Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Pinellas   Status    OPEN
 
ID 8520625   Latitude    27° 45' 20.9799
 
Name SUNCOAST FOOD STORE
1422 58TH ST S
Longitude    82° 42' 42.8138
  GULFPORT, FL 33707-3313 LL Method    DPHO
 
Contact RAHMAN, GAZI   LL Status    REVIEWED
 
Phone (727) 317-4380   Status Date    06/19/2023
 
Account Owner Information
 
Name GAZI RAHMAN
1422 58TH ST
SAINT PETERSBURG, FL 33707
Effective Date    11/07/2018
 
Contact GAZI RAHMAN
 
Phone (727) 317-4380
 
Email MAJLISHNIK@GMAIL.COM
  Placard # / Date    684625 - 06/06/2024
Property Owner Information
 
Name GLAXO INTERNATIONAL INC
1422 58TH ST S
GULFPORT, FL 33707-3313
Effective Date    05/14/2004
 
Contact GAZI RAHMAN
 
Phone (727) 345-4369
 
Email
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
4 15000 Unleaded Gas (B) 05/01/2004 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (J) Pressurized piping system
(K) Dispenser liners
(M) Double wall - pipe jacket
(N) Approved synthetic material
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 10000 Unleaded Gas (B) 09/01/1986 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
(O) Tight fill
  (B) Steel/galvanized metal
(J) Pressurized piping system
(8) Manually sampled wells
(H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
2 10000 Unleaded Gas (B) 09/01/1986 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
(O) Tight fill
  (B) Steel/galvanized metal
(J) Pressurized piping system
(8) Manually sampled wells
(H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
3 10000 Unleaded Gas (B) 09/01/1986 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
(O) Tight fill
  (B) Steel/galvanized metal
(J) Pressurized piping system
(8) Manually sampled wells
(H) Mechanical line leak detector
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   05/25/2021 05/25/2022 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   05/25/2020 05/25/2021 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   05/25/2019 05/25/2020 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   05/25/2018 05/25/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   05/25/2017 05/25/2018 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   05/25/2016 05/25/2017 COMMERCE & INDUSTRY
INSURANCE   05/25/2015 05/25/2016 COMMERCE & INDUSTRY
INSURANCE   05/25/2014 05/25/2015 COMMERCE & INDUSTRY
INSURANCE   05/25/2013 05/25/2014 COMMERCE & INDUSTRY
INSURANCE   05/25/2012 05/25/2013 COMMERCE & INDUSTRY
INSURANCE   05/25/2011 05/25/2012 COMMERCE & INDUSTRY
INSURANCE   05/25/2010 05/25/2011 COMMERCE & INDUSTRY
INSURANCE   05/25/2009 05/25/2010 COMMERCE & INDUSTRY
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
RRBD 10/03/2005 10/13/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes TANK INSTALLED 5/04 PER STCM - FINANCIAL RESPONSIBILITY SUBMITTED IS FOR 5/05 TO 5/06 - L FRAZIER WILL CONTACT TO SEE IF THERE WAS F R FOR 5/04 TO 5/05
 
RRBD 09/07/2005 10/27/2005 ROGGELIN 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes GAZI RAHMAN, OWNER. CELL #813-766-1784 OR STORE# 727-345-4369; STATUS LETTER
 
RRBD 09/06/2005 10/13/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
NCLI 08/28/2005 08/28/2005 ROGGELIN 0/1 COMPLIANCE ASSURANCE
 
NCLI 08/22/2005 08/24/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
TIN 08/22/2005 08/28/2005 SIGNIFICANT OUT-OF-COMPLIANCE ROGGELIN 0/1 COMPLIANCE ASSURANCE
 
TCI 08/22/2005 08/24/2005 SIGNIFICANT OUT-OF-COMPLIANCE FRAZIER 0/1 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 03/22/2024 Major Out of Compliance PUHR_NM_1 0/1 Routine Compliance
 
Letter 03/22/2024 Satisfied PUHR_NM_1 Compliance Assistance
 
Letter 08/31/2021 Satisfied BROWNLEE_S Enforcement
 
Enforcement Referral 08/18/2021 Accepted COLSON_NJ_1 Enforcement
 
Site Inspection 08/12/2021 Major Out of Compliance COLSON_NJ_1 0/1 Routine Compliance
 
Letter 08/12/2021 Satisfied COLSON_NJ_1 Non-Compliance
 
Electronic Communication 07/29/2021 Satisfied COLSON_NJ_1 Routine Compliance
 
Letter 07/07/2020 Satisfied COLSON_NJ_1 Compliance Assistance
 
Record Document 07/07/2020 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 08/28/2019 Minor Out of Compliance COLSON_NJ_1 0/1 Routine Compliance
 
Letter 08/28/2019 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 07/17/2019 Satisfied COLSON_NJ_1 Routine Compliance
 
Electronic Communication 12/19/2017 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 03/23/2017 Minor Out of Compliance COLSON_NJ_1 0/1 Routine Compliance
 
Letter 03/23/2017 Satisfied COLSON_NJ_1 Non-Compliance
 
Phone Conversation 02/27/2017 Satisfied COLSON_NJ_1 Routine Compliance
 
Letter 02/17/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 02/17/2015 Minor Out of Compliance COLSON_NJ_1 0/1 Routine Compliance
 
Emergency Preparedness Information 02/13/2015 Satisfied COLSON_NJ_1 Routine Compliance
 
Site Inspection 04/16/2013 In Compliance STRAUSS_RH_1 0/1 Routine Compliance
 
Issue Document 04/16/2013 Satisfied STRAUSS_RH_1 Routine Compliance
 
Record Document 04/16/2013 Satisfied STRAUSS_RH_1 Non-Compliance
 
Incident 03/23/2012 Has not led to Discharge STRAUSS_RH_1 Incident
 
TCAR 03/23/2012 Satisfied SOWERS_JA_1 Closure
 
Letter 03/23/2012 Satisfied SOWERS_JA_1 Closure
 
Site Inspection 01/23/2012 Minor Out of Compliance STRAUSS_RH_1 0/1 Installation
 
Letter 01/23/2012 Satisfied STRAUSS_RH_1 Non-Compliance
 
Letter 01/19/2012 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 01/19/2012 Minor Out of Compliance STRAUSS_RH_1 0/1 Closure
 
Letter 12/20/2011 Satisfied MEETZE_A Non-Compliance
 
Site Inspection 12/20/2011 Major Out of Compliance MEETZE_A 0/1 QA/QC
 
Site Inspection 11/03/2011 Major Out of Compliance STRAUSS_RH_1 0/1 Routine Compliance
 
Letter 11/03/2011 Satisfied STRAUSS_RH_1 Non-Compliance
 
Record Document 04/14/2011 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 09/24/2010 Minor Out of Compliance STRAUSS_RH_1 0/1 Routine Compliance
 
Letter 09/24/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 10/21/2009 In Compliance STRAUSS_RH_1 0/1 Routine Compliance
 
Emergency Preparedness Information 10/21/2009 Satisfied STRAUSS_RH_1 Routine Compliance
 
Site Inspection 04/17/2009 In Compliance BARNETT_JX 0/1 Non-Compliance
 
Site Inspection 03/27/2009 Minor Out of Compliance BARNETT_JX 0/1 Routine Compliance
 
Letter 03/27/2009 Satisfied BARNETT_JX Non-Compliance
 
Emergency Preparedness Information 03/27/2009 Satisfied BARNETT_JX Routine Compliance
 
Site Inspection 03/21/2008 In Compliance LONGEN_JL_1 0/1 Routine Compliance
 
Emergency Preparedness Information 03/21/2008 Satisfied LONGEN_JL_1 Routine Compliance
 
Letter 06/14/2007 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 05/16/2007 Major Out of Compliance LONGEN_JL_1 0/1 Routine Compliance
 
Emergency Preparedness Information 02/13/2007 Satisfied LONGEN_JL_1 Routine Compliance
 
Emergency Preparedness Information 09/20/2006 Satisfied SOWERS_JA_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
03/22/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Submit integrity testing for the STP Sumps and Dispenser liners to this office for review.
 
03/22/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. 1) Properly remove the liquid from the STP Sump and provide photos/documentation to this office for review. 2) Open the pipe interstice in the two STP Sumps & provide documentation.
 
03/22/2024 6013 Minor 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. *Submit financial responsibility documentation from 5/25/2022 to current.* (Forms Part C & Part P were provided for the 05/25/2021-05/25/2022 insurance documentation).
 
03/22/2024 6001 Minor 2.1 No reasonable access provided. *Need to remove the tank interstice cap and manually check the interstice for liquid.* Provide documentation to this office for review once completed.
 
08/12/2021 6062 Minor 2.5 Release detection devices not tested annually. Be sure to have the required testing performed within 12 months of the last test date. Maintain records on file for at least 36 months. Submit current test results for the leak detectors to this office for review.
 
08/12/2021 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Be sure to have the required testing performed within 12 months of the last test date. Maintain records on file for at least 36 months. Submit current test results for the integrity of the spill buckets to this office for review.
 
08/12/2021 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Be sure to have the required testing performed within 12 months of the last test date. Maintain records on file for at least 36 months. Submit current test results for the overfill protection devices to this office for review.
 
08/12/2021 6007 SNC-A 2.6 Owner, operator, or supplier deposited motor fuel into storage tank without current valid registration placard. Pay the applicable fees and obtain a current (2021-2022) storage tank registration placard immediately.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
05/05/1986   COMPLETED 10 EARLY DETECTION INCENTIVE-ELIGIBLE