Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||
Cover Page Report | |||||||
Report Run Date: 05/17/2025 Last Data Refresh: 05/16/2025 Report Generated from DOPPLER | |||||||
District | Northeast | Type | Retail Station | ||||
County | Alachua | Status | OPEN | ||||
ID | 8518129 | Latitude | 29° 47' 32.6904 | ||||
Name |
CHEVRON-ALACHUA 13725 MARTIN LUTHER KING JR BLVD |
Longitude | 82° 29' 31.1497 | ||||
ALACHUA, FL 32615-9742 | LL Method | DPHO | |||||
Contact | WENDA LEWIS | LL Status | REVIEWED | ||||
Phone | (352) 376-3293 | Status Date | 06/18/2009 | ||||
Account Owner Information | |||||||
Name | LEWIS OIL CO INC PO BOX 141286 GAINESVILLE, FL 32614 |
Effective Date | 05/20/1994 | ||||
Contact | WENDA LEWIS (MGR) | ||||||
Phone | (352) 376-3293 | ||||||
WLEWIS@LEWISOILCO.COM | |||||||
Placard # / Date | 701586 - 10/02/2024 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 8000 | Unleaded Gas (B) | 03/01/1987 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
2 | 10000 | Unleaded Gas (B) | 03/01/1987 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
3 | 8000 | Unleaded Gas (B) | 03/01/1987 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
4 | 10000 | Vehicular Diesel (D) | 03/01/1987 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
6 | 4000 | Unleaded Gas (B) | 07/01/1981 | UNDERGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass |
(D) External protective coating | (8) Manually sampled wells | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
7 | 4000 | Leaded Gas (A) | 07/01/1981 | UNDERGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass |
(D) External protective coating | (8) Manually sampled wells | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
8 | 4000 | Leaded Gas (A) | 07/01/1981 | UNDERGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass |
(D) External protective coating | (8) Manually sampled wells | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
9 | 4000 | Unleaded Gas (B) | 07/01/1981 | UNDERGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass |
(D) External protective coating | (8) Manually sampled wells | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
5 | 2000 | Vehicular Diesel (D) | UNDERGROUND | Removed from Site (B) | |||
Constructions | Pipings | Monitorings | |||||
(C) Steel | (D) External protective coating | (Y) Unknown | |||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
INSURANCE | 05/14/2024 | 05/14/2025 | SCOTTSDALE INSURANCE COMPANY | ||||
INSURANCE | 05/14/2023 | 05/14/2024 | SCOTTSDALE INSURANCE COMPANY | ||||
INSURANCE | 05/14/2022 | 05/14/2023 | SCOTTSDALE INSURANCE COMPANY | ||||
INSURANCE | 05/14/2021 | 05/14/2022 | SCOTTSDALE INSURANCE COMPANY | ||||
INSURANCE | 05/14/2020 | 05/14/2021 | SCOTTSDALE INSURANCE COMPANY | ||||
INSURANCE | 05/14/2019 | 05/14/2020 | ILLINOIS UNION INSURANCE COMPANY | ||||
INSURANCE | 05/14/2018 | 05/14/2019 | ACE | ||||
INSURANCE | 05/14/2017 | 05/14/2018 | ACE | ||||
INSURANCE | 05/14/2016 | 05/14/2017 | ACE AMER INS CO | ||||
INSURANCE | 01/31/2015 | 01/31/2016 | AIG | ||||
INSURANCE | 01/31/2015 | 05/14/2016 | AIG SPECIALTY INSURANCE COMPANY | ||||
INSURANCE | 01/31/2014 | 01/31/2015 | AIG | ||||
INSURANCE | 01/31/2013 | 01/31/2014 | CHARTIS SPECIALTY INSURANCE CO | ||||
INSURANCE | 01/31/2012 | 01/31/2013 | CHARTIS SPECIALTY INSURANCE CO | ||||
INSURANCE | 01/31/2011 | 01/31/2012 | CHARTIS SPECIALTY INSURANCE CO | ||||
INSURANCE | 01/31/2010 | 01/31/2011 | CHARTIS SPECIALTY INSURANCE CO | ||||
INSURANCE | 01/31/2009 | 01/31/2010 | AMERICAN INTERNATIONAL SPECIALTY LINES | ||||
Legacy Compliance Activity Information | |||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |
TCI | 04/25/2005 | 04/26/2005 | IN-COMPLIANCE | OWENS_JS | 0/4 | COMPLIANCE ASSURANCE | |
Completion Notes MLLD TEST 4/16/05, ANNUAL OPERABILITY TEST 4/25/05 | |||||||
RRBD | 03/04/2004 | 03/04/2004 | RAMSEY_T | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes RECEIVED WORK RECEIPT FOR INSTALL OF DROP TUBES | |||||||
TCI | 02/13/2004 | 02/16/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | OWENS_JS | 0/4 | COMPLIANCE ASSURANCE | |
Completion Notes LLD TEST 4/15/03, ANNUAL OPERABILITY TEST 2/13/04 | |||||||
TCI | 02/28/2003 | 03/03/2003 | IN-COMPLIANCE | OWENS_JS | 0/4 | COMPLIANCE ASSURANCE | |
Completion Notes OPERABILITY TEST 2/28/03 | |||||||
TCI | 03/22/2002 | 03/25/2002 | IN-COMPLIANCE | CHANDLER_R | 0/4 | COMPLIANCE ASSURANCE | |
Completion Notes COMPLIANCE INSPECTION, ANNUAL OPERATIONS TEST 4/17/01 | |||||||
TCI | 04/12/2001 | 04/18/2001 | IN-COMPLIANCE | CHANDLER_R | 0/4 | COMPLIANCE ASSURANCE | |
Completion Notes COMPLIANCE INSPECTION | |||||||
TCR | 07/03/2000 | 07/12/2000 | IN-COMPLIANCE | DC | 0/4 | COMPLIANCE ASSURANCE | |
Completion Notes COMPLIANCE REINSPECTION | |||||||
TCI | 05/23/2000 | 05/24/2000 | MINOR OUT-OF-COMPLIANCE | DC | 0/4 | COMPLIANCE ASSURANCE | |
Completion Notes COMPLIANCE INSPECTION | |||||||
TDI | 08/30/1999 | 09/23/1999 | IN-COMPLIANCE | CHANDLER_D | 0/4 | DISCHARGE PROJECT | |
TCI | 06/14/1999 | 07/13/1999 | MINOR OUT-OF-COMPLIANCE | CHANDLER_D | 0/4 | COMPLIANCE ASSURANCE | |
TIN | 05/24/1999 | 06/02/1999 | IN-COMPLIANCE | CHANDLER_D | 0/4 | COMPLIANCE ASSURANCE | |
TXI | 04/13/1999 | 06/02/1999 | IN-COMPLIANCE | CHANDLER_D | 0/4 | COMPLIANCE ASSURANCE | |
TCI | 03/03/1999 | 03/16/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | CHANDLER_D | 0/4 | COMPLIANCE ASSURANCE | |
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Enforcement Tracking | 02/25/2025 | Closed Without Enforcement | MACK_BT | Enforcement | |||
Letter | 08/28/2024 | Satisfied | MCNEIL_A | Enforcement | |||
Enforcement Referral | 07/29/2024 | Accepted | ZIMMERMAN_RA_2 | Enforcement | |||
Letter | 07/29/2024 | Satisfied | ZIMMERMAN_RA_2 | Compliance Assistance | |||
Electronic Communication | 07/29/2024 | Satisfied | ZIMMERMAN_RA_2 | Compliance Assistance | |||
Site Inspection | 07/29/2024 | Major Out of Compliance | ZIMMERMAN_RA_2 | 0/4 | Routine Compliance | ||
Electronic Communication | 06/27/2024 | Satisfied | ZIMMERMAN_RA_2 | Compliance Assistance | |||
Enforcement Referral | 08/17/2023 | Accepted | KEIM_MJ_1 | Enforcement | |||
Letter | 01/31/2023 | Satisfied | KEIM_MJ_1 | Compliance Assistance | |||
Site Inspection | 01/31/2023 | Major Out of Compliance | KEIM_MJ_1 | 0/4 | Routine Compliance | ||
Electronic Communication | 01/30/2023 | Satisfied | KEIM_MJ_1 | Routine Compliance | |||
Electronic Communication | 01/30/2023 | Satisfied | KEIM_MJ_1 | Routine Compliance | |||
Electronic Communication | 06/09/2022 | Satisfied | ZIMMERMAN_RA_2 | Compliance Assistance | |||
Letter | 03/26/2021 | Satisfied | ZIMMERMAN_RA_2 | Compliance Assistance | |||
Site Inspection | 03/26/2021 | Minor Out of Compliance | ZIMMERMAN_RA_2 | 0/4 | Routine Compliance | ||
Electronic Communication | 03/26/2021 | Satisfied | ZIMMERMAN_RA_2 | Compliance Assistance | |||
Phone Conversation | 03/05/2021 | Satisfied | ZIMMERMAN_RA_2 | Compliance Assistance | |||
Electronic Communication | 04/30/2019 | Satisfied | KEIM_MJ_1 | Routine Compliance | |||
Site Inspection | 04/30/2019 | Minor Out of Compliance | KEIM_MJ_1 | 0/4 | Routine Compliance | ||
Letter | 04/30/2019 | Satisfied | KEIM_MJ_1 | Compliance Assistance | |||
Phone Conversation | 04/30/2019 | Satisfied | KEIM_MJ_1 | Routine Compliance | |||
Enforcement Referral | 03/13/2018 | Accepted | HARRIS_MJ | Enforcement | |||
Enforcement Tracking | 03/13/2018 | Closed Without Enforcement | HARRIS_MJ | Enforcement | |||
Enforcement Tracking | 03/13/2018 | Closed Without Enforcement | HARRIS_MJ | Enforcement | |||
Letter | 03/13/2018 | Satisfied | OLIVA_L | Enforcement | |||
Enforcement Referral | 12/13/2017 | Accepted | ZIMMERMAN_RA_2 | Enforcement | |||
Electronic Communication | 12/29/2016 | Satisfied | ZIMMERMAN_RA_2 | Routine Compliance | |||
Site Inspection | 12/28/2016 | Minor Out of Compliance | ZIMMERMAN_RA_2 | 0/4 | Routine Compliance | ||
Letter | 12/28/2016 | Satisfied | ZIMMERMAN_RA_2 | Non-Compliance | |||
Phone Conversation | 11/28/2016 | Satisfied | ZIMMERMAN_RA_2 | Routine Compliance | |||
Site Inspection | 03/30/2015 | Minor Out of Compliance | HARRINGTON_RD_1 | 0/4 | Routine Compliance | ||
Record Document | 03/30/2015 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||
Emergency Preparedness Information | 03/30/2015 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||
Electronic Communication | 03/30/2015 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||
Record Document | 04/17/2014 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||
Record Document | 03/25/2014 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||
Letter | 03/21/2014 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||
Emergency Preparedness Information | 11/06/2013 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||
Letter | 11/06/2013 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||
Site Inspection | 11/06/2013 | Minor Out of Compliance | HARRINGTON_RD_1 | 0/4 | Routine Compliance | ||
Electronic Communication | 11/06/2013 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||
Site Inspection | 10/31/2011 | In Compliance | OWENS_JS_1 | 0/4 | Routine Compliance | ||
Emergency Preparedness Information | 09/22/2011 | Satisfied | OWENS_JS_1 | Routine Compliance | |||
Site Inspection | 05/19/2010 | In Compliance | OWENS_JS_1 | 0/4 | Routine Compliance | ||
Site Inspection | 04/02/2009 | In Compliance | OWENS_JS_1 | 0/4 | Routine Compliance | ||
Emergency Preparedness Information | 04/02/2009 | Satisfied | OWENS_JS_1 | Routine Compliance | |||
Emergency Preparedness Information | 04/28/2008 | Satisfied | OWENS_JS_1 | Routine Compliance | |||
Site Inspection | 04/24/2008 | In Compliance | OWENS_JS_1 | 0/4 | Routine Compliance | ||
Emergency Preparedness Information | 05/23/2007 | Satisfied | OWENS_JS_1 | Routine Compliance | |||
Emergency Preparedness Information | 05/21/2007 | Satisfied | OWENS_JS_1 | Routine Compliance | |||
Site Inspection | 03/19/2007 | In Compliance | OWENS_JS_1 | 0/4 | Routine Compliance | ||
Emergency Preparedness Information | 02/07/2007 | Satisfied | OWENS_JS_1 | Routine Compliance | |||
Emergency Preparedness Information | 09/20/2006 | Satisfied | OWENS_JS_1 | Routine Compliance | |||
Site Inspection | 04/26/2006 | In Compliance | OWENS_JS_1 | 0/3 | Routine Compliance | ||
Open Areas of Concern | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
07/30/2024 | 6003 | 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Please complete and submit the Storage Tank Registration Form on paper or electronic format to tankregistration@floridadep.gov to reflect updated contact and facility information. | ||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
07/29/2024 | 7064 | Minor | 3.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Email monthly electronic release detection records from July 2022 to July 2027 to DEP-NED. | |||
07/29/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Have all of the facilities line leak detectors operability tested and certified; email passing test certification to DEP-NED. | |||
07/29/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Have all of the facilities single wall spill buckets containment integrity evaluation tested and certified; email passing test certification to DEP-NED. | |||
07/29/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Have all of the facilities under dispenser containments and STP sumps containment integrity evaluation tested and certified; email passing test certification to DEP-NED. | |||
07/29/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Remove corrosion from the premium and regular STP sump pump heads, electrical conduit and product pipe fittings, repaint or reseal pump head, electrical conduit and pipe fittings with protective coating in the STP sump to help prevent future corrosion; email proof of violation resolution to DEP-NED – work order and pictures after corrosion removal. | |||
07/29/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Have the release detection system operability tested and certified; email passing test certification to DEP-NED. | |||
07/29/2024 | 7064 | Minor | 3.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Email monthly visual inspections from July 2022 to July 2027 to DEP-NED. | |||
07/29/2024 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Have all of the UST system overfill protection devices operability tested and certified; email passing test certification to DEP-NED. | |||
01/30/2023 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Have the corrosion treated and the components protected then forward the documentation to the inspector to address this violation. | |||
01/30/2023 | 6052 | SNC-B | 4.6 Overfill that shuts off/restricts flow or triggers alarm not provided. | Install or verify overfill prevention devices for all of the tanks and forward the documentation to the inspector to address this violation. | |||
01/30/2023 | 6046 | Minor | 4.14 Dispensers not installed and maintained according to standards. | Have the dispensers anchored, re-piped (shear valves) tested and protected by installing bollards or u-style large diameter piping around the dispenser islands. | |||
03/26/2021 | 4068 | Minor | 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. | Investigate and test to ensure proper system function; If there is drawdown of the brine fluid, isolate each tank and test individually; email passing operability test and submit filled out incident notification form to ACEPD. | |||
Discharge Information | |||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||
08/30/1997 | COMPLETED | 31 | PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE | ||||