Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Southeast | Type | Fuel user/Non-retail | ||||||||
County | Monroe | Status | OPEN | ||||||||
ID | 8511884 | Latitude | 25° 19' 16.3074 | ||||||||
Name |
OCEAN REEF CLUB-AIRPORT FUEL TANK BARRACUDA LN |
Longitude | 80° 16' 45.6083 | ||||||||
KEY LARGO, FL 33037-3727 | LL Method | DPHO | |||||||||
Contact | EDUARDO PEREZ | LL Status | REVIEWED | ||||||||
Phone | (305) 367-5919 | Status Date | 06/08/2005 | ||||||||
Account Owner Information | |||||||||||
Name | OCEAN REEF CLUB INC 35 OCEAN REEF DR #200 Key Largo, FL 33037-5293 |
Effective Date | 01/01/2001 | ||||||||
Contact | EDUARDO PEREZ | ||||||||||
Phone | (305) 367-5919 | ||||||||||
EPEREZ@OCEANREEF.COM | |||||||||||
Placard # / Date | 704673 - 12/12/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | OCEAN REEF CLUB INC 35 OCEAN REEF DR #200 Key Largo, FL 33037-5293 |
Effective Date | 01/01/2001 | ||||||||
Contact | EDUARDO PEREZ | ||||||||||
Phone | (305) 367-5919 | ||||||||||
EPEREZ@OCEANREEF.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 12000 | Jet Fuel (F) | 09/01/2013 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (N) Flow shut-Off (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system (J) Pressurized piping system |
(D) SPCC Plan (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 15000 | Jet Fuel (F) | 09/01/2023 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel |
(B) Steel/galvanized metal | (F) Monitor dbl wall tank space | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 8000 | Jet Fuel (F) | 09/01/2011 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (N) Flow shut-Off (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system (J) Pressurized piping system |
(D) SPCC Plan (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 4000 | Aviation Gas (E) | ABOVEGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (Y) Unknown | (I) Not required | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 2000 | Aviation Gas (E) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (Y) Unknown | (I) Not required | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 2000 | Aviation Gas (E) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (Y) Unknown | (I) Not required | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 06/01/2018 | 06/01/2019 | ILLINOIS UNION | ||||||||
INSURANCE | 03/18/2014 | 03/18/2017 | AIG | ||||||||
INSURANCE | 03/01/2011 | 03/01/2014 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Referral | 06/13/2023 | Accepted | SHANBERG_V | Enforcement | |||||||
Site Inspection | 05/24/2023 | Major Out of Compliance | SHANBERG_V | 1/0 | Routine Compliance | ||||||
Record Document | 10/02/2019 | Satisfied | WINKLER_MG_1 | Compliance Assistance | |||||||
Letter | 10/02/2019 | Satisfied | WINKLER_MG_1 | Compliance Assistance | |||||||
Letter | 11/16/2018 | Satisfied | WINKLER_MG_1 | Compliance Assistance | |||||||
Site Inspection | 11/15/2018 | Minor Out of Compliance | WINKLER_MG_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 06/09/2016 | In Compliance | WINKLER_MG_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 08/28/2014 | In Compliance | WINKLER_MG_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 10/25/2013 | In Compliance | WINKLER_MG_1 | 1/0 | Installation | ||||||
Site Inspection | 10/25/2013 | In Compliance | WINKLER_MG_1 | 1/0 | Closure | ||||||
Site Inspection | 07/19/2012 | In Compliance | WINKLER_MG_1 | 1/0 | Routine Compliance | ||||||
Site Inspection | 10/26/2011 | In Compliance | WINKLER_MG_1 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
05/24/2023 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Provide visual monthly monitoring documentation for 2020, 2021, and 2022 to the Department. | |||||||
12/29/2022 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | Provide financial responsibility documentation for 2020, 2021, and 2022 to the Department. | |||||||
12/29/2022 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Provide release detection annual operability testing documentation for 2020, 2021, and 2022 to the Department. | |||||||
12/29/2022 | 7002 | Minor | 1.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Update registration with correct facility contact information and provide documentation to the Department. | |||||||
12/29/2022 | 7094 | Minor | 1.13 Permanent records not available within 5 working days notice. | Provide missing documentation identified in this report for 2020, 2021, and 2022 to the Department. | |||||||
12/29/2022 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Provide overfill protection device annual operability testing documentation for 2020, 2021, and 2022 to the Department. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
12/05/1991 | COMPLETED | 10 | ABANDONED TANK RESTORATION PROGRAM-ELIGIBLE | ||||||||