DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 03/19/2025        Last Data Refresh: 03/18/2025        Report Generated from DOPPLER
 
District Northeast   Type    Retail Station
 
County Putnam   Status    OPEN
 
ID 8515788   Latitude    29° 35' 15.2497
 
Name LEWIS OIL CO. INC.
298 HWY 21 S
Longitude    81° 58' 24.304
  HAWTHORNE, FL 32640 LL Method    DPHO
 
Contact WENDA LEWIS   LL Status    REVIEWED
 
Phone (352) 376-3293   Status Date    06/02/2003
 
Account Owner Information
 
Name LEWIS OIL CO INC
PO BOX 141286
GAINESVILLE, FL 32614
Effective Date    11/07/2023
 
Contact WENDA LEWIS (MGR)
 
Phone (352) 376-3293
 
Email WLEWIS@LEWISOILCO.COM
  Placard # / Date    701584 - 10/02/2024
Property Owner Information
 
Name LEWIS OIL CO INC
PO BOX 141286
GAINESVILLE, FL 32614
Effective Date    11/07/2023
 
Contact WENDA LEWIS (MGR)
 
Phone (352) 376-3293
 
Email WLEWIS@LEWISOILCO.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
10 8000 Unleaded Gas (B) 10/01/1995 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(L) Bulk product system
(4) Visual inspect dispenser liners
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
11 8000 Unleaded Gas (B) 10/01/1995 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(L) Bulk product system
(4) Visual inspect dispenser liners
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
12 10000 Vehicular Diesel (D) 11/01/2005 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(D) Unknown
(K) AST containment
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(J) Pressurized piping system
(K) Dispenser liners
(L) Bulk product system
(4) Visual inspect dispenser liners
(K) Monitor dbl wall pipe space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
6 20000 Vehicular Diesel (D) 07/01/1986 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
(P) Level gauges/alarms
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(J) Pressurized piping system
(L) Bulk product system
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
7 550 Kerosene (K) 01/01/1991 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
8 550 Vehicular Diesel (D) 01/01/1991 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
1 6000 Vehicular Diesel (D) 07/01/1964 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(J) Pressurized piping system
(L) Bulk product system
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
2 6000 Kerosene (K) 07/01/1964 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
  (A) Abv, no soil contact
(J) Pressurized piping system
(L) Bulk product system
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
3 4000 Unleaded Gas (B) 07/01/1980 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
4 4000 Unleaded Gas (B) 07/01/1980 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
5 6000 Unleaded Gas (B) 07/01/1980 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
9 550 Vehicular Diesel (D) 01/01/1991 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (I) Not required
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   01/19/2020 01/19/2024 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   01/19/2019 01/19/2024
INSURANCE   01/19/2016 01/19/2019 COMMERCE & INDUSTRY
INSURANCE   01/19/2015 01/19/2016 COMMERCE & INDUSTRY
INSURANCE   01/19/2014 01/19/2015 COMMERCE & INDUSTRY
INSURANCE   01/19/2013 01/19/2014 COMMERCE & INDUSTRY
INSURANCE   01/19/2011 01/19/2012 COMMERCE & INDUSTRY
INSURANCE   01/19/2010 01/19/2011 COMMERCE & INDUSTRY
INSURANCE   01/19/2009 01/19/2010 COMMERCE & INDUSTRY
INSURANCE   08/29/1991 08/29/1996 FPLIPA
INSURANCE   04/26/1991 04/26/1993 FPLIPA
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TIN 12/02/2005 12/06/2005 IN-COMPLIANCE FLOWERS_D 4/0 COMPLIANCE ASSURANCE
 
 Completion Notes INSTALLED NEW HIGHLAND VERTICAL STEEL TANK EQ-573 WITH CAPACITY OF 10,000 GAL. FOR ON ROAD DISEL. REGISTRATION FORM UPDATED AND INSURANCE CARRIER HAS BEEN NOTIFIED OF CHANGES.
 
TXI 12/02/2005 12/06/2005 IN-COMPLIANCE FLOWERS_D 5/0 COMPLIANCE ASSURANCE
 
 Completion Notes REMOVED T#1 AND T#2 BOTH 6,000 GALLON INSTALLED7/01/64. INSURANCE CARRIER WILL NOT COVER IN POLICY AFTER JAN. 19,2006.
 
TCI 08/16/2005 08/17/2005 IN-COMPLIANCE FLOWERS_D 5/0 COMPLIANCE ASSURANCE
 
 Completion Notes BUREAU OF EMERG.RESPONSE CASE #04-11-0243, DIESEL SPILL 9/16/04 HAS BEEN CLOSED-BY MR. KENTON BROWN.
 
DCS 03/01/2005 03/08/2005 DOHANEY_T 0/0 DISCHARGE PROJECT
 
 Completion Notes EMERGENCY RESPONSE SECTION CLOSED CASE BASED ON AAG REPORT DATED 12/24/04.
 
SV 09/20/2004 09/21/2004 FLOWERS_D 5/0 DISCHARGE PROJECT
 
 Completion Notes SOIL REMOVAL FROM SPILL OF DIESEL HAS BEEN COMPLETED. NO PRODUCT WAS SEEN DURING SITE VISIT TODAY. MANIFEST OF REMOVAL WILL BE FORWARDED TO AGENCY.
 
TDI 09/16/2004 09/16/2004 IN-COMPLIANCE FLOWERS_D 5/0 DISCHARGE PROJECT
 
 Completion Notes DISCHARGE BY HUMAN ERROR, PUMP SWITCH WAS NOT TURNED OFF PRIOR TO MAIN BREAKER BEING ACTIVATED. LOSS OF 339 GALLONS OF ON ROAD DISEL FROM OVERHEAD LOADING ARM USED TO FUEL TANKER TRUCKS
 
TCI 08/25/2004 08/27/2004 IN-COMPLIANCE FLOWERS_D 5/0 COMPLIANCE ASSURANCE
 
TCI 08/25/2003 08/26/2003 IN-COMPLIANCE FLOWERS_D 5/0 COMPLIANCE ASSURANCE
 
TCI 08/08/2002 08/08/2002 IN-COMPLIANCE FLOWERS_D 5/0 COMPLIANCE ASSURANCE
 
TCI 08/15/2001 08/17/2001 IN-COMPLIANCE FLOWERS_D 5/0 COMPLIANCE ASSURANCE
 
TCI 08/24/2000 08/25/2000 IN-COMPLIANCE FLOWERS_D 5/0 COMPLIANCE ASSURANCE
 
TCR 01/07/2000 01/18/2000 IN-COMPLIANCE FLOWERS_D 5/0 COMPLIANCE ASSURANCE
 
TCI 08/31/1999 08/31/1999 IN-COMPLIANCE FLOWERS_D 5/0 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 04/22/2024 Satisfied MILLS_MM Enforcement
 
Phone Conversation 01/17/2024 Satisfied MILLS_MM Enforcement
 
Letter 12/21/2023 Satisfied MILLS_MM Enforcement
 
Enforcement Referral 06/13/2023 Accepted HARRINGTON_RD_1 Enforcement
 
Electronic Communication 05/08/2023 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Letter 05/08/2023 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 05/08/2023 Major Out of Compliance HARRINGTON_RD_1 4/0 Routine Compliance
 
Electronic Communication 06/30/2022 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Record Document 06/23/2019 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 01/06/2019 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 12/30/2018 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Meeting 12/30/2018 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Letter 12/30/2018 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 12/28/2018 Major Out of Compliance HARRINGTON_RD_1 4/0 Routine Compliance
 
Phone Conversation 10/27/2015 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 10/27/2015 In Compliance HARRINGTON_RD_1 6/0 Routine Compliance
 
Phone Conversation 09/21/2015 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Emergency Preparedness Information 10/21/2013 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 10/21/2013 In Compliance HARRINGTON_RD_1 6/0 Routine Compliance
 
Record Document 10/07/2011 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Site Inspection 09/22/2011 Minor Out of Compliance HARRINGTON_RD_1 6/0 Routine Compliance
 
Letter 09/22/2011 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Site Inspection 10/19/2010 In Compliance HARRINGTON_RD_1 6/0 Routine Compliance
 
Discharge Reporting 10/30/2009 Satisfied BARNETT_PC_1 Discharge
 
Site Inspection 07/13/2009 In Compliance BARNETT_PC_1 4/0 Discharge
 
Site Inspection 02/19/2009 In Compliance BROWN_JZ 4/0 Routine Compliance
 
Site Inspection 01/24/2008 In Compliance BARNETT_PC_1 4/0 Routine Compliance
 
Emergency Preparedness Information 05/23/2007 Satisfied BARNETT_PC_1 Routine Compliance
 
Emergency Preparedness Information 02/08/2007 Satisfied BARNETT_PC_1 Routine Compliance
 
Emergency Preparedness Information 09/26/2006 Satisfied FLOWERS_D Routine Compliance
 
Site Inspection 08/24/2006 In Compliance FLOWERS_D 4/0 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
05/08/2023 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Provide current hydro tests of the dispenser liners and the concrete fill containment box. (The tests are required every 3 years).
 
12/23/2018 5057 SNC-B 3.5 Pressurized small diameter piping not installed with line leak detectors and meeting requirements. Install line leak detectors on the two underground, small diameter, pressurized piping. Provide test result documentation. test every 12 months. Maintain on file for 3 years.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
06/15/2009   COMPLETED
 
09/16/2004   COMPLETED 50
 
10/21/1991   INACTIVE 56 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE
 
12/20/1988   ACTIVE 56 EARLY DETECTION INCENTIVE-ELIGIBLE