Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/10/2025 Last Data Refresh: 05/09/2025 Report Generated from DOPPLER | |||||||||||
District | Northeast | Type | Retail Station | ||||||||
County | Clay | Status | OPEN | ||||||||
ID | 8519274 | Latitude | 29° 58' 53.7026 | ||||||||
Name |
STRICKLANDS ONE STOP MART 6023A KINGSLEY LAKE DR |
Longitude | 81° 59' 47.8026 | ||||||||
STARKE, FL 32091-9728 | LL Method | DGPS | |||||||||
Contact | SANDRA HILCHEY | LL Status | REVIEWED | ||||||||
Phone | (904) 210-2502 | Status Date | 11/04/2003 | ||||||||
Account Owner Information | |||||||||||
Name | HILCO DEVELOPMENT LLC 2965 S DEER AVE MIDDLEBURG, FL 32068-6422 |
Effective Date | 09/17/2019 | ||||||||
Contact | SANDRA HILCHEY | ||||||||||
Phone | (904) 210-2502 | ||||||||||
OHILCHEY@GMAIL.COM | |||||||||||
Placard # / Date | 569784 - 09/17/2019 | ||||||||||
Property Owner Information | |||||||||||
Name | HILCO DEVELOPMENT LLC 2965 S DEER AVE MIDDLEBURG, FL 32068-6422 |
Effective Date | 07/13/2019 | ||||||||
Contact | SANDRA HILCHEY | ||||||||||
Phone | (904) 210-2502 | ||||||||||
OHILCHEY@GMAIL.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
10 | 3000 | Vehicular Diesel (D) | 05/01/1996 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (G) Electronic line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 3000 | Unleaded Gas (B) | 05/01/1996 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (G) Electronic line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
8 | 3000 | Unleaded Gas (B) | 05/01/1996 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (G) Electronic line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
9 | 3000 | Unleaded Gas (B) | 05/01/1996 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (G) Electronic line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 4000 | Leaded Gas (A) | 05/01/1980 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 4000 | Leaded Gas (A) | 05/01/1980 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 4000 | Unleaded Gas (B) | 05/01/1980 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 4000 | Unleaded Gas (B) | 05/01/1980 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 3000 | Unleaded Gas (B) | 05/01/1980 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 2000 | Vehicular Diesel (D) | 05/01/1980 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (Y) Unknown | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | |||||||||||
INSURANCE | 10/01/2019 | 10/01/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 07/13/2019 | 10/01/2019 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 07/13/2018 | 07/13/2019 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 07/13/2017 | 07/13/2018 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 07/13/2016 | 07/13/2017 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 07/13/2015 | 07/13/2016 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 07/13/2014 | 07/13/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/01/2014 | 07/01/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/13/2013 | 07/13/2014 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/13/2012 | 07/13/2013 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/13/2010 | 07/13/2011 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/13/2009 | 07/13/2010 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 07/13/2005 | 07/13/2006 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 06/15/1990 | 06/15/1992 | FPLIPA | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
RRBD | 09/27/2005 | 09/27/2005 | COMPLIANCE ASSURANCE | ||||||||
RRBD | 09/09/2005 | 09/09/2005 | COMPLIANCE ASSURANCE | ||||||||
TCI | 05/16/2005 | 06/03/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | BARNETT_P | 0/4 | COMPLIANCE ASSURANCE | |||||
TIN | 05/11/2005 | 06/03/2005 | IN-COMPLIANCE | BARNETT_P | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes INSTALLATION OF NEW PIPING, DISPENSERS, SUMPS | |||||||||||
TXI | 05/04/2005 | 06/03/2005 | IN-COMPLIANCE | BARNETT_P | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes APPROVED CONTRACTOR CLOSING PIPING, DISPENSERS, AND SUMP | |||||||||||
TPI | 04/06/2005 | 06/03/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | BARNETT_P | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes UNLICENSED CONTRACTOR DOING CLOSURE WORK | |||||||||||
RRBD | 05/17/2004 | 05/18/2004 | BARNETT_P | 0/4 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED COPY OF PAYMENT TO DEP FOR PLACARDS FOR 2003-2004 AND 2004/2005 | |||||||||||
TCI | 04/28/2004 | 05/11/2004 | MINOR OUT-OF-COMPLIANCE | BARNETT_P | 0/4 | COMPLIANCE ASSURANCE | |||||
RRBD | 06/26/2003 | 07/18/2003 | COMPLIANCE ASSURANCE | ||||||||
TCI | 04/29/2003 | 05/06/2003 | MINOR OUT-OF-COMPLIANCE | BARNETT_P | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes LD TEST 6/7/02 3/3 PASS | |||||||||||
RRBD | 03/13/2003 | 06/18/2003 | BARNETT_P | 0/4 | COMPLIANCE ASSURANCE | ||||||
Completion Notes WORK SHOULD BE COMPLETED BY END OF THIS WEEK | |||||||||||
TCI | 05/01/2002 | 05/06/2002 | IN-COMPLIANCE | BARNETT_P | 0/4 | COMPLIANCE ASSURANCE | |||||
PDNE | 09/20/2001 | 09/20/2001 | DOHANEY_T | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes VIOLATION WAS CLOSED BECAUSE IT WAS RECORDED IN ERROR FOR THIS FACILITY. | |||||||||||
RRBD | 07/18/2001 | 07/18/2001 | COMPLIANCE ASSURANCE | ||||||||
TCI | 05/16/2001 | 06/05/2001 | SIGNIFICANT OUT-OF-COMPLIANCE | BARNETT_P | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 05/11/2000 | 05/22/2000 | MINOR OUT-OF-COMPLIANCE | BARNETT-P | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 06/25/1999 | 06/25/1999 | MINOR OUT-OF-COMPLIANCE | BARNETT_P | 0/4 | COMPLIANCE ASSURANCE | |||||
PDNE | 03/29/1999 | 03/29/1999 | BARNETT_P | 0/0 | COMPLIANCE ASSURANCE | ||||||
UTCI | 04/17/1998 | 04/17/1998 | MINOR OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 05/05/2025 | Satisfied | JACKSON_SM | Enforcement | |||||||
Electronic Communication | 05/05/2025 | Satisfied | JACKSON_SM | Enforcement | |||||||
Enforcement Referral | 05/05/2025 | Accepted | HARRINGTON_RD_1 | Enforcement | |||||||
Phone Conversation | 05/05/2025 | Satisfied | JACKSON_SM | Enforcement | |||||||
Electronic Communication | 05/05/2025 | Satisfied | JACKSON_SM | Enforcement | |||||||
Enforcement Tracking | 05/05/2025 | Closed Without Enforcement | JACKSON_SM | Enforcement | |||||||
Meeting | 05/05/2025 | Satisfied | JACKSON_SM | Enforcement | |||||||
Meeting | 05/05/2025 | Satisfied | JACKSON_SM | Enforcement | |||||||
Electronic Communication | 05/05/2025 | Satisfied | JACKSON_SM | Enforcement | |||||||
Electronic Communication | 05/05/2025 | Satisfied | JACKSON_SM | Enforcement | |||||||
Phone Conversation | 05/05/2025 | Satisfied | JACKSON_SM | Enforcement | |||||||
Electronic Communication | 05/02/2025 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||||||
Electronic Communication | 05/02/2025 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||||||
Letter | 05/02/2025 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||||||
Site Inspection | 04/27/2025 | Major Out of Compliance | HARRINGTON_RD_1 | 0/4 | Routine Compliance | ||||||
Letter | 01/16/2025 | Satisfied | JACKSON_SM | Enforcement | |||||||
Enforcement Referral | 05/03/2024 | Accepted | HARRINGTON_RD_1 | Enforcement | |||||||
Electronic Communication | 10/25/2022 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||||||
Electronic Communication | 06/13/2022 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||||||
Letter | 06/13/2022 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||||||
Site Inspection | 06/09/2022 | Major Out of Compliance | HARRINGTON_RD_1 | 0/4 | Routine Compliance | ||||||
Electronic Communication | 06/09/2022 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||||||
Letter | 03/07/2021 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||||||
Record Document | 01/13/2021 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||||||
Letter | 06/12/2020 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||||||
Electronic Communication | 06/12/2020 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||||||
Electronic Communication | 06/12/2020 | Satisfied | HARRINGTON_RD_1 | Routine Compliance | |||||||
Site Inspection | 06/01/2020 | Minor Out of Compliance | HARRINGTON_RD_1 | 0/4 | Routine Compliance | ||||||
Enforcement Tracking | 10/23/2019 | Closed With Enforcement | BRADSHAW_B | Enforcement | |||||||
Letter | 10/23/2019 | Satisfied | BRADSHAW_B | Enforcement | |||||||
Document Management | 10/23/2019 | Satisfied | BRADSHAW_B | Enforcement | |||||||
Incident | 10/16/2019 | Has not led to Discharge | BRADSHAW_B | Incident | |||||||
Document Management | 10/16/2019 | Satisfied | BRADSHAW_B | Incident | |||||||
Letter | 06/12/2019 | Satisfied | BRADSHAW_B | Enforcement | |||||||
Enforcement Referral | 06/15/2018 | Accepted | HARRIS_MJ | Enforcement | |||||||
Enforcement Referral | 01/08/2018 | Accepted | HARRINGTON_RD_1 | Enforcement | |||||||
Letter | 06/30/2017 | Satisfied | HARRINGTON_RD_1 | Compliance Assistance | |||||||
Site Inspection | 06/20/2017 | Minor Out of Compliance | HARRINGTON_RD_1 | 0/4 | Routine Compliance | ||||||
Site Inspection | 02/09/2015 | In Compliance | HARRINGTON_RD_1 | 0/4 | Non-Compliance | ||||||
Electronic Communication | 01/02/2015 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Issue Document | 12/31/2014 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Letter | 10/08/2014 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Enforcement Tracking | 07/07/2014 | Closed Without Enforcement | DEFALCO_L | Enforcement | |||||||
Letter | 06/11/2014 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Site Inspection | 06/11/2014 | Minor Out of Compliance | HARRINGTON_RD_1 | 0/4 | Routine Compliance | ||||||
Electronic Communication | 12/23/2013 | Satisfied | DEFALCO_L | Non-Compliance | |||||||
Electronic Communication | 07/29/2013 | Satisfied | DEFALCO_L | Non-Compliance | |||||||
Enforcement Referral | 07/16/2013 | Accepted | DEFALCO_L | Enforcement | |||||||
Letter | 04/26/2013 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Record Document | 12/07/2012 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 11/29/2012 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Letter | 11/29/2012 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Site Inspection | 11/29/2012 | Minor Out of Compliance | HARRINGTON_RD_1 | 0/4 | Routine Compliance | ||||||
Record Document | 08/29/2011 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Letter | 08/29/2011 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Record Document | 04/29/2011 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Letter | 04/13/2011 | Satisfied | BARNETT_PC_1 | Non-Compliance | |||||||
Site Inspection | 04/13/2011 | Minor Out of Compliance | BARNETT_PC_1 | 0/4 | Routine Compliance | ||||||
Record Document | 03/04/2010 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Record Document | 03/04/2010 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Record Document | 02/15/2010 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Record Document | 02/15/2010 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Record Document | 02/15/2010 | Satisfied | HARRINGTON_RD_1 | Non-Compliance | |||||||
Letter | 01/27/2010 | Minor Out of Compliance | BARNETT_PC_1 | Non-Compliance | |||||||
Letter | 01/27/2010 | Minor Out of Compliance | BARNETT_PC_1 | Non-Compliance | |||||||
Site Inspection | 12/22/2009 | Minor Out of Compliance | BARNETT_PC_1 | 0/4 | Routine Compliance | ||||||
Record Document | 03/21/2008 | Satisfied | BARNETT_PC_1 | Non-Compliance | |||||||
Letter | 01/29/2008 | Satisfied | BARNETT_PC_1 | Non-Compliance | |||||||
Site Inspection | 01/29/2008 | Minor Out of Compliance | BARNETT_PC_1 | 0/4 | Routine Compliance | ||||||
Emergency Preparedness Information | 02/09/2007 | Satisfied | BARNETT_PC_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/22/2006 | Satisfied | BARNETT_PC_1 | Routine Compliance | |||||||
Record Document | 08/31/2006 | Satisfied | BARNETT_PC_1 | Non-Compliance | |||||||
Letter | 08/31/2006 | Satisfied | BARNETT_PC_1 | Non-Compliance | |||||||
Record Document | 08/30/2006 | Satisfied | BARNETT_PC_1 | Non-Compliance | |||||||
Site Inspection | 06/16/2006 | Minor Out of Compliance | BARNETT_PC_1 | 0/4 | Routine Compliance | ||||||
Letter | 06/16/2006 | Satisfied | BARNETT_PC_1 | Non-Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
04/27/2025 | 6012 | SNC-A | 2.9 No financial responsibility instrument or expired instrument for > 180 days. | Provide verification of Financial Responsibility and facility-completed CFR Form. The CFR Form will be sent to the facility with this report for completion. | |||||||
04/27/2025 | 6001 | Minor | 2.1 No reasonable access provided. | Contact Alachua County EPD inspector for re-inspection. | |||||||
06/09/2022 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Provide current spill bucket Integrity Test results. | |||||||
06/09/2022 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Provide verification that monthly inspections are being completed as required for In Service USTs. | |||||||
06/09/2022 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Remove water from the tank interstice. Provide verification. | |||||||
06/09/2022 | 6011 | SNC-B | 2.8 No financial responsibility instrument or expired instrument for < 180 days. | Provide verification of Financial Responsibility and facility-completed CFR Form. The CFR Form will be sent to the facility with this report for cmpletion. | |||||||
06/09/2022 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Provide overfill prevention test results. | |||||||
06/09/2022 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Provide current overfill prevention test results. | |||||||
06/09/2022 | 6038 | SNC-B | 4.9 Shear valve not installed properly. | Replace the missing shear valve anchor bolt so the shear valve is properly anchored. The valve needs to be able to function properly in the event of vehicle impact to the dispenser. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
06/04/1996 | INACTIVE | 46 | PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE | ||||||||