DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/10/2025        Last Data Refresh: 05/09/2025        Report Generated from DOPPLER
 
District Northeast   Type    Retail Station
 
County Clay   Status    OPEN
 
ID 8519274   Latitude    29° 58' 53.7026
 
Name STRICKLANDS ONE STOP MART
6023A KINGSLEY LAKE DR
Longitude    81° 59' 47.8026
  STARKE, FL 32091-9728 LL Method    DGPS
 
Contact SANDRA HILCHEY   LL Status    REVIEWED
 
Phone (904) 210-2502   Status Date    11/04/2003
 
Account Owner Information
 
Name HILCO DEVELOPMENT LLC
2965 S DEER AVE
MIDDLEBURG, FL 32068-6422
Effective Date    09/17/2019
 
Contact SANDRA HILCHEY
 
Phone (904) 210-2502
 
Email OHILCHEY@GMAIL.COM
  Placard # / Date    569784 - 09/17/2019
Property Owner Information
 
Name HILCO DEVELOPMENT LLC
2965 S DEER AVE
MIDDLEBURG, FL 32068-6422
Effective Date    07/13/2019
 
Contact SANDRA HILCHEY
 
Phone (904) 210-2502
 
Email OHILCHEY@GMAIL.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
10 3000 Vehicular Diesel (D) 05/01/1996 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
7 3000 Unleaded Gas (B) 05/01/1996 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
8 3000 Unleaded Gas (B) 05/01/1996 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
9 3000 Unleaded Gas (B) 05/01/1996 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
(O) Tight fill
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(G) Electronic line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 4000 Leaded Gas (A) 05/01/1980 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
2 4000 Leaded Gas (A) 05/01/1980 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
3 4000 Unleaded Gas (B) 05/01/1980 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
4 4000 Unleaded Gas (B) 05/01/1980 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
5 3000 Unleaded Gas (B) 05/01/1980 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
6 2000 Vehicular Diesel (D) 05/01/1980 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (Y) Unknown
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE  
INSURANCE   10/01/2019 10/01/2020 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   07/13/2019 10/01/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   07/13/2018 07/13/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   07/13/2017 07/13/2018 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   07/13/2016 07/13/2017 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   07/13/2015 07/13/2016 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   07/13/2014 07/13/2015 COMMERCE & INDUSTRY
INSURANCE   07/01/2014 07/01/2015 COMMERCE & INDUSTRY
INSURANCE   07/13/2013 07/13/2014 COMMERCE & INDUSTRY
INSURANCE   07/13/2012 07/13/2013 COMMERCE & INDUSTRY
INSURANCE   07/13/2010 07/13/2011 COMMERCE & INDUSTRY
INSURANCE   07/13/2009 07/13/2010 COMMERCE & INDUSTRY
INSURANCE   07/13/2005 07/13/2006 COMMERCE & INDUSTRY
INSURANCE   06/15/1990 06/15/1992 FPLIPA
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
RRBD 09/27/2005 09/27/2005 COMPLIANCE ASSURANCE
 
RRBD 09/09/2005 09/09/2005 COMPLIANCE ASSURANCE
 
TCI 05/16/2005 06/03/2005 SIGNIFICANT OUT-OF-COMPLIANCE BARNETT_P 0/4 COMPLIANCE ASSURANCE
 
TIN 05/11/2005 06/03/2005 IN-COMPLIANCE BARNETT_P 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes INSTALLATION OF NEW PIPING, DISPENSERS, SUMPS
 
TXI 05/04/2005 06/03/2005 IN-COMPLIANCE BARNETT_P 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes APPROVED CONTRACTOR CLOSING PIPING, DISPENSERS, AND SUMP
 
TPI 04/06/2005 06/03/2005 SIGNIFICANT OUT-OF-COMPLIANCE BARNETT_P 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes UNLICENSED CONTRACTOR DOING CLOSURE WORK
 
RRBD 05/17/2004 05/18/2004 BARNETT_P 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED COPY OF PAYMENT TO DEP FOR PLACARDS FOR 2003-2004 AND 2004/2005
 
TCI 04/28/2004 05/11/2004 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/4 COMPLIANCE ASSURANCE
 
RRBD 06/26/2003 07/18/2003 COMPLIANCE ASSURANCE
 
TCI 04/29/2003 05/06/2003 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes LD TEST 6/7/02 3/3 PASS
 
RRBD 03/13/2003 06/18/2003 BARNETT_P 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes WORK SHOULD BE COMPLETED BY END OF THIS WEEK
 
TCI 05/01/2002 05/06/2002 IN-COMPLIANCE BARNETT_P 0/4 COMPLIANCE ASSURANCE
 
PDNE 09/20/2001 09/20/2001 DOHANEY_T 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes VIOLATION WAS CLOSED BECAUSE IT WAS RECORDED IN ERROR FOR THIS FACILITY.
 
RRBD 07/18/2001 07/18/2001 COMPLIANCE ASSURANCE
 
TCI 05/16/2001 06/05/2001 SIGNIFICANT OUT-OF-COMPLIANCE BARNETT_P 0/4 COMPLIANCE ASSURANCE
 
TCI 05/11/2000 05/22/2000 MINOR OUT-OF-COMPLIANCE BARNETT-P 0/4 COMPLIANCE ASSURANCE
 
TCI 06/25/1999 06/25/1999 MINOR OUT-OF-COMPLIANCE BARNETT_P 0/4 COMPLIANCE ASSURANCE
 
PDNE 03/29/1999 03/29/1999 BARNETT_P 0/0 COMPLIANCE ASSURANCE
 
UTCI 04/17/1998 04/17/1998 MINOR OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 05/05/2025 Satisfied JACKSON_SM Enforcement
 
Electronic Communication 05/05/2025 Satisfied JACKSON_SM Enforcement
 
Enforcement Referral 05/05/2025 Accepted HARRINGTON_RD_1 Enforcement
 
Phone Conversation 05/05/2025 Satisfied JACKSON_SM Enforcement
 
Electronic Communication 05/05/2025 Satisfied JACKSON_SM Enforcement
 
Enforcement Tracking 05/05/2025 Closed Without Enforcement JACKSON_SM Enforcement
 
Meeting 05/05/2025 Satisfied JACKSON_SM Enforcement
 
Meeting 05/05/2025 Satisfied JACKSON_SM Enforcement
 
Electronic Communication 05/05/2025 Satisfied JACKSON_SM Enforcement
 
Electronic Communication 05/05/2025 Satisfied JACKSON_SM Enforcement
 
Phone Conversation 05/05/2025 Satisfied JACKSON_SM Enforcement
 
Electronic Communication 05/02/2025 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Electronic Communication 05/02/2025 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Letter 05/02/2025 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 04/27/2025 Major Out of Compliance HARRINGTON_RD_1 0/4 Routine Compliance
 
Letter 01/16/2025 Satisfied JACKSON_SM Enforcement
 
Enforcement Referral 05/03/2024 Accepted HARRINGTON_RD_1 Enforcement
 
Electronic Communication 10/25/2022 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 06/13/2022 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Letter 06/13/2022 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 06/09/2022 Major Out of Compliance HARRINGTON_RD_1 0/4 Routine Compliance
 
Electronic Communication 06/09/2022 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Letter 03/07/2021 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Record Document 01/13/2021 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Letter 06/12/2020 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 06/12/2020 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Electronic Communication 06/12/2020 Satisfied HARRINGTON_RD_1 Routine Compliance
 
Site Inspection 06/01/2020 Minor Out of Compliance HARRINGTON_RD_1 0/4 Routine Compliance
 
Enforcement Tracking 10/23/2019 Closed With Enforcement BRADSHAW_B Enforcement
 
Letter 10/23/2019 Satisfied BRADSHAW_B Enforcement
 
Document Management 10/23/2019 Satisfied BRADSHAW_B Enforcement
 
Incident 10/16/2019 Has not led to Discharge BRADSHAW_B Incident
 
Document Management 10/16/2019 Satisfied BRADSHAW_B Incident
 
Letter 06/12/2019 Satisfied BRADSHAW_B Enforcement
 
Enforcement Referral 06/15/2018 Accepted HARRIS_MJ Enforcement
 
Enforcement Referral 01/08/2018 Accepted HARRINGTON_RD_1 Enforcement
 
Letter 06/30/2017 Satisfied HARRINGTON_RD_1 Compliance Assistance
 
Site Inspection 06/20/2017 Minor Out of Compliance HARRINGTON_RD_1 0/4 Routine Compliance
 
Site Inspection 02/09/2015 In Compliance HARRINGTON_RD_1 0/4 Non-Compliance
 
Electronic Communication 01/02/2015 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Issue Document 12/31/2014 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Letter 10/08/2014 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Enforcement Tracking 07/07/2014 Closed Without Enforcement DEFALCO_L Enforcement
 
Letter 06/11/2014 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Site Inspection 06/11/2014 Minor Out of Compliance HARRINGTON_RD_1 0/4 Routine Compliance
 
Electronic Communication 12/23/2013 Satisfied DEFALCO_L Non-Compliance
 
Electronic Communication 07/29/2013 Satisfied DEFALCO_L Non-Compliance
 
Enforcement Referral 07/16/2013 Accepted DEFALCO_L Enforcement
 
Letter 04/26/2013 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Record Document 12/07/2012 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Emergency Preparedness Information 11/29/2012 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Letter 11/29/2012 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Site Inspection 11/29/2012 Minor Out of Compliance HARRINGTON_RD_1 0/4 Routine Compliance
 
Record Document 08/29/2011 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Letter 08/29/2011 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Record Document 04/29/2011 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Letter 04/13/2011 Satisfied BARNETT_PC_1 Non-Compliance
 
Site Inspection 04/13/2011 Minor Out of Compliance BARNETT_PC_1 0/4 Routine Compliance
 
Record Document 03/04/2010 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Record Document 03/04/2010 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Record Document 02/15/2010 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Record Document 02/15/2010 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Record Document 02/15/2010 Satisfied HARRINGTON_RD_1 Non-Compliance
 
Letter 01/27/2010 Minor Out of Compliance BARNETT_PC_1 Non-Compliance
 
Letter 01/27/2010 Minor Out of Compliance BARNETT_PC_1 Non-Compliance
 
Site Inspection 12/22/2009 Minor Out of Compliance BARNETT_PC_1 0/4 Routine Compliance
 
Record Document 03/21/2008 Satisfied BARNETT_PC_1 Non-Compliance
 
Letter 01/29/2008 Satisfied BARNETT_PC_1 Non-Compliance
 
Site Inspection 01/29/2008 Minor Out of Compliance BARNETT_PC_1 0/4 Routine Compliance
 
Emergency Preparedness Information 02/09/2007 Satisfied BARNETT_PC_1 Routine Compliance
 
Emergency Preparedness Information 09/22/2006 Satisfied BARNETT_PC_1 Routine Compliance
 
Record Document 08/31/2006 Satisfied BARNETT_PC_1 Non-Compliance
 
Letter 08/31/2006 Satisfied BARNETT_PC_1 Non-Compliance
 
Record Document 08/30/2006 Satisfied BARNETT_PC_1 Non-Compliance
 
Site Inspection 06/16/2006 Minor Out of Compliance BARNETT_PC_1 0/4 Routine Compliance
 
Letter 06/16/2006 Satisfied BARNETT_PC_1 Non-Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
04/27/2025 6012 SNC-A 2.9 No financial responsibility instrument or expired instrument for > 180 days. Provide verification of Financial Responsibility and facility-completed CFR Form. The CFR Form will be sent to the facility with this report for completion.
 
04/27/2025 6001 Minor 2.1 No reasonable access provided. Contact Alachua County EPD inspector for re-inspection.
 
06/09/2022 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Provide current spill bucket Integrity Test results.
 
06/09/2022 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. Provide verification that monthly inspections are being completed as required for In Service USTs.
 
06/09/2022 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove water from the tank interstice. Provide verification.
 
06/09/2022 6011 SNC-B 2.8 No financial responsibility instrument or expired instrument for < 180 days. Provide verification of Financial Responsibility and facility-completed CFR Form. The CFR Form will be sent to the facility with this report for cmpletion.
 
06/09/2022 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Provide overfill prevention test results.
 
06/09/2022 6062 Minor 2.5 Release detection devices not tested annually. Provide current overfill prevention test results.
 
06/09/2022 6038 SNC-B 4.9 Shear valve not installed properly. Replace the missing shear valve anchor bolt so the shear valve is properly anchored. The valve needs to be able to function properly in the event of vehicle impact to the dispenser.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
06/04/1996   INACTIVE 46 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE