DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Central   Type    Retail Station
 
County Seminole   Status    OPEN
 
ID 8516593   Latitude    28° 39' 6.8856
 
Name CASSELBERRY BP
750 STATE ROAD 436
Longitude    81° 19' 41.05
  CASSELBERRY, FL 32707-5303 LL Method    DPHO
 
Contact NARINDER GOLEN   LL Status    REVIEWED
 
Phone (407) 767-1258   Status Date    07/01/2003
 
Account Owner Information
 
Name NARINDER S GOLEN
750 STATE ROAD 436
CASSELBERRY, FL 32707
Effective Date    06/18/2015
 
Contact
 
Phone (916) 217-3535
 
Email NARINDER_GOLEN@YAHOO.COM
  Placard # / Date    688506 - 06/18/2024
Property Owner Information
 
Name OM PATI LLC
750 STATE ROAD 436
CASSELBERRY, FL 32707-5303
Effective Date    06/18/2015
 
Contact NARINDER GOLEN
 
Phone (407) 767-1258
 
Email
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
4 8000 Unleaded Gas (B) 09/01/1995 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(Z) DEP approved piping
(2) Visual inspect pipe sumps
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
5 8000 Unleaded Gas (B) 09/01/1995 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(Z) DEP approved piping
(2) Visual inspect pipe sumps
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
6 8000 Unleaded Gas (B) 09/01/1995 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
  (F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(Z) DEP approved piping
(2) Visual inspect pipe sumps
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 8000 Unleaded Gas (B) 07/01/1977 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
  (B) Steel/galvanized metal (8) Manually sampled wells
(H) Mechanical line leak detector
(M) Manual tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
2 8000 Unleaded Gas (B) 07/01/1977 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
  (B) Steel/galvanized metal (8) Manually sampled wells
(H) Mechanical line leak detector
(M) Manual tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
3 8000 Unleaded Gas (B) 07/01/1977 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
  (B) Steel/galvanized metal (8) Manually sampled wells
(H) Mechanical line leak detector
(M) Manual tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   06/15/2018 06/15/2019 CRUM & FORSTER SPECIALTY INSURANCE COMPANY
INSURANCE   06/15/2017 06/15/2019 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   05/17/2016 05/17/2017 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   05/17/2016 05/17/2017 CRUM & FORSTER INDEMNITY
INSURANCE   05/17/2015 05/17/2017 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   03/04/2014 03/04/2015 COMMERCE & INDUSTRY
INSURANCE   03/04/2013 03/04/2014 COMMERCE & INDUSTRY
INSURANCE   03/04/2012 03/04/2013 COMMERCE & INDUSTRY
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   09/01/2011 08/31/2014
INSURANCE   09/01/2011 08/31/2014
INSURANCE   06/26/2006 06/26/2011 AMERICAN INTERNATIONAL SPECIALTY LINES
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   06/26/2006 06/26/2011
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 10/07/2005 10/12/2005 IN-COMPLIANCE BAUTISTA 0/3 COMPLIANCE ASSURANCE
 
TCR 11/19/2004 11/19/2004 IN-COMPLIANCE BAUTISTA 0/3 COMPLIANCE ASSURANCE
 
TCI 09/15/2004 09/15/2004 MINOR OUT-OF-COMPLIANCE BAUTISTA 0/3 COMPLIANCE ASSURANCE
 
TCI 09/09/2003 09/09/2003 IN-COMPLIANCE BAUTISTA 0/3 COMPLIANCE ASSURANCE
 
TCI 09/18/2002 09/19/2002 IN-COMPLIANCE BAUTISTA 0/3 COMPLIANCE ASSURANCE
 
TCI 10/23/2001 10/24/2001 IN-COMPLIANCE PERRY 0/3 COMPLIANCE ASSURANCE
 
TCI 10/18/2000 10/19/2000 IN-COMPLIANCE PERRY 0/3 COMPLIANCE ASSURANCE
 
TCI 10/22/1999 10/25/1999 IN-COMPLIANCE PERRY 0/3 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 06/29/2023 Satisfied BOYLES_S Enforcement
 
Enforcement Referral 06/26/2023 Accepted BOYLES_S Enforcement
 
Enforcement Referral 05/24/2023 Cancelled KIDDER_MS_1 Enforcement
 
Site Inspection 05/24/2023 Major Out of Compliance KIDDER_MS_1 0/3 Routine Compliance
 
Electronic Communication 04/07/2023 Satisfied BOYLES_S Enforcement
 
Meeting 04/04/2023 Satisfied BOYLES_S Enforcement
 
Electronic Communication 04/04/2023 Satisfied BOYLES_S Enforcement
 
Phone Conversation 03/28/2023 Satisfied KIDDER_MS_1 Routine Compliance
 
Electronic Communication 03/28/2023 Satisfied KIDDER_MS_1 Routine Compliance
 
Electronic Communication 03/28/2023 Satisfied BOYLES_S Enforcement
 
Electronic Communication 02/01/2023 Satisfied KIDDER_MS_1 Routine Compliance
 
Letter 06/21/2021 Satisfied KIDDER_MS_1 Compliance Assistance
 
Site Inspection 06/16/2021 Minor Out of Compliance KIDDER_MS_1 0/3 Routine Compliance
 
Document Management 03/09/2021 Satisfied RAUENZAHN_RA_1 Closure
 
TCAR 03/09/2021 Satisfied RAUENZAHN_RA_1 Closure
 
Letter 03/09/2021 Satisfied RAUENZAHN_RA_1 Closure
 
Document Management 03/09/2021 Satisfied RAUENZAHN_RA_1 Closure
 
Document Management 01/29/2021 Satisfied BOYLES_S Enforcement
 
Document Management 01/19/2021 Satisfied BOYLES_S Enforcement
 
Phone Conversation 08/31/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 08/28/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 08/24/2020 Satisfied BOYLES_S Enforcement
 
Document Management 08/10/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 07/29/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 07/29/2020 Satisfied BOYLES_S Enforcement
 
Incident 07/21/2020 Has not led to Discharge BOYLES_S Incident
 
Document Management 07/21/2020 Satisfied BOYLES_S Incident
 
Electronic Communication 07/20/2020 Satisfied BOYLES_S Enforcement
 
Document Management 07/17/2020 Satisfied BOYLES_S Incident
 
Electronic Communication 07/17/2020 Satisfied BOYLES_S Enforcement
 
Incident 07/17/2020 Has not led to Discharge BOYLES_S Incident
 
Phone Conversation 07/10/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 07/10/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 07/07/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 07/07/2020 Satisfied BOYLES_S Enforcement
 
Meeting 07/07/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 07/06/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 07/06/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 07/02/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 07/01/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 05/05/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 05/04/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 05/04/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 04/30/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 04/28/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 04/28/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 04/28/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 04/17/2020 Satisfied BOYLES_S Enforcement
 
Incident 04/13/2020 Has not led to Discharge PIERCE_BN_1 Incident
 
Electronic Communication 04/06/2020 Satisfied BOYLES_S Enforcement
 
Meeting 04/06/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/30/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/06/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/06/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/06/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 02/11/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 02/11/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 02/06/2020 Satisfied BOYLES_S Enforcement
 
Phone Conversation 01/13/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 01/02/2020 Satisfied BOYLES_S Enforcement
 
Electronic Communication 12/16/2019 Satisfied BOYLES_S Enforcement
 
Electronic Communication 12/16/2019 Satisfied BOYLES_S Enforcement
 
Phone Conversation 12/06/2019 Satisfied BOYLES_S Enforcement
 
Phone Conversation 12/06/2019 Satisfied BOYLES_S Enforcement
 
Document Management 07/02/2019 Satisfied BOYLES_S Incident
 
Electronic Communication 06/28/2019 Satisfied BOYLES_S Enforcement
 
Electronic Communication 06/25/2019 Satisfied BOYLES_S Enforcement
 
Electronic Communication 06/25/2019 Satisfied BOYLES_S Enforcement
 
Phone Conversation 06/10/2019 Satisfied BOYLES_S Enforcement
 
Electronic Communication 06/10/2019 Satisfied BOYLES_S Enforcement
 
Phone Conversation 05/30/2019 Satisfied BOYLES_S Enforcement
 
Electronic Communication 05/30/2019 Satisfied BOYLES_S Enforcement
 
Phone Conversation 05/07/2019 Satisfied BOYLES_S Enforcement
 
Letter 05/01/2019 Satisfied BOYLES_S Enforcement
 
Electronic Communication 04/18/2019 Satisfied BOYLES_S Enforcement
 
Enforcement Referral 04/16/2019 Accepted RAUENZAHN_RA_1 Enforcement
 
Electronic Communication 04/01/2019 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Issue Document 04/01/2019 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Electronic Communication 03/29/2019 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 03/27/2019 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 03/27/2019 Satisfied PIERCE_BN_1 Compliance Assistance
 
Phone Conversation 03/27/2019 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 02/15/2019 Satisfied PIERCE_BN_1 Compliance Assistance
 
Site Inspection 01/02/2019 Minor Out of Compliance PIERCE_BN_1 0/3 Routine Compliance
 
Letter 01/02/2019 Satisfied PIERCE_BN_1 Compliance Assistance
 
Phone Conversation 12/03/2018 Satisfied PIERCE_BN_1 Routine Compliance
 
Electronic Communication 06/22/2017 Satisfied COTTRELL_SA_1 Compliance Assistance
 
Site Inspection 06/21/2017 Major Out of Compliance COTTRELL_SA_1 0/3 Compliance Assistance
 
Letter 06/21/2017 Satisfied COTTRELL_SA_1 Compliance Assistance
 
Electronic Communication 06/21/2017 Satisfied COTTRELL_SA_1 Compliance Assistance
 
Phone Conversation 06/19/2017 Satisfied COTTRELL_SA_1 Compliance Assistance
 
Phone Conversation 06/19/2017 Satisfied COTTRELL_SA_1 Compliance Assistance
 
Electronic Communication 06/19/2017 Satisfied COTTRELL_SA_1 Compliance Assistance
 
Electronic Communication 06/16/2016 Satisfied BECKER_GT_1 Non-Compliance
 
Letter 06/15/2016 Satisfied BECKER_GT_1 Non-Compliance
 
Site Inspection 06/15/2016 Major Out of Compliance BECKER_GT_1 0/3 Routine Compliance
 
Site Inspection 12/12/2014 In Compliance COTTRELL_SA_1 0/3 Non-Compliance
 
Electronic Communication 12/12/2014 Satisfied COTTRELL_SA_1 Non-Compliance
 
Site Inspection 11/03/2014 Minor Out of Compliance COTTRELL_SA_1 0/3 Routine Compliance
 
Emergency Preparedness Information 11/03/2014 Satisfied COTTRELL_SA_1 Routine Compliance
 
Letter 11/03/2014 Satisfied COTTRELL_SA_1 Non-Compliance
 
Electronic Communication 11/03/2014 Satisfied COTTRELL_SA_1 Routine Compliance
 
Electronic Communication 12/13/2013 Satisfied COTTRELL_SA_1 Non-Compliance
 
Site Inspection 12/13/2013 In Compliance COTTRELL_SA_1 0/3 Non-Compliance
 
Site Inspection 09/05/2013 Minor Out of Compliance COTTRELL_SA_1 0/3 Routine Compliance
 
Electronic Communication 09/05/2013 Satisfied COTTRELL_SA_1 Routine Compliance
 
Electronic Communication 09/05/2013 Satisfied COTTRELL_SA_1 Non-Compliance
 
Letter 09/05/2013 Satisfied COTTRELL_SA_1 Non-Compliance
 
Emergency Preparedness Information 09/03/2013 Satisfied COTTRELL_SA_1 Routine Compliance
 
Site Inspection 10/20/2011 In Compliance BAUTISTA_E_1 0/3 Non-Compliance
 
Letter 10/13/2011 Satisfied BAUTISTA_E_1 Non-Compliance
 
Site Inspection 10/13/2011 Minor Out of Compliance BAUTISTA_E_1 0/3 Routine Compliance
 
Emergency Preparedness Information 10/12/2011 Satisfied BAUTISTA_E_1 Routine Compliance
 
Site Inspection 11/01/2010 In Compliance BAUTISTA_E_1 0/3 Non-Compliance
 
Site Inspection 10/19/2010 Minor Out of Compliance BAUTISTA_E_1 0/3 Routine Compliance
 
Emergency Preparedness Information 10/19/2010 Satisfied BAUTISTA_E_1 Routine Compliance
 
Letter 10/19/2010 Satisfied BAUTISTA_E_1 Non-Compliance
 
Site Inspection 11/02/2009 In Compliance BAUTISTA_E_1 0/3 Non-Compliance
 
Site Inspection 10/27/2009 Minor Out of Compliance BAUTISTA_E_1 0/3 Routine Compliance
 
Site Inspection 10/15/2008 In Compliance BAUTISTA_E_1 0/3 Routine Compliance
 
Site Inspection 10/04/2007 In Compliance BAUTISTA_E_1 0/3 Routine Compliance
 
Emergency Preparedness Information 02/06/2007 Satisfied BAUTISTA_E_1 Routine Compliance
 
Site Inspection 11/02/2006 In Compliance BAUTISTA_E_1 0/0 Non-Compliance
 
Letter 10/27/2006 Satisfied PERRY_JF Non-Compliance
 
Site Inspection 10/24/2006 Minor Out of Compliance BAUTISTA_E_1 0/3 Routine Compliance
 
Emergency Preparedness Information 09/20/2006 Satisfied BAUTISTA_E_1 Routine Compliance
 
Emergency Preparedness Information 09/20/2006 Satisfied BAUTISTA_E_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
05/23/2023 6002 Minor 2.1 Operator Training records not available. Please make operator training certificates available for review. If training has not been completed please visit the link provided in order to do so. https://floridadep.gov/waste/permitting-compliance-assistance/content/underground-storage-tank-operator-training
 
05/18/2023 6074 Minor 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. All records, whether in paper or electronic format, shall be dated and available for inspection by the Department or county. If records are not kept at the facility, they shall be made available at the facility or another agreed upon location upon five business days of receipt of the Department’s or county’s request.
 
05/18/2023 6012 SNC-A 2.9 No financial responsibility instrument or expired instrument for > 180 days. Financial responsibility shall be maintained and demonstrated to the county or Department for all storage tank systems until the storage tank systems are properly closed. Provide Part D (COI), and Part P (CFR) storage tank insurance documents dating back to 06/15/2019.
 
05/16/2023 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Please provide monthly visual inspection records for review. If visual inspections are not being recorded please begin doing so. The RUL 2 interstitial space needs to undergo manual monitoring until the sensor can be repaired.
 
05/15/2023 6062 Minor 2.5 Release detection devices not tested annually. Have a contractor perform operability testing on all release detection devices.
 
05/15/2023 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have a contractor perform the required integrity testing as soon as possible.
 
05/11/2023 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Please hire a petroleum contractor to make the necessary repairs to the following tank components. 1) RUL tank 2 interstitial alarm 2) RUL 2 STP head 3) RUL 2 single walled spill bucket (will likely need to be replaced).
 
05/10/2023 6014 SNC-B 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. An investigation will need to be initiated in order to determine whether or not a discharge has occurred within certain containments areas (RUL 1 STP Sump, RUL 2 STP Sump, PUL STP Sump, RUL 1 DW Spill Bucket). Integrity testing will need to be completed for all impacted containments. If integrity testing does not pass, containments will need to be replaced/repaired, and sampling will need to take place.
 
05/10/2023 6009 Minor 4.1 Incident Notification Form (INF) not received in a timely manner. Please submit an INF to the OCEPD for the liquid discovered within these containments. It will need to be determined whether or not a discharge has occurred. An INF is required to be submitted within 72 hours of the discovery of any excess amount of liquid within containment areas.
 
05/10/2023 6001 Minor 2.1 No reasonable access provided. The facility owner or operator shall provide an authorized facility representative to unlock and open any covers, manways, and release detection equipment associated with the storage tank system or system component and demonstrate operational functionality of electronic equipment.
 
03/02/2021 4015 Minor 2.10 Incomplete documentation demonstrating financial responsibility. Facility owners shall ensure that copies of the current financial responsibility document(s) are available for inspection at the facility where the storage tank system(s) is located or at their place of business.
 
02/24/2021 4068 Minor 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. Spill bucket should be replaced with a new double walled containment. Have your contractor asses the situation as soon as possible.
 
02/23/2021 4076 Minor 4.11 Failure to conduct required periodic containment and interstitial integrity testing. Single walled spill buckets are required to be tested once every 12 months. Have a contractor perform an integrity test for RUL #2 spill bucket.
 
02/23/2021 4057 Minor 4.31 Overfill protection devices not registered or tested annually. Have a contractor perform overfill protection testing as soon as possible.
 
02/22/2021 4077 Minor 4.12 Spill containment, sumps, and interstices not accessible. Water/regulated substances not timely removed. Petroleum contact water not properly managed. Have a contractor remove water from the two STP sumps as soon as possible.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
05/11/1991   COMPLETED