DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Central   Type    Retail Station
 
County Lake   Status    OPEN
 
ID 8510141   Latitude    28° 48' 41.2857
 
Name SQRL SERVICE STATION 336
1200 W MAIN ST
Longitude    81° 53' 1.89
  LEESBURG, FL 34748-4935 LL Method    DPHO
 
Contact MATT BONAMINIO   LL Status    REVIEWED
 
Phone (501) 319-5315   Status Date    10/01/2003
 
Account Owner Information
 
Name SQRL SERVICE STATIONS LLC
27 RAHLING CIRCLE STE C
LITTLE ROCK, AR 72223
Effective Date    03/15/2023
 
Contact JAMAL HIZAM
 
Phone (504) 595-7385
 
Email JAMAL@SQRLHOLDINGS.COM
  Placard # / Date    661499 - 06/20/2023
Property Owner Information
 
Name RCP LEESBURG LLC
411 THEODORE FREMD AVENUE SUITE 206 S
RYE, NY 10580
Effective Date    03/15/2023
 
Contact ANDREW FEIN/DAVID SHENFELD (201) 575-0643
 
Phone (914) 921-8269
 
Email ANDREW@RHINOCP.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
7 20000 Unleaded Gas (B) 11/01/2004 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
1 4000 Unleaded Gas (B) 07/01/1974 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(G) Electronic line leak detector
(I) Not required
(L) Automatic tank gauging - USTs
(S) Statistical Inventory Reconcile
(U) Annual piping pressure test
 
 
Tank Tank Size Content Installed Placement Status
2 4000 Unleaded Gas (B) 07/01/1974 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(G) Electronic line leak detector
(I) Not required
(L) Automatic tank gauging - USTs
(S) Statistical Inventory Reconcile
(U) Annual piping pressure test
 
 
Tank Tank Size Content Installed Placement Status
3 4000 Unleaded Gas (B) 07/01/1974 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(G) Electronic line leak detector
(I) Not required
(L) Automatic tank gauging - USTs
(S) Statistical Inventory Reconcile
(U) Annual piping pressure test
 
 
Tank Tank Size Content Installed Placement Status
4 4000 Unleaded Gas (B) 07/01/1974 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(G) Electronic line leak detector
(I) Not required
(L) Automatic tank gauging - USTs
(S) Statistical Inventory Reconcile
(U) Annual piping pressure test
 
 
Tank Tank Size Content Installed Placement Status
5 4000 Unleaded Gas (B) 07/01/1965 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(G) Electronic line leak detector
(I) Not required
(L) Automatic tank gauging - USTs
(S) Statistical Inventory Reconcile
(U) Annual piping pressure test
 
 
Tank Tank Size Content Installed Placement Status
6 4000 Vehicular Diesel (D) 07/01/1965 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(G) Electronic line leak detector
(I) Not required
(L) Automatic tank gauging - USTs
(S) Statistical Inventory Reconcile
(U) Annual piping pressure test
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   07/14/2023 07/14/2024 LIBERTY SURPLUS INSURANCE CORPORATION
INSURANCE   10/01/2021 10/01/2022 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   10/01/2020 10/01/2021 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   10/01/2019 10/01/2020 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   10/01/2018 10/01/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   10/01/2017 10/01/2018 COMMERCE & INDUSTRY
INSURANCE   10/01/2015 10/01/2016 COMMERCE & INDUSTRY
INSURANCE   10/01/2013 10/01/2014 COMMERCE & INDUSTRY
INSURANCE   10/01/2011 10/01/2012 ZURICH-AMERICAN
INSURANCE   10/01/2010 10/01/2011 ZURICH-AMERICAN
INSURANCE   10/01/2009 10/01/2010 ZURICH-AMERICAN
INSURANCE   03/14/2008 03/14/2009 AIG
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCR 04/04/2006 04/18/2006 MINOR OUT-OF-COMPLIANCE COX 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes MLLDS TESTED 3/22/06(REG AND PREM) 3/29/06 (DIESEL). SENSOR OP. DONE 3/29/06. PREM. AND DIESEL SPILL BUCKETS HAVE CRACKED RINGS, TEST AND REPAIR. REG. AND PREM. STP SUMP LIDS DON'T FIT. PAINT VAPOR RECOVERY LIDS ORANGE.
 
TCR 03/16/2006 03/17/2006 SIGNIFICANT OUT-OF-COMPLIANCE COX/BOWERS 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes NO VIOLATIONS HAVE BEEN ADDRESSED. R/UL STP SUMP LIFTED AND LID DOES NOT FIT.
 
TCI 02/15/2006 02/16/2006 MINOR OUT-OF-COMPLIANCE BOWERS/COX 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes MISSING MARCH 05 THROUGH PRESENT LIQUID STATUS PRINT OUTS. MISSING CURRENT MLLD AND VR/SENSOR CERT. RD IS VISUALS AND "LIQUID STATUS".
 
LTR 03/11/2005 03/14/2005 COX 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes DIESEL MLLD TEST RECEIVED.
 
TXP 03/01/2005 03/01/2005 COX 0/6 COMPLIANCE ASSURANCE
 
 Completion Notes CONTAMINATION EVALUATION WELLS DRILLED, ATC ON SITE SAMPLING 2/15/05.
 
TIN 02/22/2005 03/01/2005 IN-COMPLIANCE COX 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes PLACARD ON SITE, ALL SHEAR VALVES ANCHORED, TLS 350 WORKING OK, STILL NEED PROOF OF DIESEL MLLD TEST.
 
TIN 02/15/2005 03/01/2005 MINOR OUT-OF-COMPLIANCE COX 0/1 COMPLIANCE ASSURANCE
 
 Completion Notes INSTALLATION OF ONE 20,000 GAL. UST. AMERON DUOLOY PIPING, DIESEL HAS FLAPPER VALVE, R/UL AND PREMIUM FILLS HAVE BALLCHECK VALVES. NEED PROOF OF MLLD TESTS, TIGHTEN SHEAR VALVE ANCHORS, NO PLACARD ON SITE.
 
TXI 11/19/2004 12/02/2004 IN-COMPLIANCE BOWERS 0/6 COMPLIANCE ASSURANCE
 
 Completion Notes REMOVAL OF 6 USTS BY PETRO PLUS, INC. (PCC#1256780). FACILITY HAS SITE ASSESSMENT IN PROGRESS, REQUIRING FULL CLOSURE OR COPY OF COMPLETED SITE ASSESSMENT WITHIN 60 DAYS.
 
LTR 11/01/2004 11/02/2004 BOWERS 0/6 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED RESULTS OF TANK LINING TEST. ALL TANKS INSPECTED ON 9/9/04 - PASSED. 10 YEAR TEST WAS DONE 9/01.
 
TCR 08/25/2004 08/30/2004 IN-COMPLIANCE BOWERS 0/6 COMPLIANCE ASSURANCE
 
 Completion Notes TANKNOLOGY ON SITE TO PERFORM TTT, MLLD & SPILL BUCKET TESTS. VERBLE PASSING, AWAITING TEST RESULTS. SPILL BUCKETS OK.
 
TCR 04/14/2004 04/21/2004 IN-COMPLIANCE COX 0/6 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED ALL REQUIRED RECORDS. LIQUID REMOVED FROM STPS AND SUMPS.
 
TCI 02/24/2004 02/26/2004 MINOR OUT-OF-COMPLIANCE COX 0/6 COMPLIANCE ASSURANCE
 
 Completion Notes PLLD & 3YRTTTW/SIRS TESTED 4/25/03 AND 8/24/04. MISSING SIRS AND VISUALS, WATER IN DISP. AND R/UL STP.
 
DCCR 04/11/2003 05/05/2003 BOWERS 0/0 DISCHARGE PROJECT
 
 Completion Notes DRF SUBMITTED BY S&ME AS PART OF A PRE-BUY AUDIT BY SUN OIL CO.
 
TCR 03/11/2003 03/14/2003 IN-COMPLIANCE BOWERS 0/6 COMPLIANCE ASSURANCE
 
 Completion Notes LIQUID REMOVED FROM DISP. 1/2 AND R/UL STP SUMP
 
TCI 02/20/2003 02/21/2003 MINOR OUT-OF-COMPLIANCE BOWERS/COX 0/6 COMPLIANCE ASSURANCE
 
 Completion Notes SENSOR CERT. 5/02. AMARON, DW, RIDGED, FIB. PIPING.
 
TCI 02/21/2002 02/27/2002 IN-COMPLIANCE BOWERS/COX 0/6 COMPLIANCE ASSURANCE
 
 Completion Notes ANNUAL COMPLIANCE-PLLD DONE 3/26/01, 3YRTTT W/SIR 12/3/01
 
TCI 02/26/2001 03/02/2001 MINOR OUT-OF-COMPLIANCE BOWERS/COX 0/6 COMPLIANCE ASSURANCE
 
 Completion Notes ANNUAL COMPLIANCE
 
TCI 03/27/2000 03/30/2000 MINOR OUT-OF-COMPLIANCE BOWERS/COX 0/6 COMPLIANCE ASSURANCE
 
 Completion Notes ANNUAL COMPLIANCE
 
TCI 02/12/1999 03/16/1999 SIGNIFICANT OUT-OF-COMPLIANCE KRUSE 0/6 COMPLIANCE ASSURANCE
 
UTCI 02/12/1998 02/24/1998 SIGNIFICANT OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 09/09/2024 Accepted RIVERA_JX_2 Enforcement
 
Electronic Communication 08/14/2024 Satisfied COX_CD_1 Compliance Assistance
 
Site Inspection 02/08/2024 Major Out of Compliance COX_CD_1 0/1 Routine Compliance
 
Letter 02/08/2024 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 01/24/2024 Satisfied COX_CD_1 Routine Compliance
 
Electronic Communication 04/03/2023 Satisfied COX_CD_1 Incident
 
Electronic Communication 04/03/2023 Satisfied COX_CD_1 Incident
 
Electronic Communication 02/15/2023 Satisfied COX_CD_1 Routine Compliance
 
Document Management 02/15/2023 Satisfied COX_CD_1 Incident
 
Electronic Communication 02/15/2023 Satisfied COX_CD_1 Incident
 
Electronic Communication 02/15/2023 Satisfied COX_CD_1 Routine Compliance
 
Letter 04/25/2022 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 04/25/2022 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 04/25/2022 Satisfied COX_CD_1 Compliance Assistance
 
Letter 01/13/2022 Satisfied COX_CD_1 Compliance Assistance
 
Site Inspection 01/13/2022 Minor Out of Compliance COX_CD_1 0/1 Routine Compliance
 
Phone Conversation 01/03/2022 Satisfied COX_CD_1 Routine Compliance
 
Phone Conversation 12/30/2021 Satisfied COX_CD_1 Routine Compliance
 
Phone Conversation 12/30/2021 Satisfied COX_CD_1 Routine Compliance
 
Electronic Communication 09/03/2020 Satisfied COX_CD_1 Compliance Assistance
 
Letter 09/03/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 09/01/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 08/18/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 08/17/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 06/02/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 06/02/2020 Satisfied COX_CD_1 Compliance Assistance
 
Document Management 06/02/2020 Satisfied COX_CD_1 Routine Compliance
 
Electronic Communication 01/09/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 01/09/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 01/03/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 01/03/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 01/02/2020 Satisfied COX_CD_1 Compliance Assistance
 
Electronic Communication 01/02/2020 Satisfied COX_CD_1 Compliance Assistance
 
Site Inspection 12/16/2019 Major Out of Compliance COX_CD_1 0/1 Routine Compliance
 
Electronic Communication 12/16/2019 Satisfied COX_CD_1 Compliance Assistance
 
Letter 12/16/2019 Satisfied COX_CD_1 Compliance Assistance
 
Phone Conversation 11/07/2019 Satisfied COX_CD_1 Routine Compliance
 
Phone Conversation 11/07/2019 Satisfied COX_CD_1 Routine Compliance
 
Phone Conversation 11/04/2019 Satisfied COX_CD_1 Routine Compliance
 
Phone Conversation 11/04/2019 Satisfied COX_CD_1 Routine Compliance
 
Electronic Communication 02/28/2018 Satisfied COX_CD_1 Compliance Assistance
 
Letter 02/28/2018 Satisfied COX_CD_1 Compliance Assistance
 
Letter 02/15/2018 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Phone Conversation 02/15/2018 Satisfied COX_CD_1 Compliance Assistance
 
Site Inspection 11/28/2017 Major Out of Compliance COX_CD_1 0/1 Routine Compliance
 
Letter 11/28/2017 Satisfied COX_CD_1 Compliance Assistance
 
Phone Conversation 11/07/2017 Satisfied COX_CD_1 Routine Compliance
 
Phone Conversation 11/07/2017 Satisfied COX_CD_1 Routine Compliance
 
Phone Conversation 10/27/2017 Satisfied COX_CD_1 Routine Compliance
 
Phone Conversation 10/27/2017 Satisfied COX_CD_1 Routine Compliance
 
Site Inspection 12/04/2015 In Compliance COX_CD_1 0/1 Non-Compliance
 
Letter 11/05/2015 Satisfied COX_CD_1 Non-Compliance
 
Site Inspection 10/28/2015 Minor Out of Compliance COX_CD_1 0/1 Routine Compliance
 
Document Management 09/29/2015 Complete COX_CD_1 Routine Compliance
 
Phone Conversation 09/22/2015 Satisfied COX_CD_1 Routine Compliance
 
Letter 01/28/2014 Satisfied COX_CD_1 Non-Compliance
 
Site Inspection 01/27/2014 Minor Out of Compliance COX_CD_1 0/1 Routine Compliance
 
Site Inspection 02/14/2012 In Compliance COX_CD_1 0/1 Routine Compliance
 
Site Inspection 04/06/2011 In Compliance ZIMMERMAN_RA_1 0/1 Non-Compliance
 
Letter 02/16/2011 Satisfied ZIMMERMAN_RA_1 Non-Compliance
 
Site Inspection 02/16/2011 Minor Out of Compliance ZIMMERMAN_RA_1 0/1 Routine Compliance
 
Site Inspection 03/12/2010 In Compliance ZIMMERMAN_RA_1 0/1 Non-Compliance
 
Letter 02/16/2010 Satisfied ZIMMERMAN_RA_1 Non-Compliance
 
Site Inspection 02/16/2010 Minor Out of Compliance ZIMMERMAN_RA_1 0/1 Routine Compliance
 
Site Inspection 02/11/2009 In Compliance COX_CD_1 0/1 Routine Compliance
 
Record Document 09/11/2008 Satisfied ZIMMERMAN_RA_1 Non-Compliance
 
Record Document 04/14/2008 Satisfied ZIMMERMAN_RA_1 Non-Compliance
 
Site Inspection 02/12/2008 Minor Out of Compliance ZIMMERMAN_RA_1 0/7 Routine Compliance
 
Letter 02/12/2008 Satisfied ZIMMERMAN_RA_1 Non-Compliance
 
Site Inspection 03/30/2007 In Compliance ZIMMERMAN_RA_1 0/7 Non-Compliance
 
Letter 02/27/2007 Satisfied ZIMMERMAN_RA_1 Non-Compliance
 
Site Inspection 02/27/2007 Minor Out of Compliance ZIMMERMAN_RA_1 0/7 Routine Compliance
 
Emergency Preparedness Information 02/08/2007 Satisfied ZIMMERMAN_RA_1 Routine Compliance
 
Emergency Preparedness Information 09/26/2006 Satisfied ZIMMERMAN_RA_1 Routine Compliance
 
Site Inspection 05/03/2006 Major Out of Compliance COX_CD_1 0/7 Non-Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/08/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Submit proof of the repair of the premium spill bucket and a closure assessment of the bucket.
 
02/02/2024 6066 Minor 4.4 Not repaired per applicable standards. Clean and re-coat the components of the regular and premium STP sumps. Loosen the test boots in the dispensers and the STP sumps.
 
02/02/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove the water from the premium and regular STP sumps.
 
 
 
No Discharges Found