIRED 3/6/05, NEED PROOF OF NEW INSURANCE. PUMP LIQUID FROM DIESEL STP SUMP. NOTE: RECORD FILL BUCKET CONDITION ON MONTHLYS, PAINT CROSSES ON FILL LIDS. SENSOR OP. 12/28/04, MLLDS TESTED 12/28/04.
 
TCI 03/19/2004 03/24/2004 IN-COMPLIANCE COX, BOWERS 0/1 COMPLIANCE ASSURANCE
 
TCI 03/14/2003 03/21/2003 IN-COMPLIANCE BOWERS/COX 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes MLLD 3/3/03, SENSOR CERT. 3/10/03.
 
TCI 03/22/2002 03/26/2002 IN-COMPLIANCE BOWERS 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes ANNUAL COMPLIANCE. MLLD DONE 2/22/02.
 
TCR 05/14/2001 05/23/2001 IN-COMPLIANCE BOWERS/COX 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes RE-INSP.
 
TCI 03/12/2001 03/13/2001 MINOR OUT-OF-COMPLIANCE BOWERS/COX 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes ANNUAL COMPLIANCE
 
TIN 08/03/2000 08/08/2000 IN-COMPLIANCE COX 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes ANNUAL COMPLIANCE
 
TXI 06/20/2000 06/20/2000 IN-COMPLIANCE BOWERS/COX 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes REMOVAL OF 2 8000 GAL. UST'S. BY PETROTECH. PCC#056694.
 
TCI 04/25/2000 04/27/2000 SIGNIFICANT OUT-OF-COMPLIANCE BOWERS/COX 0/2 COMPLIANCE ASSURANCE
 
 Completion Notes ANNUAL COMPLIANCE
 
UTCI 06/23/1998 06/29/1998 MINOR OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 03/13/2025 Satisfied DURAN_Z Enforcement
 
Enforcement Referral 08/29/2024 Accepted RIVERA_JX_2 Enforcement
 
Letter 08/16/2024 Satisfied BECKER_GT_1 Compliance Assistance
 
Site Inspection 02/08/2024 Major Out of Compliance COX_CD_1 0/1 Routine Compliance
 
Letter 02/08/2024 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 01/24/2024 Satisfied COX_CD_1 Routine Compliance
 
Electronic Communication 12/29/2022 Satisfied BECKER_GT_1 Compliance Assistance
 
Site Inspection 01/13/2022 In Compliance COX_CD_1 0/1 Routine Compliance
 
Letter 01/13/2022 Satisfied COX_CD_1 Routine Compliance
 
Phone Conversation 01/03/2022 Satisfied COX_CD_1 Routine Compliance
 
Meeting 04/05/2021 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 02/23/2021 Satisfied BECKER_GT_1 Compliance Assistance
 
Letter 01/04/2021 Satisfied JOHNSON_CJ Compliance Assistance
 
Electronic Communication 12/28/2020 Satisfied JOHNSON_CJ Enforcement
 
Electronic Communication 12/28/2020 Satisfied JOHNSON_CJ Enforcement
 
Electronic Communication 12/28/2020 Satisfied JOHNSON_CJ Enforcement
 
Enforcement Tracking 12/28/2020 Closed Without Enforcement JOHNSON_CJ Enforcement
 
Phone Conversation 12/21/2020 Satisfied JOHNSON_CJ Enforcement
 
Phone Conversation 12/21/2020 Satisfied JOHNSON_CJ Enforcement
 
Electronic Communication 12/15/2020 Satisfied JOHNSON_CJ Enforcement
 
Electronic Communication 12/01/2020 Satisfied JOHNSON_CJ Enforcement
 
Electronic Communication 12/01/2020 Satisfied JOHNSON_CJ Enforcement
 
Electronic Communication 12/01/2020 Satisfied JOHNSON_CJ Enforcement
 
Electronic Communication 10/12/2020 Satisfied JOHNSON_CJ Enforcement
 
Phone Conversation 09/25/2020 Satisfied COX_CD_1 Compliance Assistance
 
Enforcement Referral 09/21/2020 Accepted RAUENZAHN_RA_1 Enforcement
 
Phone Conversation 09/15/2020 Satisfied COX_CD_1 Compliance Assistance
 
Phone Conversation 06/26/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 06/23/2020 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Issue Document 06/23/2020 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Electronic Communication 04/27/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 04/27/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 04/13/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 10/07/2019 Satisfied COX_CD_1 Compliance Assistance
 
Phone Conversation 08/21/2019 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 08/19/2019 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 07/05/2019 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 06/26/2019 Satisfied COX_CD_1 Compliance Assistance
 
Site Inspection 06/03/2019 Major Out of Compliance COX_CD_1 0/1 Routine Compliance
 
Letter 06/03/2019 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 05/21/2019 Satisfied COX_CD_1 Routine Compliance
 
Phone Conversation 03/20/2019 Satisfied COX_CD_1 Routine Compliance
 
Electronic Communication 03/20/2019 Satisfied COX_CD_1 Routine Compliance
 
Electronic Communication 02/25/2019 Satisfied COX_CD_1 Compliance Assistance
 
Phone Conversation 02/22/2019 Satisfied COX_CD_1 Routine Compliance
 
Site Inspection 01/05/2017 In Compliance COX_CD_1 0/1 Non-Compliance
 
Letter 11/14/2016 Satisfied COX_CD_1 Non-Compliance
 
Site Inspection 11/08/2016 Minor Out of Compliance COX_CD_1 0/1 Routine Compliance
 
Phone Conversation 10/24/2016 Satisfied COX_CD_1 Routine Compliance
 
Phone Conversation 10/24/2016 Satisfied COX_CD_1 Routine Compliance
 
Site Inspection 05/20/2015 In Compliance COX_CD_1 0/1 Non-Compliance
 
Meeting 04/29/2015 Satisfied COX_CD_1 Non-Compliance
 
Letter 03/12/2015 Satisfied COX_CD_1 Non-Compliance
 
Site Inspection 03/03/2015 Major Out of Compliance COX_CD_1 0/1 Non-Compliance
 
Letter 10/31/2014 Satisfied COX_CD_1 Non-Compliance
 
Site Inspection 10/28/2014 Major Out of Compliance COX_CD_1 0/1 Routine Compliance
 
Record Document 04/05/2013 Satisfied COX_CD_1 Non-Compliance
 
Letter 03/27/2013 Satisfied COX_CD_1 Non-Compliance
 
Site Inspection 03/26/2013 Minor Out of Compliance COX_CD_1 0/1 Routine Compliance
 
Site Inspection 12/31/2012 In Compliance COX_CD_1 0/1 Non-Compliance
 
Site Inspection 06/21/2012 Minor Out of Compliance ZIMMERMAN_RA_1 0/1 Non-Compliance
 
Letter 06/21/2012 Satisfied ZIMMERMAN_RA_1 Non-Compliance
 
Letter 05/31/2012 Satisfied ZIMMERMAN_RA_1 Non-Compliance
 
Site Inspection 05/31/2012 Minor Out of Compliance ZIMMERMAN_RA_1 0/1 Non-Compliance
 
Letter 04/26/2012 Satisfied ZIMMERMAN_RA_1 Non-Compliance
 
Site Inspection 04/26/2012 Minor Out of Compliance ZIMMERMAN_RA_1 0/1 Routine Compliance
 
Site Inspection 05/18/2011 In Compliance ZIMMERMAN_RA_1 0/1 Non-Compliance
 
Letter 04/13/2011 Satisfied ZIMMERMAN_RA_1 Non-Compliance
 
Site Inspection 04/13/2011 Minor Out of Compliance ZIMMERMAN_RA_1 0/1 Routine Compliance
 
Site Inspection 04/21/2010 In Compliance ZIMMERMAN_RA_1 0/1 Routine Compliance
 
Site Inspection 06/01/2009 In Compliance ZIMMERMAN_RA_1 0/1 Non-Compliance
 
Letter 04/21/2009 Satisfied ZIMMERMAN_RA_1 Non-Compliance
 
Site Inspection 04/21/2009 Minor Out of Compliance ZIMMERMAN_RA_1 0/1 Routine Compliance
 
Site Inspection 07/10/2008 In Compliance ZIMMERMAN_RA_1 0/3 Non-Compliance
 
Site Inspection 04/14/2008 Minor Out of Compliance ZIMMERMAN_RA_1 0/3 Routine Compliance
 
Letter 04/14/2008 Satisfied ZIMMERMAN_RA_1 Non-Compliance
 
Site Inspection 05/14/2007 In Compliance ZIMMERMAN_RA_1 0/3 Non-Compliance
 
Site Inspection 04/19/2007 Minor Out of Compliance COX_CD_1 0/3 Routine Compliance
 
Letter 04/19/2007 Satisfied COX_CD_1 Non-Compliance
 
Emergency Preparedness Information 02/06/2007 Satisfied COX_CD_1 Routine Compliance
 
Site Inspection 02/06/2007 In Compliance COX_CD_1 0/3 Non-Compliance
 
Site Inspection 12/15/2006 Minor Out of Compliance COX_CD_1 0/3 Non-Compliance
 
Emergency Preparedness Information 09/22/2006 Satisfied ZIMMERMAN_RA_1 Routine Compliance
 
Site Inspection 08/24/2006 Minor Out of Compliance COX_CD_1 0/3 Non-Compliance
 
Site Inspection 04/28/2006 Minor Out of Compliance COX_CD_1 0/3 Non-Compliance
 
Letter 04/28/2006 Satisfied COX_CD_1 Non-Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/08/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Submit proof of the required annual testing of the flapper valves.
 
02/08/2024 6062 Minor 2.5 Release detection devices not tested annually. Submit proof of the required annual testing of the monitor and line leak detectors.
 
02/08/2024 6066 Minor 4.4 Not repaired per applicable standards. Loosen and pull back the test boots in the dispensers. Verify the test boots are loose in the STP sumps also.
 
02/08/2024 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Submit proof of the required monthly visual and electronic monitoring of the fuel system.
 
02/08/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Submit proof of the required integrity testing of the STP sumps, dispensers sumps and single wall spill buckets.
 
 
 
No Discharges Found