Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Northwest | Type | Retail Station | ||||||||
County | Okaloosa | Status | OPEN | ||||||||
ID | 8512351 | Latitude | 30° 24' 23.7646 | ||||||||
Name |
GROOVY DHRUVI 245 MIRACLE STRIP PKWY |
Longitude | 86° 37' 50.8011 | ||||||||
FORT WALTON BEACH, FL 32548 | LL Method | DPHO | |||||||||
Contact | ALLAN SHAH | LL Status | REVIEWED | ||||||||
Phone | (850) 319-8224 | Status Date | 09/21/2023 | ||||||||
Account Owner Information | |||||||||||
Name | GROOVY DHRUVI LLC 314 BAINBRIDGE ST PANAMA CITY BEACH, FL 32413 |
Effective Date | 07/07/2017 | ||||||||
Contact | ALLAN SHAH | ||||||||||
Phone | (850) 319-8224 | ||||||||||
MAGICMART31@GMAIL.COM | |||||||||||
Placard # / Date | 701386 - 09/12/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | GROOVY DHRUVI LLC 314 BAINBRIDGE ST PANAMA CITY BEACH, FL 32413 |
Effective Date | 07/07/2017 | ||||||||
Contact | ALLAN SHAH | ||||||||||
Phone | (850) 319-8224 | ||||||||||
MAGICMART31@GMAIL.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
10 | 20000 | Ethanol E10 (8) | 05/01/2017 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (I) Double wall (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms |
(F) Double wall (J) Pressurized piping system (L) Bulk product system (N) Approved synthetic material |
(F) Monitor dbl wall tank space (H) Mechanical line leak detector (J) Monitor piping/liner space (Z) DEP approved monitoring |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 6000 | Unleaded Gas (B) | 07/01/1982 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (D) External protective coating | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 3000 | Leaded Gas (A) | 07/01/1970 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (D) External protective coating | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 3000 | Leaded Gas (A) | 07/01/1970 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (D) External protective coating | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 3000 | Unleaded Gas (B) | 07/01/1970 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (D) External protective coating (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 3000 | Unleaded Gas (B) | 07/01/1970 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (D) External protective coating (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 6000 | Vehicular Diesel (D) | 07/01/1982 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (D) External protective coating (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 10000 | Unleaded Gas (B) | 12/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (G) Sacrificial anode CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
8 | 10000 | Unleaded Gas (B) | 12/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (G) Sacrificial anode CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
9 | 10000 | Unleaded Gas (B) | 12/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (G) Sacrificial anode CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
EXEMPT-NOT REQUIRED | |||||||||||
INSURANCE | 06/23/2024 | 06/23/2026 | CRUM & FORSTER SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 06/23/2022 | 06/23/2024 | CRUM & FORSTER SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 06/23/2020 | 06/23/2022 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 06/23/2018 | 06/23/2019 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 06/23/2017 | 06/23/2018 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 11/11/2009 | 11/11/2010 | ZURICH-AMERICAN | ||||||||
INSURANCE | 11/11/2008 | 11/11/2009 | ZURICH-AMERICAN | ||||||||
INSURANCE | 09/25/1999 | 09/25/2000 | COMMERCE & INDUSTRY | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TDI | 02/03/2006 | 02/10/2006 | SIGNIFICANT OUT-OF-COMPLIANCE | JOSEPH D. THAYER | 0/3 | DISCHARGE PROJECT | |||||
Completion Notes THIS INSPECTION IS FOR AN INCIDENT NOTIFICATION FORM FOR A FAILED PRECISION TIGHTNESS TEST ON THE PREMIUM TANK. TEST INDICATED A HOLE AT THE BOTTOM OF THE TANK IN THE AREA OF THE STRIKE PLATE. | |||||||||||
TCI | 10/20/2005 | 10/31/2005 | IN-COMPLIANCE | JOSEPH D. THAYER | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 05/17/2005 | 05/19/2005 | COMPLIANCE ASSURANCE | ||||||||
TCI | 02/10/2005 | 02/24/2005 | MINOR OUT-OF-COMPLIANCE | JOHN S. STEVENSON | 0/3 | COMPLIANCE ASSURANCE | |||||
TCR | 02/18/2004 | 02/23/2004 | IN-COMPLIANCE | J. SCOTT HALE | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 10/29/2003 | 10/31/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | J. SCOTT HALE | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 08/27/2002 | 09/04/2002 | IN-COMPLIANCE | V. PAUL HUTCHERSON | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 08/23/2001 | 08/24/2001 | IN-COMPLIANCE | THAYER_JD | 0/3 | COMPLIANCE ASSURANCE | |||||
TCR | 12/19/2000 | 12/27/2000 | IN-COMPLIANCE | THAYER_JD | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 08/29/2000 | 09/09/2000 | MINOR OUT-OF-COMPLIANCE | THAYER_JD | 0/3 | COMPLIANCE ASSURANCE | |||||
TCR | 04/18/2000 | 04/20/2000 | IN-COMPLIANCE | HOLLINGSHEAD_JB | 0/3 | COMPLIANCE ASSURANCE | |||||
TIN | 12/28/1999 | 01/03/2000 | SIGNIFICANT OUT-OF-COMPLIANCE | HOLLINGSHEAD_JB | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 11/03/1999 | 11/09/1999 | THAYER_JD | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 08/13/1999 | 08/23/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | THAYER_JD | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 01/15/2025 | Satisfied | ELLIOTT_EV_1 | Compliance Assistance | |||||||
Site Inspection | 01/15/2025 | Major Out of Compliance | ELLIOTT_EV_1 | 0/1 | Routine Compliance | ||||||
Electronic Communication | 01/15/2025 | Satisfied | ELLIOTT_EV_1 | Routine Compliance | |||||||
Letter | 02/09/2023 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 02/08/2023 | In Compliance | PAYNE_CL_1 | 0/1 | Compliance Assistance | ||||||
Record Document | 12/21/2022 | Satisfied | PAYNE_CL_1 | Compliance Assistance | |||||||
Site Inspection | 12/19/2022 | Major Out of Compliance | PAYNE_CL_1 | 0/1 | Routine Compliance | ||||||
Letter | 12/19/2022 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Electronic Communication | 12/14/2022 | Satisfied | PAYNE_CL_1 | Routine Compliance | |||||||
Enforcement Tracking | 07/12/2022 | Closed With Enforcement | TOMAS_M | Enforcement | |||||||
Document Management | 07/12/2022 | Satisfied | TOMAS_M | Enforcement | |||||||
Document Management | 07/12/2022 | Satisfied | TOMAS_M | Enforcement | |||||||
Letter | 03/10/2022 | Satisfied | TOMAS_M | Enforcement | |||||||
Enforcement Referral | 02/28/2022 | Accepted | PAYNE_CL_1 | Enforcement | |||||||
Issue Document | 02/24/2022 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Letter | 02/24/2022 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 02/23/2022 | Major Out of Compliance | PAYNE_CL_1 | 0/1 | Complaint | ||||||
Letter | 02/22/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Issue Document | 02/22/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Record Document | 12/28/2020 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Record Document | 12/10/2020 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Enforcement Tracking | 11/19/2020 | Closed Without Enforcement | BRISTOL_S | Enforcement | |||||||
Letter | 11/18/2020 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 11/18/2020 | Minor Out of Compliance | PAYNE_CL_1 | 0/1 | Compliance Assistance | ||||||
Issue Document | 11/18/2020 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Phone Conversation | 11/10/2020 | Satisfied | PAYNE_CL_1 | Compliance Assistance | |||||||
Record Document | 10/12/2020 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Letter | 10/09/2020 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Issue Document | 10/09/2020 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 10/09/2020 | Major Out of Compliance | PAYNE_CL_1 | 0/1 | Routine Compliance | ||||||
Phone Conversation | 10/06/2020 | Satisfied | PAYNE_CL_1 | Routine Compliance | |||||||
Electronic Communication | 09/16/2019 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Electronic Communication | 09/09/2019 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Enforcement Referral | 01/30/2019 | Accepted | PAYNE_CL_1 | Enforcement | |||||||
Electronic Communication | 10/04/2018 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Record Document | 07/31/2018 | Satisfied | PAYNE_CL_1 | Routine Compliance | |||||||
Record Document | 07/24/2018 | Satisfied | PAYNE_CL_1 | Compliance Assistance | |||||||
Site Inspection | 07/19/2018 | Major Out of Compliance | PAYNE_CL_1 | 0/1 | Routine Compliance | ||||||
Letter | 07/19/2018 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Issue Document | 07/19/2018 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Phone Conversation | 07/17/2018 | Satisfied | PAYNE_CL_1 | Routine Compliance | |||||||
Site Inspection | 07/21/2017 | In Compliance | BRAZILE_DO_1 | 0/1 | Installation | ||||||
Electronic Communication | 07/21/2017 | Satisfied | BRAZILE_DO_1 | Installation | |||||||
TCAR | 07/02/2014 | Satisfied | DAURIA_KL_1 | Closure | |||||||
Letter | 06/04/2014 | Satisfied | FOXWORTH_S_1 | Closure | |||||||
Document Management | 05/23/2014 | Complete | DAURIA_KL_1 | Closure | |||||||
Enforcement Tracking | 04/28/2014 | Closed Without Enforcement | GILLMAN_M | Enforcement | |||||||
Site Inspection | 04/23/2014 | In Compliance | FOXWORTH_S_1 | 0/3 | Closure | ||||||
Electronic Communication | 11/07/2013 | Satisfied | BRISTOL_S | Enforcement | |||||||
Electronic Communication | 10/24/2013 | Satisfied | BRISTOL_S | Enforcement | |||||||
Phone Conversation | 10/15/2013 | Satisfied | BRISTOL_S | Enforcement | |||||||
Issue Document | 08/09/2013 | Satisfied | BRISTOL_S | Enforcement | |||||||
Letter | 05/16/2013 | Satisfied | DAURIA_KL_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 05/16/2013 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Site Inspection | 05/16/2013 | Major Out of Compliance | KHAN_MR_1 | 0/2 | Routine Compliance | ||||||
Record Document | 12/15/2011 | Satisfied | GILLMAN_M | Enforcement | |||||||
Record Document | 10/12/2011 | Satisfied | GILLMAN_M | Enforcement | |||||||
Letter | 09/28/2011 | Satisfied | GILLMAN_M | Enforcement | |||||||
Phone Conversation | 09/28/2011 | Satisfied | GILLMAN_M | Enforcement | |||||||
Phone Conversation | 09/28/2011 | Satisfied | GILLMAN_M | Enforcement | |||||||
Phone Conversation | 09/06/2011 | Satisfied | GILLMAN_M | Enforcement | |||||||
Site Inspection | 08/15/2011 | Major Out of Compliance | GILLMAN_M | 0/3 | Enforcement | ||||||
Letter | 08/04/2011 | Satisfied | RHOADS_KM_1 | Non-Compliance | |||||||
Site Inspection | 08/03/2011 | Major Out of Compliance | TISSINGTON_AB_1 | 0/3 | Routine Compliance | ||||||
Enforcement Referral | 11/09/2010 | Accepted | GILLMAN_M | Enforcement | |||||||
Letter | 11/08/2010 | Satisfied | PIERCE_LL_1 | Non-Compliance | |||||||
Site Inspection | 11/04/2010 | Minor Out of Compliance | TISSINGTON_AB_1 | 0/3 | Non-Compliance | ||||||
Letter | 09/20/2010 | Satisfied | PIERCE_LL_1 | Non-Compliance | |||||||
Site Inspection | 08/27/2010 | Minor Out of Compliance | TISSINGTON_AB_1 | 0/3 | Routine Compliance | ||||||
Meeting | 04/02/2010 | Satisfied | TISSINGTON_AB_1 | Routine Compliance | |||||||
Letter | 09/08/2009 | Satisfied | TISSINGTON_AB_1 | Non-Compliance | |||||||
Site Inspection | 08/31/2009 | Minor Out of Compliance | TISSINGTON_AB_1 | 0/1 | Routine Compliance | ||||||
Emergency Preparedness Information | 08/31/2009 | Satisfied | TISSINGTON_AB_1 | Routine Compliance | |||||||
Record Document | 08/28/2009 | Satisfied | STEVENSON_JS | Non-Compliance | |||||||
Record Document | 11/07/2008 | Satisfied | TISSINGTON_AB_1 | Non-Compliance | |||||||
Record Document | 11/06/2008 | Satisfied | TISSINGTON_AB_1 | Non-Compliance | |||||||
Phone Conversation | 10/21/2008 | Satisfied | TISSINGTON_AB_1 | Non-Compliance | |||||||
Letter | 09/11/2008 | Satisfied | TISSINGTON_AB_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 08/26/2008 | Satisfied | TISSINGTON_AB_1 | Routine Compliance | |||||||
Site Inspection | 08/26/2008 | Major Out of Compliance | TISSINGTON_AB_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 02/26/2008 | In Compliance | STEVENSON_JS | 0/3 | Routine Compliance | ||||||
Site Inspection | 02/27/2007 | In Compliance | STEVENSON_JS | 0/3 | Non-Compliance | ||||||
Letter | 02/27/2007 | Satisfied | STEVENSON_JS | Non-Compliance | |||||||
Letter | 02/27/2007 | Satisfied | STEVENSON_JS | Non-Compliance | |||||||
Emergency Preparedness Information | 02/12/2007 | Satisfied | TISSINGTON_AB_1 | Routine Compliance | |||||||
Site Inspection | 01/09/2007 | Minor Out of Compliance | STEVENSON_JS | 0/3 | Non-Compliance | ||||||
Site Inspection | 12/29/2006 | Minor Out of Compliance | STEVENSON_JS | 0/3 | Routine Compliance | ||||||
Record Document | 11/17/2006 | Satisfied | THAYER_JD_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 09/26/2006 | Satisfied | TISSINGTON_AB_1 | Routine Compliance | |||||||
Letter | 06/28/2006 | Satisfied | THAYER_JD_1 | Non-Compliance | |||||||
Letter | 06/28/2006 | Warning Letter Issued | THAYER_JD_1 | Non-Compliance | |||||||
Site Inspection | 06/28/2006 | Major Out of Compliance | THAYER_JD_1 | 0/9 | Discharge | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
01/15/2025 | 6066 | Minor | 4.4 Not repaired per applicable standards. | Have a certified contractor/technician remove as much rust as possible and coat the pump/components with a rust preventative paint. If necessary, replace any components that are severely corroded/rusted. Email a detailed work invoice to the inspector and a picture of the sump after work has been completed. Email: Emily.Elliott@FLHelath.gov | |||||||
01/15/2025 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Remove the liquid from the secondary and re-install or replace the interstitial gauge as necessary. The integrity of the regular non ethanol spill containment must be tested before it brought back into service. Please provide a copy of testing results and detailed work invoice of work completed to clear the violation. Email: Emily.Elliott@FLHealth.gov | |||||||
01/15/2025 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Have the liquid removed and properly disposed of from the Premium and Regular Non-Ethanol STP Sumps. Email a copy of the work invoice to the inspector for review and labeled pictures. Email: Emily.Elliott@FLHealth.gov | |||||||
01/15/2025 | 6043 | Minor | 4.13 Fillbox covers not marked according to requirements. | Have the Regular Non-Ethanol and Premium Spill Containment Lids repainted according to API standards. Email to the inspector a detailed work invoice and/or a picture of the painted Regular Non-Ethanol and Premium Spill Containment Lids. Email: Emily.Elliott@FLHealth.gov | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
06/22/1987 | ACTIVE | 10 | EARLY DETECTION INCENTIVE-ELIGIBLE | ||||||||