Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | South | Type | Retail Station | ||||||||
County | Lee | Status | OPEN | ||||||||
ID | 8519482 | Latitude | 26° 40' 27.1733 | ||||||||
Name |
GAS & GOODIES-GOLD COAST PETRO INC 14490 N CLEVELAND AVE |
Longitude | 81° 53' 43.8613 | ||||||||
NORTH FORT MYERS, FL 33903 | LL Method | DPHO | |||||||||
Contact | MUNAF RASHID | LL Status | REVIEWED | ||||||||
Phone | (813) 334-0151 | Status Date | 10/03/2003 | ||||||||
Account Owner Information | |||||||||||
Name | EDISON PETROLEUM INC 8673 LITTLETON RD NORTH FORT MYERS, FL 33903 |
Effective Date | 07/02/2002 | ||||||||
Contact | MUNAF RASHID | ||||||||||
Phone | (239) 656-1072 | ||||||||||
SHORTCUT8673@GMAIL.COM | |||||||||||
Placard # / Date | 697110 - 06/28/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | EDISON PETROLEUM INC 8673 LITTLETON RD NORTH FORT MYERS, FL 33903 |
Effective Date | 07/02/2002 | ||||||||
Contact | MUNAF RASHID | ||||||||||
Phone | (239) 656-1072 | ||||||||||
SHORTCUT8673@GMAIL.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 6000 | Unleaded Gas (B) | 05/01/1993 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
8 | 4000 | Vehicular Diesel (D) | 05/01/1993 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 4000 | Unleaded Gas (B) | 05/01/1970 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(B) Internal lining | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 4000 | Vehicular Diesel (D) | 05/01/1970 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(B) Internal lining | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 3000 | Unleaded Gas (B) | 05/01/1970 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(B) Internal lining | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 3000 | Unleaded Gas (B) | 05/01/1970 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel |
(B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 4000 | Unleaded Gas (B) | 05/01/1970 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(B) Internal lining | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 4000 | Unleaded Gas (B) | 05/01/1993 | UNDERGROUND | Out of Service (T) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
9 | 300 | Kerosene (K) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (X) None | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 10/08/2023 | 10/08/2024 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 10/08/2021 | 10/08/2022 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 10/08/2020 | 10/08/2021 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 03/04/2017 | 03/04/2018 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 03/04/2016 | 03/04/2017 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 03/04/2015 | 03/04/2016 | CRUM & FORSTER SPECIALTY INS. CO. | ||||||||
INSURANCE | 03/04/2014 | 03/04/2015 | CRUM & FORSTER INDEMNITY | ||||||||
INSURANCE | 03/04/2013 | 03/04/2014 | AMERICAN SAFETY | ||||||||
INSURANCE | 03/04/2011 | 03/04/2012 | ACE | ||||||||
INSURANCE | 02/09/2010 | 02/09/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 11/20/1991 | 07/20/2009 | ZURICH-AMERICAN | ||||||||
INSURANCE | 10/06/1989 | 11/06/1991 | FPLIPA | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
NCLI | 11/02/2005 | 11/02/2005 | S. JOHNSON | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 10/31/2005 | 11/02/2005 | MINOR OUT-OF-COMPLIANCE | S. JOHNSON | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PIPING - DW FIBERGLASS RD - MONTHLY VISUALS 8/1/2005 - LLD TESTED/PASSED - UST ENV. STUCK INTERSTIAL SPACES OF TANKS-UNLEADED 3/4 WATER, NO FUEL. DIESEL 3/4 WATER, NO FUEL. PREMIUM 1/2 WATER, 1/4 FUEL. PREMIUM TANK HAS BEEN TESTED AND PASSED. FUEL LEVEL | |||||||||||
TCR | 01/28/2005 | 01/28/2005 | IN-COMPLIANCE | S JOHNSON | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes CHAR. MOINT. HAS CONTINUED TO MONITOR THE SUPER INTERSTITIAL SPACE. DIPS SPACE MONTHLY TO REMOVE WATER/PRODUCT. PASSED TANK TEST 8/20/04. SPACE MAY HAVE BEEN FILLED IN ERROR. INTIALLY 6 GALLONS WAS REMOVED. LEVEL OF LIQUID HAS STAY CONSISTANT. | |||||||||||
TCI | 10/07/2004 | 10/08/2004 | IN-COMPLIANCE | S JOHNSON/J SAIYA | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PIPING- DW FIBERGLASS RDRL- MONTHLY VISUALS FACILITY HAS APPROXIMATELY 1/4INCH PRODUCT/WATER IN INTERSTITIAL SPACE. FACILITY CONDUCTED TIGHTNESS TEST, PASSED. TO CONTINUE TO REMOVE PRODUCT/WATER AND MONITOR SPACE. IF PRODUCT/WATER RETURNS SUBMIT INF. | |||||||||||
RRBD | 02/19/2004 | 02/20/2004 | IN-COMPLIANCE | S. JOHNSON | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 12/09/2003 | 12/09/2003 | MINOR OUT-OF-COMPLIANCE | S. JOHNSON | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PIPING - DW FIBERGLASS RDRL - MONTHLY VISUALS AND MANUALLY STICKING OF INTERSTITIAL SPACE OF DW TANK. NOTE: , 1" WATER IN ALL THREE SPACES. SMALL AMOUNT OF PRODUCT IN SUPER SPACE. APPEARS THAT PRIMARY AND SECONDARY TANK SHARE SAME VENT LINES. | |||||||||||
TCI | 12/11/2002 | 02/11/2003 | MINOR OUT-OF-COMPLIANCE | DEMACK,P | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes REMOVE WATER FROM PIPING SUMPS AND DIESEL DISPENSER LINER. | |||||||||||
TCI | 11/30/2001 | 12/03/2001 | IN-COMPLIANCE | DEMACK | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 10/30/2000 | 11/02/2000 | IN-COMPLIANCE | HOENE | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes LEAK DETECTOR TEST DUE. | |||||||||||
TCI | 10/06/1999 | 10/07/1999 | MINOR OUT-OF-COMPLIANCE | HOENE | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes WATER IN SUMPS NEEDS REMOVED. | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Referral | 11/12/2024 | Accepted | PARKS_J_4 | Enforcement | |||||||
Letter | 10/16/2024 | Satisfied | PARKS_J_4 | Compliance Assistance | |||||||
Electronic Communication | 10/16/2024 | Satisfied | PARKS_J_4 | Routine Compliance | |||||||
Site Inspection | 10/16/2024 | Major Out of Compliance | PARKS_J_4 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 09/11/2024 | Satisfied | PARKS_J_4 | Routine Compliance | |||||||
Letter | 11/10/2022 | Satisfied | KLEINMANN_K_1 | Compliance Assistance | |||||||
Site Inspection | 11/07/2022 | Major Out of Compliance | KLEINMANN_K_1 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 09/08/2022 | Satisfied | KLEINMANN_K_1 | Routine Compliance | |||||||
Letter | 07/01/2021 | Satisfied | KLEINMANN_K_1 | Compliance Assistance | |||||||
Site Inspection | 10/13/2020 | Major Out of Compliance | KLEINMANN_K_1 | 0/3 | Routine Compliance | ||||||
Electronic Communication | 09/29/2020 | Satisfied | KLEINMANN_K_1 | Routine Compliance | |||||||
Letter | 02/13/2018 | Satisfied | ZIMMERMAN_CA_1 | Routine Compliance | |||||||
Site Inspection | 02/13/2018 | In Compliance | ZIMMERMAN_CA_1 | 0/3 | Routine Compliance | ||||||
Record Document | 01/29/2016 | Satisfied | HERNANDEZ_N | Enforcement | |||||||
Enforcement Tracking | 01/29/2016 | Closed With Enforcement | HERNANDEZ_N | Enforcement | |||||||
Site Inspection | 12/22/2015 | In Compliance | ZIMMERMAN_CA_1 | 0/3 | Routine Compliance | ||||||
Site Inspection | 01/29/2014 | In Compliance | ZIMMERMAN_CA_1 | 0/3 | Non-Compliance | ||||||
Letter | 10/30/2013 | Satisfied | ZIMMERMAN_CA_1 | Non-Compliance | |||||||
Site Inspection | 10/30/2013 | Minor Out of Compliance | ZIMMERMAN_CA_1 | 0/3 | Routine Compliance | ||||||
Issue Document | 09/25/2012 | Satisfied | CERQUERA_L | Enforcement | |||||||
Issue Document | 09/10/2012 | Satisfied | CERQUERA_L | Enforcement | |||||||
Issue Document | 09/10/2012 | Satisfied | CERQUERA_L | Enforcement | |||||||
Phone Conversation | 08/01/2012 | Satisfied | CERQUERA_L | Enforcement | |||||||
Record Document | 07/27/2012 | Satisfied | CERQUERA_L | Enforcement | |||||||
Phone Conversation | 07/24/2012 | Satisfied | CERQUERA_L | Enforcement | |||||||
Electronic Communication | 07/10/2012 | Satisfied | CERQUERA_L | Enforcement | |||||||
Electronic Communication | 07/10/2012 | Satisfied | CERQUERA_L | Enforcement | |||||||
Electronic Communication | 07/10/2012 | Satisfied | CERQUERA_L | Enforcement | |||||||
Electronic Communication | 06/11/2012 | Satisfied | CERQUERA_L | Enforcement | |||||||
Issue Document | 05/22/2012 | Satisfied | CERQUERA_L | Enforcement | |||||||
Electronic Communication | 05/22/2012 | Satisfied | CERQUERA_L | Enforcement | |||||||
Site Inspection | 01/13/2012 | In Compliance | JOHNSON_SG_1 | 0/3 | Non-Compliance | ||||||
Site Inspection | 09/30/2011 | Major Out of Compliance | JOHNSON_SG_1 | 0/3 | Routine Compliance | ||||||
Letter | 09/30/2011 | Satisfied | JOHNSON_SG_1 | Non-Compliance | |||||||
Site Inspection | 04/21/2011 | Major Out of Compliance | JOHNSON_SG_1 | 0/3 | Non-Compliance | ||||||
Letter | 11/24/2010 | Satisfied | JOHNSON_SG_1 | Closure | |||||||
Record Document | 11/24/2010 | Satisfied | JOHNSON_SG_1 | Closure | |||||||
Letter | 11/15/2010 | Satisfied | JOHNSON_SG_1 | Discharge | |||||||
Document Management | 11/15/2010 | Complete | JOHNSON_SG_1 | Discharge | |||||||
Discharge Reporting | 11/15/2010 | Satisfied | JOHNSON_SG_1 | Discharge | |||||||
Incident | 10/29/2010 | Has not led to Discharge | JOHNSON_SG_1 | Incident | |||||||
Site Inspection | 10/22/2010 | Major Out of Compliance | JOHNSON_SG_1 | 0/3 | Closure | ||||||
Site Inspection | 10/22/2010 | Major Out of Compliance | JOHNSON_SG_1 | 0/3 | Installation | ||||||
Document Management | 10/15/2010 | Complete | JOHNSON_SG_1 | Incident | |||||||
Letter | 09/13/2010 | Satisfied | JOHNSON_SG_1 | Non-Compliance | |||||||
Site Inspection | 09/13/2010 | Major Out of Compliance | JOHNSON_SG_1 | 0/3 | Routine Compliance | ||||||
Letter | 09/13/2010 | Satisfied | JOHNSON_SG_1 | Non-Compliance | |||||||
Letter | 07/13/2010 | Satisfied | JOHNSON_SG_1 | Non-Compliance | |||||||
Site Inspection | 07/13/2010 | Major Out of Compliance | JOHNSON_SG_1 | 0/3 | Non-Compliance | ||||||
Enforcement Referral | 11/23/2009 | Accepted | MURPHY_EM | Enforcement | |||||||
Site Inspection | 11/13/2009 | Major Out of Compliance | JOHNSON_SG_1 | 0/3 | Routine Compliance | ||||||
Letter | 11/13/2009 | Satisfied | JOHNSON_SG_1 | Non-Compliance | |||||||
Issue Document | 02/20/2009 | Satisfied | JOHNSON_SG_1 | Non-Compliance | |||||||
Site Inspection | 02/13/2009 | Minor Out of Compliance | JOHNSON_SG_1 | 0/3 | Non-Compliance | ||||||
Site Inspection | 11/13/2008 | Minor Out of Compliance | JOHNSON_SG_1 | 0/3 | Routine Compliance | ||||||
Letter | 11/13/2008 | Satisfied | JOHNSON_SG_1 | Non-Compliance | |||||||
Site Inspection | 11/07/2007 | In Compliance | JOHNSON_SG_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 02/05/2007 | Satisfied | ZIMMERMAN_CA_1 | Routine Compliance | |||||||
Site Inspection | 10/25/2006 | In Compliance | JOHNSON_SG_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 09/20/2006 | Satisfied | JOHNSON_SG_1 | Routine Compliance | |||||||
Site Inspection | 07/28/2006 | In Compliance | RUPP_SS | 0/3 | Non-Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
10/16/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Begin conducting all required annual testing and make the records available for department review. | |||||||
10/16/2024 | 6015 | Minor | 4.3 Incident investigation not completed within 14 days, and/or no DRF or written confirmation received at the end of the 14-day investigation period. | The inspection conducted on 9/14/2022 indicated that the RUL STP sump had over 5 inches of product on top of the PCW in the sump. No INF has been received. | |||||||
10/16/2024 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Begin conducting monthly visual inspections and make the records of the inspection available for department review. | |||||||
10/16/2024 | 6075 | Minor | 2.9 Records of current training certificates for designated Class A, B, and C operators shall be maintained for as long as the operators are designated for that facility not kept. | No records of Class A,B or C were made available. Provide training to all staff and provide their records for department review. | |||||||
10/16/2024 | 6002 | Minor | 2.1 Operator Training records not available. | All staff must receive the required training and certificates of training completion must be made available for department review. | |||||||
10/16/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Schedule and conduct all required testing and make the records available for department review. | |||||||
11/07/2022 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | At least once a month, but not exceeding 35 days, every component of a storage tank system that contains, transfers, or stores, or is designed to contain, transfer, or store regulated substances that can be inspected visually shall be visually inspected and documented as to its condition pursuant to Rule 62-761.710, F.A.C. Any visual inspection of a storage tank system that reveals uncontrolled pitting corrosion, structural damage, leakage, or other similar problems is considered a positive response. The positive response shall be recorded as part of the release detection records. Repairs shall be made in accordance with Rule 62-761.700, F.A.C. The positive response shall be reported and investigated as an incident pursuant to Rule 62-761.430, F.A.C., if it is determined that a release has occurred. A monthly visual inspection is not required for any system component using an electronic release detection method; however, piping and dispenser sumps that use an electronic release detection method must also be visually inspected every six months and records kept of the visual inspection. | |||||||
11/07/2022 | 6024 | Minor | 2.2 Integrity test not performed on storage tank, integral piping, single-walled spill containment system, double-walled spill containment system, or doubled-walled sump prior to placing into service. | An interstitial integrity test shall be performed on the storage tank after it is delivered and installed at the facility and before the storage tank is placed into service. This test shall be performed in accordance with manufacturer’s requirements. For storage tanks without manufacturer’s interstitial integrity testing specifications, PEI/RP100-17, 2017 Edition shall be used. PEI/RP100-17 Recommended Practices for Installation of Underground Liquid Storage Systems, PEI/RP100-17, 2017 Edition; and PEI/RP1200-17, 2017 Edition. | |||||||
11/07/2022 | 6043 | Minor | 4.13 Fillbox covers not marked according to requirements. | Fillbox covers, regardless of the date of installation of the storage tank system, shall be marked or the fill connection tagged and facility signage shall be prominently displayed in accordance with the following documents hereby adopted and incorporated by reference: Using the API Color-Symbol System to Mark Equipment and Vehicles for Product Identification at Gasoline Dispensing Facilities and Distribution Terminals, API Recommended Practice 1637, (R2012), 3rd Edition, July 2006 or Identification Markings for Dedicated Aviation Fuel Manufacturing and Distribution Facilities, Airport Storage and Mobile Fuelling Equipment, EI 1542, 9th Edition, July 2012; or with an equivalent method approved by the Department in accordance with subsection 62-761.850(1), F.A.C. | |||||||
11/07/2022 | 6077 | Minor | 4.8 Out of service storage tank systems not tested annually for operability or interstice and liquid level not monitored annually. | Facility owners and operators of out-of-service storage tank systems shall monitor the interstice and the liquid level in the storage tank annually but not to exceed 12 months, unless the tank system contains no regulated substances. Records of these inspections shall be maintained in accordance with subsection 62-761.710(2), F.A.C. In the event that liquid in excess of one inch, or 0.3 percent by weight, in the storage tank or any liquid, other than condensate, in the interstice is discovered, facility owners and operators must follow the procedures for incidents pursuant to Rule 62-761.430, F.A.C | |||||||
10/28/2022 | 6009 | Minor | 4.1 Incident Notification Form (INF) not received in a timely manner. | Notification of the discovery of an incident shall be made to the county in writing or electronic format on Form 62-761.900(6), Incident Notification Form (INF), effective date, January 2017, hereby adopted and incorporated by reference, within 72 hours of the discovery or before the close of the County’s next business day; | |||||||
09/21/2022 | 6002 | Minor | 2.1 Operator Training records not available. | During hours of operation, facilities must have at least one certified operator (either a Class A, Class B, or Class C operator) present at the facility. 9/2020 - No operator certification for on site staff. 9/2022 - No certified operator present at the facility during hours of operation. | |||||||
09/21/2022 | 6014 | SNC-B | 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. | If an incident occurs at a facility, actions shall be taken within 24 hours of discovery to investigate the incident to determine if a discharge has occurred. | |||||||
09/14/2022 | 6074 | Minor | 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. | Replace with: This facility is being referred to FDEP for Enforcement. Corrective actions to be determine by FDEP. | |||||||
09/14/2022 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Schedule, perform current and future all required annual inspections for the facility. | |||||||
10/13/2020 | 4059 | SNC-B | 4.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days.) For electronically monitored sumps, visual inspections not conducted every 6 months. This violation may lead to Placard Revocation and Delivery Prohibition. | Perform and record monthly visual inspections | |||||||
09/29/2020 | 4081 | Minor | 2.9 Records of current training certificates for designated Class A, B, and C operators shall be maintained for as long as the operators are designated for that facility not kept. | Keep certificates on site. | |||||||
09/29/2020 | 4001 | Minor | 2.2 Operator certification requirements not met. | Obtain certifications for each staff. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
11/02/2010 | INACTIVE | 55 | Sego, John R. | 8137446100 | |||||||
07/02/1986 | COMPLETED | 51 | EARLY DETECTION INCENTIVE-ELIGIBLE | ||||||||