Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||
Cover Page Report | |||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||
District | Southwest | Type | Local Government | ||||
County | Hernando | Status | OPEN | ||||
ID | 8520259 | Latitude | 28° 31' 46.5585 | ||||
Name |
SPRINGBROOK HOSPITAL 7007 GROVE RD |
Longitude | 82° 29' 3.3942 | ||||
BROOKSVILLE, FL 34609-8610 | LL Method | DPHO | |||||
Contact | MICHAEL PARKER | LL Status | REVIEWED | ||||
Phone | (352) 596-4306 | Status Date | 11/12/2003 | ||||
Account Owner Information | |||||||
Name | SPRINGBROOK HOSPITAL INC 7007 GROVE RD BROOKSVILLE, FL 34609 |
Effective Date | 07/17/2000 | ||||
Contact | MICHAEL PARKER | ||||||
Phone | (352) 596-4306 | ||||||
Placard # / Date | 699312 - 07/10/2024 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
2 | 1000 | Emerg Generator Diesel (G) | 12/01/2008 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(A) Abv, no soil contact (B) Steel/galvanized metal (I) Suction piping system |
(F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 1000 | Vehicular Diesel (D) | 07/01/1985 | UNDERGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(E) Fiberglass (M) Spill containment bucket (O) Tight fill |
(I) Suction piping system (M) Double wall - pipe jacket (N) Approved synthetic material |
(I) Not required | |||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
INSURANCE | 12/19/2018 | 12/19/2019 | ACE | ||||
INSURANCE | 12/19/2017 | 12/19/2018 | ACE | ||||
INSURANCE | 12/19/2016 | 12/19/2017 | ACE | ||||
INSURANCE | 12/19/2015 | 12/19/2016 | ACE | ||||
INSURANCE | 12/19/2014 | 12/19/2015 | ACE | ||||
INSURANCE | 12/19/2013 | 12/19/2014 | ILLINOIS UNION | ||||
INSURANCE | 12/19/2012 | 12/19/2013 | ILLINOIS UNION | ||||
INSURANCE | 12/19/2011 | 12/19/2012 | ILLINOIS UNION | ||||
INSURANCE | 12/19/2010 | 12/19/2011 | ILLINOIS UNION | ||||
INSURANCE | 12/19/2009 | 12/19/2010 | ILLINOIS UNION | ||||
INSURANCE | 12/19/2008 | 12/19/2009 | ILLINOIS UNION | ||||
INSURANCE | 12/09/2008 | 12/19/2009 | ILLINOIS UNION | ||||
Legacy Compliance Activity Information | |||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |
TCI | 12/20/2005 | 12/27/2005 | IN-COMPLIANCE | HARMAN_G | 1/0 | COMPLIANCE ASSURANCE | |
TCI | 11/02/2004 | 11/02/2004 | IN-COMPLIANCE | SUMNER_C | 0/1 | COMPLIANCE ASSURANCE | |
RRBD | 09/08/2004 | 09/09/2004 | MOLLI_SA | 0/1 | COMPLIANCE ASSURANCE | ||
CWOE | 09/08/2004 | 09/09/2004 | MOLLI_SA | 0/1 | COMPLIANCE ASSURANCE | ||
TCR | 04/06/2004 | 04/06/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | SUMNER_C | 0/1 | COMPLIANCE ASSURANCE | |
Completion Notes COPPER PIPING IN A BLUE OPW CHASE | |||||||
NCLI | 11/05/2003 | 11/12/2003 | SUMNER_C | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 11/05/2003 | 11/12/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | SUMNER_C | 0/1 | COMPLIANCE ASSURANCE | |
Completion Notes COPPER PIPING IN A BLUE OPW CHASE FROM TANK TO THE DAY TANK. | |||||||
TCI | 08/08/2002 | 09/14/2002 | IN-COMPLIANCE | MONROE_P | 0/1 | COMPLIANCE ASSURANCE | |
TCI | 10/04/2001 | 11/16/2001 | IN-COMPLIANCE | MONROE_P | 0/1 | COMPLIANCE ASSURANCE | |
TCI | 03/07/2001 | 04/24/2001 | IN-COMPLIANCE | MONROE_P | 0/1 | COMPLIANCE ASSURANCE | |
RRBD | 01/12/2001 | 03/12/2001 | MONROE_P | 0/1 | COMPLIANCE ASSURANCE | ||
TCR | 05/11/2000 | 05/24/2000 | SIGNIFICANT OUT-OF-COMPLIANCE | MONROE_P | 0/1 | COMPLIANCE ASSURANCE | |
TCI | 09/28/1999 | 10/15/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | MONROE | 0/1 | COMPLIANCE ASSURANCE | |
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Site Inspection | 11/16/2023 | Major Out of Compliance | LEE_MC_1 | 1/0 | Routine Compliance | ||
Letter | 10/20/2022 | Satisfied | GREEN_SM | Enforcement | |||
Enforcement Referral | 10/05/2022 | Accepted | MULLIGAN_PC_1 | Enforcement | |||
Record Document | 09/15/2022 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||
Record Document | 09/14/2022 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||
Electronic Communication | 09/14/2022 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||
Phone Conversation | 09/14/2022 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||
Record Document | 03/02/2022 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||
Phone Conversation | 07/12/2021 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||
Letter | 04/22/2021 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||
Site Inspection | 04/22/2021 | Major Out of Compliance | MULLIGAN_PC_1 | 1/0 | Routine Compliance | ||
Electronic Communication | 04/22/2021 | Satisfied | MULLIGAN_PC_1 | Routine Compliance | |||
Record Document | 05/21/2019 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||
Letter | 05/21/2019 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||
Electronic Communication | 03/28/2019 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||
Record Document | 03/25/2019 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||
Record Document | 02/25/2019 | Satisfied | MULLIGAN_PC_1 | Compliance Assistance | |||
Letter | 02/19/2019 | Satisfied | LEE_MC_1 | Compliance Assistance | |||
Site Inspection | 02/19/2019 | Major Out of Compliance | LEE_MC_1 | 1/0 | Routine Compliance | ||
Record Document | 11/28/2017 | Satisfied | HECKMAN_DA_1 | Routine Compliance | |||
Electronic Communication | 04/19/2017 | Satisfied | ANTON_TM_1 | Non-Compliance | |||
Letter | 03/27/2017 | Satisfied | ANTON_TM_1 | Non-Compliance | |||
Electronic Communication | 02/27/2017 | Satisfied | ANTON_TM_1 | Non-Compliance | |||
Electronic Communication | 02/27/2017 | Satisfied | ANTON_TM_1 | Routine Compliance | |||
Site Inspection | 02/22/2017 | Major Out of Compliance | ANTON_TM_1 | 1/0 | Routine Compliance | ||
Letter | 02/22/2017 | Satisfied | ANTON_TM_1 | Non-Compliance | |||
Site Inspection | 09/29/2014 | In Compliance | HECKMAN_DA_1 | 1/0 | Routine Compliance | ||
Site Inspection | 11/07/2011 | In Compliance | COLSON_NJ_1 | 1/0 | Routine Compliance | ||
Site Inspection | 10/04/2010 | In Compliance | JUARISTIC_GK_1 | 1/0 | Routine Compliance | ||
Site Inspection | 12/16/2009 | In Compliance | JUARISTIC_GK_1 | 1/0 | Routine Compliance | ||
TCAR | 11/25/2009 | Satisfied | JUARISTIC_GK_1 | Closure | |||
Site Inspection | 02/27/2009 | In Compliance | BAUER_DR_1 | 1/0 | Routine Compliance | ||
Record Document | 12/24/2008 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||
Letter | 12/12/2008 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||
Site Inspection | 12/12/2008 | Major Out of Compliance | OSTENSEN_SA_1 | 1/0 | Installation | ||
Site Inspection | 12/12/2008 | In Compliance | COLSON_NJ_1 | 0/1 | Closure | ||
Site Inspection | 11/30/2007 | In Compliance | BAUER_DR_1 | 0/1 | Routine Compliance | ||
Site Inspection | 01/04/2007 | In Compliance | HARMAN_GR | 0/1 | Routine Compliance | ||
No Open AOCs Found | |||||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
11/16/2023 | 7064 | Minor | 3.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Annual operability testing of the Krueger leak gauge shall be performed at least once per year no more than 12 months apart. Submit previous test results if available. if testing was not performed or results not available perform operability testing of the Krueger leak gauge and submit results to to Citrus County Health Department and DEP enforcement office. | |||
11/16/2023 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | Financial responsibility must be maintained for the life of the system. Any tank that does not have financial responsibility for a period over 90 days must be permanently closed. Submit current financial responsibility documentation | |||
11/16/2023 | 7040 | SNC-B | 3.8 Overfill protection not provided. Fuel transfer not monitored. Alarms not installed. | Annual operability testing of the primary overfill device (Krueger level gauge) shall be performed at least once per year no more than 12 months apart. Submit previous test results if available. If testing was not performed or results are not available perform operability testing of the primary overfill device (Krueger level gauge) and submit results to Citrus County Environmental Health and DEP enforcement office. | |||
04/19/2021 | 5011 | SNC-B | 1.6 Failure to maintain and demonstrate financial responsibility. | Financial responsibility must be maintained for the life of the system. Any tank that does not have financial responsibility for a period over 90 days must be permanently closed. Submit financial responsibility documentation covering from 12/19/2019 to current to Citrus County Environmental Health. | |||
04/19/2021 | 5094 | SNC-B | 3.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days) for shop fabricated tank systems. For electronically monitored sumps, visual inspections not conducted every 6 months. | Monthly visual inspections shall be performed and recorded at least once per calendar month no more than 35 days apart and must at a minimum show the tank, aboveground piping, spill bucket, and tank interstice (Krueger leak gauge) are being inspected. Perform visual inspections for the next two months (May and June of 2021) and submit logs to Citrus County Environmental Health. | |||
04/19/2021 | 5042 | SNC-B | 3.22 Failure to provide approved overfill protection for shop fabricated tank systems. | Annual testing of the primary overfill device (Krueger level gauge) shall be performed at least once per year no more than 12 months apart. Submit previous test results if available. If testing was not performed or results are not available perform operability testing of the primary overfill device (Krueger level gauge) and submit results to Citrus County Environmental Health. | |||
No Discharges Found |