DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/17/2025        Last Data Refresh: 05/16/2025        Report Generated from DOPPLER
 
District Northeast   Type    Bulk Storage Facility
 
County Putnam   Status    OPEN
 
ID 8515743   Latitude    29° 39' 30.4609
 
Name LEWIS OIL CO
893 HWY 19 N
Longitude    81° 40' 2.1577
  PALATKA, FL 32177 LL Method    DPHO
 
Contact WENDA LEWIS EXT 225   LL Status    REVIEWED
 
Phone (352) 376-3293   Status Date    08/05/2003
 
Account Owner Information
 
Name LEWIS OIL CO INC
PO BOX 141286
GAINESVILLE, FL 32614
Effective Date    05/20/1994
 
Contact WENDA LEWIS (MGR)
 
Phone (352) 376-3293
 
Email WLEWIS@LEWISOILCO.COM
  Placard # / Date    701581 - 10/02/2024
Property Owner Information
 
Name LEWIS OIL CO INC
PO BOX 141286
GAINESVILLE, FL 32614
Effective Date    08/13/2003
 
Contact WENDA LEWIS (MGR)
 
Phone (352) 376-3293
 
Email WLEWIS@LEWISOILCO.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
10 8000 Vehicular Diesel (D) 02/01/1995 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
11 15000 Unleaded Gas (B) 09/01/1995 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
12 15000 Kerosene (K) 07/01/1996 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
(L) Compartmented
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
6 17000 Vehicular Diesel (D) 02/01/1995 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
7 15000 Vehicular Diesel (D) 02/01/1995 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
8 15000 Unleaded Gas (B) 02/01/1995 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
9 10000 Unleaded Gas (B) 02/01/1995 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
1 3000 Unleaded Gas (B) 08/01/1983 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass
(F) Double wall
(8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
2 3000 Unleaded Gas (B) 08/01/1983 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass
(F) Double wall
(8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
3 5000 Unleaded Gas (B) 08/01/1983 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass
(F) Double wall
(8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
4 12000 Vehicular Diesel (D) 08/01/1983 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (C) Fiberglass
(F) Double wall
(8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
5 3000 Fuel Oil - Distribution (N) 08/01/1983 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (A) Abv, no soil contact (I) Not required
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   06/14/2020 06/14/2022 SCOTTSDALE INSURANCE COMPANY
INSURANCE   05/14/2019 05/14/2020 ACE AMERICAN INSURANCE COMPANY
INSURANCE   05/14/2018 05/14/2019 ILLINOIS UNION
INSURANCE   05/14/2016 05/14/2018 ACE
INSURANCE   01/31/2015 05/14/2016 AIG
INSURANCE   01/31/2015 01/31/2016 AIG
INSURANCE   01/31/2014 01/31/2015 AIG
INSURANCE   01/31/2013 01/31/2014 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/31/2012 01/31/2013 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/31/2010 01/31/2011 CHARTIS SPECIALTY INSURANCE CO
INSURANCE   01/31/2009 01/31/2010 AIG
INSURANCE   01/31/2008 01/31/2009 ZURICH-AMERICAN
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCR 02/01/2006 02/02/2006 MINOR OUT-OF-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
 Completion Notes ANTI-SIPHON VALVES HAVE NOT BEEN INSTALLED.
 
TCR 12/20/2005 12/20/2005 MINOR OUT-OF-COMPLIANCE FLOWERS_D 0/7 COMPLIANCE ASSURANCE
 
 Completion Notes ANTI-SIPHON VALVES HAVE NOT BEEN INSTALLED ON ANY TANKS AT SITE.
 
WLI 12/20/2005 12/20/2005 FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
TCR 11/22/2005 11/22/2005 IN-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
 Completion Notes NEW PAINT ON TANKS AND CONTAINMENT AREA HAS BEEN APPROVED BY ENGINEER BY WRITTEN LETTER 11/21/05.
 
TCR 11/01/2005 11/15/2005 MINOR OUT-OF-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
 Completion Notes FIELD VISIT FOUND NO ANTI-SIPHON VALVES ON ANY OF THE 7-SEVEN TANKS FOR PIPING GOING FROM TOP OF TANKS TO UNDERGROUND TO ENVIRON SUMP CONTAINMENTS.
 
RRBD 09/20/2005 11/28/2005 FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
TCR 09/14/2005 09/14/2005 SIGNIFICANT OUT-OF-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
 Completion Notes NO RECORDS AVAILABLE FOR FOR CONTAINMENT RECERTIFICATION OR EVIDENCE THAT TANKS HAVE BEEN REPAINTED OVER RUST SECTIONS.
 
TCI 07/21/2005 07/21/2005 SIGNIFICANT OUT-OF-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
 Completion Notes PAINT PEELING OFF SIDES AND TOP OF TANKS,CONTAINMENT AREA HAS BEEN REPAIRED IN AREAS AND NEEDS ENGINEER APPROVAL THAT IT STILL MEETS ACI224R-89 STANDARDS.
 
TCI 07/15/2004 07/16/2004 IN-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
TCI 07/22/2003 07/22/2003 IN-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
TCI 07/16/2002 07/17/2002 IN-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
TCR 09/24/2001 09/25/2001 IN-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
TCI 07/18/2001 07/20/2001 MINOR OUT-OF-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
TCR 07/20/2000 07/21/2000 IN-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
TCI 07/18/2000 07/21/2000 MINOR OUT-OF-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
TCR 04/03/2000 04/05/2000 IN-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
TCR 09/22/1999 09/22/1999 IN-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
TCI 08/10/1999 08/10/1999 MINOR OUT-OF-COMPLIANCE FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
NCLI 08/10/1999 08/10/1999 FLOWERS_D 7/0 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 11/07/2022 Accepted HARRINGTON_RD_1 Enforcement
 
Electronic Communication 02/09/2022 Satisfied RAMSEY_TH_1 Closure
 
TCAR 02/09/2022 Satisfied RAMSEY_TH_1 Closure
 
Discharge Reporting 02/09/2022 Satisfied HARRINGTON_RD_1 Discharge
 
Letter 02/09/2022 Satisfied RAMSEY_TH_1 Closure
 
Electronic Communication 11/07/2021 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Letter 11/07/2021 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 11/07/2021 Major Out of Compliance HARRINGTON_RD_1 7/0 Routine Compliance
 
Electronic Communication 11/07/2021 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Issue Document 01/19/2021 Satisfied HARRIS_MJ Routine Compliance
 
Enforcement Tracking 11/24/2020 Closed Without Enforcement COLE_K Enforcement
 
Letter 11/24/2020 Satisfied COLE_K Enforcement
 
Electronic Communication 02/24/2020 Satisfied COLE_K Enforcement
 
Phone Conversation 02/24/2020 Satisfied COLE_K Enforcement
 
Phone Conversation 02/19/2020 Satisfied COLE_K Enforcement
 
Enforcement Referral 12/16/2019 Accepted HARRINGTON_RD_1 Enforcement
 
Electronic Communication 12/08/2019 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 02/17/2019 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Electronic Communication 02/17/2019 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Letter 02/17/2019 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 02/17/2019 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 02/17/2019 Minor Out of Compliance HARRINGTON_RD_1 7/0 Routine Compliance
 
Site Inspection 11/04/2018 In Compliance HARRINGTON_RD_1 7/0 Discharge
 
Document Management 11/04/2018 Satisfied HARRINGTON_RD_1 Discharge
 
Record Document 09/02/2018 Satisfied HARRINGTON_RD_1 Installation
 
Record Document 06/24/2016 Satisfied HARRINGTON_RD_1 Installation
 
Site Inspection 05/13/2016 In Compliance HARRINGTON_RD_1 0/0 Closure
 
Electronic Communication 05/13/2016 Satisfied HARRINGTON_RD_1 Closure
 
Site Inspection 05/13/2016 In Compliance HARRINGTON_RD_1 7/0 Installation
 
Letter 12/10/2015 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Site Inspection 12/10/2015 Minor Out of Compliance HARRINGTON_RD_1 7/0 Routine Compliance
 
Record Document 05/16/2014 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 05/14/2014 In Compliance HARRINGTON_RD_1 7/0 Routine Compliance
 
Electronic Communication 05/14/2014 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Meeting 05/13/2013 Satisfied DEFALCO_L QA/QC
 
Site Inspection 04/17/2013 In Compliance CERIC_M_1 7/0 Non-Compliance
 
Record Document 03/04/2013 Satisfied CERIC_M_1 Non-Compliance
 
Emergency Preparedness Information 02/20/2013 Satisfied CERIC_M_1 Routine Compliance
 
Site Inspection 02/19/2013 Major Out of Compliance CERIC_M_1 7/0 Routine Compliance
 
Letter 02/19/2013 Satisfied CERIC_M_1 Non-Compliance
 
Record Document 06/07/2011 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Site Inspection 01/26/2011 Minor Out of Compliance BARNETT_PC_1 7/0 Routine Compliance
 
Letter 01/26/2011 Satisfied BARNETT_PC_1 Non-Compliance
 
Issue Document 05/14/2010 Satisfied DEFALCO_L Enforcement
 
Site Inspection 12/23/2009 In Compliance BARNETT_PC_1 7/0 Routine Compliance
 
Site Inspection 09/05/2008 In Compliance BARNETT_PC_1 7/0 Routine Compliance
 
Enforcement Tracking 04/15/2008 Closed With Enforcement DEFALCO_L Enforcement
 
Site Inspection 04/11/2008 In Compliance BARNETT_PC_1 7/0 Non-Compliance
 
Enforcement Referral 10/23/2007 Accepted DEFALCO_L Enforcement
 
Letter 08/23/2007 Satisfied BARNETT_PC_1 Non-Compliance
 
Site Inspection 08/14/2007 Minor Out of Compliance BARNETT_PC_1 7/0 Routine Compliance
 
Emergency Preparedness Information 05/25/2007 Satisfied BARNETT_PC_1 Routine Compliance
 
Emergency Preparedness Information 02/19/2007 Satisfied BARNETT_PC_1 Routine Compliance
 
Record Document 01/08/2007 Satisfied DOHANEY_T Enforcement
 
Issue Document 01/08/2007 Satisfied DEFALCO_L Enforcement
 
Site Inspection 08/29/2006 Minor Out of Compliance FLOWERS_D 7/0 Non-Compliance
 
Record Document 08/11/2006 Satisfied DOHANEY_T Non-Compliance
 
Issue Document 08/11/2006 Satisfied DOHANEY_T Enforcement
 
Site Inspection 08/09/2006 Minor Out of Compliance DEFALCO_L 7/0 Enforcement
 
Letter 07/27/2006 Satisfied FLOWERS_D Non-Compliance
 
Site Inspection 07/27/2006 Minor Out of Compliance FLOWERS_D 7/0 Routine Compliance
 
Site Inspection 05/26/2006 Minor Out of Compliance FLOWERS_D 7/0 Non-Compliance
 
Letter 05/01/2006 Satisfied FLOWERS_D Non-Compliance
 
Site Inspection 05/01/2006 Minor Out of Compliance FLOWERS_D 7/0 Non-Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
11/07/2021 7055 SNC-B 3.3 Pressurized piping not installed with line leak detectors or does not meet requirements of paragraph 62-762.601(4)(b). Replace the line leak detectors on small diameter pressurized piping. provide documentation and test results.
 
11/07/2021 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove liquid from the components listed above. Provide documentation.
 
11/07/2021 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Repair or replace the transition sump sensors. Alternately, monthly visuals can be done for the sumps as release detection. Provide documentation or resolution.
 
11/07/2021 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Perform Integrity tests of the piping transition sumps and dispenser liners (every 3 years). Provide result documentation.
 
11/07/2021 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Repair the leaking meter in dispenser 6. Provide documentation.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
02/28/1995   COMPLETED 75 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE