DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Central   Type    Retail Station
 
County Seminole   Status    OPEN
 
ID 8520651   Latitude    28° 48' 36.1282
 
Name SANFORD DOWNTOWN GAS
217 S PARK AVE
Longitude    81° 16' 3.9566
  SANFORD, FL 32771-1247 LL Method    DPHO
 
Contact MOHAMMAD ASGAR   LL Status    REVIEWED
 
Phone (407) 688-0703   Status Date    06/10/2005
 
Account Owner Information
 
Name ASGAR, MOHAMMED
217 S PARK AVE
SANFORD, FL 32771
Effective Date    04/03/2009
 
Contact MOHAMMED ASGAR
 
Phone (407) 688-0703
 
Email AKTERF62@GMAIL.COM
  Placard # / Date    688001 - 06/14/2024
Property Owner Information
 
Name KARE ROHEME
217 S PARK AVE
SANFORD, FL 32771
Effective Date    12/02/2019
 
Contact
 
Phone (305) 725-5481
 
Email KAREROHEME@LIVE.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
4 12000 Unleaded Gas (B) 11/01/1994 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(I) Double wall
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
  (F) Double wall
(G) Pipe trench liner
(J) Pressurized piping system
(K) Dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 8000 Unleaded Gas (B) 09/01/1973 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
  (B) Steel/galvanized metal (8) Manually sampled wells
(H) Mechanical line leak detector
(M) Manual tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
2 8000 Unleaded Gas (B) 09/01/1973 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
  (B) Steel/galvanized metal (8) Manually sampled wells
(H) Mechanical line leak detector
(M) Manual tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
3 8000 Unleaded Gas (B) 09/01/1973 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
  (B) Steel/galvanized metal (8) Manually sampled wells
(H) Mechanical line leak detector
(M) Manual tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   07/31/2018 07/31/2019 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   05/13/2017 05/13/2018 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   05/13/2016 05/13/2017 CRUM & FORSTER SPECIALTY INS. CO.
INSURANCE   05/13/2015 05/13/2016 CRUM & FORSTER INDEMNITY
INSURANCE   05/13/2014 05/13/2015 CRUM & FORSTER INDEMNITY
INSURANCE   05/13/2013 05/13/2014 ACE
INSURANCE   05/12/2012 05/12/2013 ZURICH-AMERICAN
INSURANCE   05/12/2011 05/12/2012 ZURICH-AMERICAN
INSURANCE   03/08/2011 03/08/2012 ZURICH-AMERICAN
INSURANCE   03/08/2011 03/08/2011 ZURICH-AMERICAN
INSURANCE   11/20/2009 11/20/2010 ZURICH-AMERICAN
INSURANCE   10/09/2008 10/09/2009 ZURICH-AMERICAN
INSURANCE   08/27/1993 08/27/1994 FPLIPA
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
LTR 03/29/2006 04/03/2006 PERRY 0/1 COMPLIANCE ASSURANCE
 
TCI 03/13/2006 03/28/2006 SIGNIFICANT OUT-OF-COMPLIANCE BAUTISTA 0/1 COMPLIANCE ASSURANCE
 
TCR 08/26/2005 09/26/2005 IN-COMPLIANCE BAUTISTA 0/1 COMPLIANCE ASSURANCE
 
TCR 08/10/2005 08/11/2005 IN-COMPLIANCE BAUTISTA 0/1 COMPLIANCE ASSURANCE
 
TCR 07/14/2005 07/14/2005 IN-COMPLIANCE PERRY 0/1 COMPLIANCE ASSURANCE
 
TCR 06/20/2005 06/22/2005 SIGNIFICANT OUT-OF-COMPLIANCE BAUTISTA 0/3 COMPLIANCE ASSURANCE
 
TCI 03/24/2005 03/29/2005 MINOR OUT-OF-COMPLIANCE BAUTISTA 0/1 COMPLIANCE ASSURANCE
 
TCR 11/07/2003 11/10/2003 IN-COMPLIANCE BAUTISTA 0/1 COMPLIANCE ASSURANCE
 
TCI 10/15/2003 10/16/2003 SIGNIFICANT OUT-OF-COMPLIANCE BAUTISTA 0/1 COMPLIANCE ASSURANCE
 
TCI 09/19/2002 09/19/2002 IN-COMPLIANCE BAUTISTA 0/1 COMPLIANCE ASSURANCE
 
TCR 01/03/2002 01/03/2002 IN-COMPLIANCE ARBELIUS 0/1 COMPLIANCE ASSURANCE
 
TCI 10/11/2001 10/29/2001 SIGNIFICANT OUT-OF-COMPLIANCE PERRY 0/1 COMPLIANCE ASSURANCE
 
TCR 05/02/2001 05/03/2001 IN-COMPLIANCE PERRY 0/1 COMPLIANCE ASSURANCE
 
TCI 11/28/2000 11/28/2000 MINOR OUT-OF-COMPLIANCE PERRY 0/1 COMPLIANCE ASSURANCE
 
TCI 10/14/1999 10/18/1999 IN-COMPLIANCE PERRY 0/1 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 06/24/2024 Satisfied KIDDER_MS_1 Incident
 
Electronic Communication 06/20/2024 Satisfied KIDDER_MS_1 Enforcement
 
Electronic Communication 06/20/2024 Satisfied KIDDER_MS_1 Enforcement
 
Site Inspection 05/22/2024 Major Out of Compliance KIDDER_MS_1 0/1 Routine Compliance
 
Electronic Communication 05/17/2024 Satisfied KIDDER_MS_1 Routine Compliance
 
Document Management 05/08/2024 Satisfied KIDDER_MS_1 Component Closure
 
TCAR 05/08/2024 Satisfied KIDDER_MS_1 Component Closure
 
Electronic Communication 05/02/2024 Satisfied KIDDER_MS_1 Routine Compliance
 
Discharge Reporting 08/09/2023 Satisfied KIDDER_MS_1 Discharge
 
Letter 08/09/2023 Satisfied KIDDER_MS_1 Discharge
 
Document Management 07/17/2023 Satisfied BOYLES_S Enforcement
 
Electronic Communication 06/30/2023 Satisfied BOYLES_S Enforcement
 
Electronic Communication 06/30/2023 Satisfied BOYLES_S Enforcement
 
Electronic Communication 10/04/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 10/04/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 10/04/2022 Satisfied BOYLES_S Enforcement
 
Document Management 09/26/2022 Satisfied KIDDER_MS_1 Discharge
 
Electronic Communication 09/23/2022 Satisfied KIDDER_MS_1 Discharge
 
Electronic Communication 09/15/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 09/15/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 09/14/2022 Satisfied BOYLES_S Enforcement
 
Letter 09/09/2022 Satisfied KIDDER_MS_1 Compliance Assistance
 
Site Inspection 09/09/2022 Major Out of Compliance KIDDER_MS_1 0/1 Compliance Assistance
 
Electronic Communication 09/06/2022 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 08/30/2022 Satisfied KIDDER_MS_1 Compliance Assistance
 
Electronic Communication 08/16/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 07/11/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 07/11/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 07/11/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 06/06/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 06/03/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 06/03/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 06/03/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 06/03/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 05/27/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 05/27/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 05/27/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 05/27/2022 Satisfied BOYLES_S Enforcement
 
Meeting 05/17/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 05/17/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 05/05/2022 Satisfied BOYLES_S Enforcement
 
Phone Conversation 05/04/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 05/04/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 04/21/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 04/21/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 04/18/2022 Satisfied BOYLES_S Enforcement
 
Letter 04/08/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/18/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/08/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/08/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/02/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 03/02/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 02/23/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 02/23/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 02/21/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 02/21/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 02/18/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 02/18/2022 Satisfied BOYLES_S Enforcement
 
Letter 02/14/2022 Satisfied KIDDER_MS_1 Non-Compliance
 
Site Inspection 02/14/2022 Major Out of Compliance KIDDER_MS_1 0/1 Routine Compliance
 
Phone Conversation 02/09/2022 Satisfied BOYLES_S Enforcement
 
Meeting 02/09/2022 Satisfied BOYLES_S Enforcement
 
Electronic Communication 01/05/2022 Satisfied KIDDER_MS_1 Routine Compliance
 
Electronic Communication 12/29/2021 Satisfied BOYLES_S Enforcement
 
Electronic Communication 12/14/2021 Satisfied BOYLES_S Enforcement
 
Electronic Communication 11/18/2021 Satisfied RAUENZAHN_RA_1 Enforcement
 
Electronic Communication 10/12/2021 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Electronic Communication 10/12/2021 Satisfied JOHNSON_CJ Enforcement
 
Meeting 09/30/2021 Satisfied KIDDER_MS_1 Enforcement
 
Electronic Communication 10/20/2020 Satisfied BROCK_CT Enforcement
 
Electronic Communication 10/20/2020 Satisfied BROCK_CT Enforcement
 
Phone Conversation 10/20/2020 Satisfied BROCK_CT Enforcement
 
Phone Conversation 10/06/2020 Satisfied BROCK_CT Enforcement
 
Electronic Communication 10/05/2020 Satisfied BROCK_CT Enforcement
 
Enforcement Referral 09/22/2020 Accepted RAUENZAHN_RA_1 Enforcement
 
Issue Document 09/08/2020 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Electronic Communication 09/08/2020 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Electronic Communication 06/23/2020 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Electronic Communication 04/28/2020 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Electronic Communication 04/13/2020 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Electronic Communication 03/26/2020 Satisfied BECKER_GT_1 Compliance Assistance
 
Electronic Communication 03/03/2020 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
TCAR 03/03/2020 Satisfied RAUENZAHN_RA_1 Closure
 
Letter 03/02/2020 Satisfied RAUENZAHN_RA_1 Compliance Assistance
 
Electronic Communication 11/04/2019 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 09/10/2019 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 08/09/2019 Satisfied PIERCE_BN_1 Compliance Assistance
 
Site Inspection 06/12/2019 Minor Out of Compliance PIERCE_BN_1 0/1 Routine Compliance
 
Letter 06/12/2019 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 05/24/2019 Satisfied PIERCE_BN_1 Routine Compliance
 
Phone Conversation 05/20/2019 Satisfied PIERCE_BN_1 Routine Compliance
 
Electronic Communication 05/20/2019 Satisfied PIERCE_BN_1 Routine Compliance
 
Letter 05/19/2017 Satisfied RAUENZAHN_RA_1 Discharge
 
Discharge Reporting 05/19/2017 Satisfied RAUENZAHN_RA_1 Discharge
 
Site Inspection 03/06/2017 In Compliance COTTRELL_SA_1 0/1 Installation
 
Electronic Communication 03/06/2017 Satisfied RAUENZAHN_RA_1 Non-Compliance
 
Electronic Communication 03/06/2017 Satisfied COTTRELL_SA_1 Installation
 
Phone Conversation 03/01/2017 Satisfied COTTRELL_SA_1 Non-Compliance
 
Letter 02/10/2017 Satisfied RAUENZAHN_RA_1 Non-Compliance
 
Phone Conversation 01/18/2017 Satisfied COTTRELL_SA_1 Non-Compliance
 
Electronic Communication 12/05/2016 Satisfied COTTRELL_SA_1 Non-Compliance
 
Letter 11/08/2016 Satisfied COTTRELL_SA_1 Non-Compliance
 
Electronic Communication 11/08/2016 Satisfied COTTRELL_SA_1 Routine Compliance
 
Electronic Communication 11/08/2016 Satisfied COTTRELL_SA_1 Non-Compliance
 
Site Inspection 11/08/2016 Major Out of Compliance COTTRELL_SA_1 0/1 Routine Compliance
 
Phone Conversation 10/24/2016 Satisfied COTTRELL_SA_1 Routine Compliance
 
Document Management 08/02/2016 Satisfied RAUENZAHN_RA_1 Closure
 
Incident 05/06/2016 Led to Discharge (Incident promoted) COTTRELL_SA_1 Incident
 
Document Management 04/28/2016 Complete RAUENZAHN_RA_1 Closure
 
Letter 04/28/2016 Satisfied RAUENZAHN_RA_1 Closure
 
Phone Conversation 02/16/2016 Satisfied COTTRELL_SA_1 Non-Compliance
 
Phone Conversation 02/16/2016 Satisfied COTTRELL_SA_1 Closure
 
Letter 02/10/2016 Satisfied RAUENZAHN_RA_1 Closure
 
Document Management 02/09/2016 Complete RAUENZAHN_RA_1 Closure
 
Site Inspection 10/02/2015 Minor Out of Compliance COTTRELL_SA_1 0/1 Closure
 
Site Inspection 10/02/2015 Minor Out of Compliance COTTRELL_SA_1 0/1 Installation
 
Electronic Communication 10/02/2015 Satisfied COTTRELL_SA_1 Installation
 
Electronic Communication 10/02/2015 Satisfied COTTRELL_SA_1 Closure
 
Letter 10/02/2015 Satisfied COTTRELL_SA_1 Non-Compliance
 
Electronic Communication 09/21/2015 Satisfied COTTRELL_SA_1 Non-Compliance
 
Site Inspection 09/21/2015 Major Out of Compliance COTTRELL_SA_1 0/1 Non-Compliance
 
Document Management 09/21/2015 Complete COTTRELL_SA_1 Incident
 
Meeting 04/30/2015 Satisfied COTTRELL_SA_1 Non-Compliance
 
Letter 04/02/2015 Satisfied RAUENZAHN_RA_1 Non-Compliance
 
Electronic Communication 04/01/2015 Satisfied COTTRELL_SA_1 Non-Compliance
 
Site Inspection 04/01/2015 Minor Out of Compliance COTTRELL_SA_1 0/1 Non-Compliance
 
Electronic Communication 01/05/2015 Satisfied COTTRELL_SA_1 Non-Compliance
 
Electronic Communication 11/04/2014 Satisfied COTTRELL_SA_1 Routine Compliance
 
Site Inspection 11/04/2014 Major Out of Compliance COTTRELL_SA_1 0/1 Routine Compliance
 
Letter 11/04/2014 Satisfied COTTRELL_SA_1 Non-Compliance
 
Emergency Preparedness Information 11/04/2014 Satisfied COTTRELL_SA_1 Routine Compliance
 
Site Inspection 02/28/2013 In Compliance COTTRELL_SA_1 0/1 Non-Compliance
 
Site Inspection 01/17/2013 Minor Out of Compliance COTTRELL_SA_1 0/1 Routine Compliance
 
Letter 01/17/2013 Satisfied COTTRELL_SA_1 Non-Compliance
 
Emergency Preparedness Information 01/16/2013 Satisfied COTTRELL_SA_1 Routine Compliance
 
Meeting 01/04/2013 Satisfied COTTRELL_SA_1 Routine Compliance
 
Site Inspection 03/19/2012 In Compliance BAUTISTA_E_1 0/1 Non-Compliance
 
Site Inspection 03/15/2012 Major Out of Compliance BAUTISTA_E_1 0/1 Routine Compliance
 
Letter 03/15/2012 Satisfied BAUTISTA_E_1 Non-Compliance
 
Emergency Preparedness Information 03/06/2012 Satisfied BAUTISTA_E_1 Routine Compliance
 
Enforcement Tracking 08/11/2011 Closed Without Enforcement SCHULTZ_C Enforcement
 
Site Inspection 03/28/2011 In Compliance BAUTISTA_E_1 0/1 Non-Compliance
 
Site Inspection 03/10/2011 Major Out of Compliance BAUTISTA_E_1 0/1 Routine Compliance
 
Letter 03/10/2011 Satisfied BAUTISTA_E_1 Non-Compliance
 
Emergency Preparedness Information 03/07/2011 Satisfied BAUTISTA_E_1 Routine Compliance
 
Site Inspection 11/02/2010 In Compliance SCHULTZ_C 0/4 Enforcement
 
Site Inspection 03/18/2010 In Compliance BAUTISTA_E_1 0/1 Non-Compliance
 
Site Inspection 03/17/2010 Major Out of Compliance BAUTISTA_E_1 0/1 Routine Compliance
 
Site Inspection 07/20/2009 In Compliance BAUTISTA_E_1 0/1 Non-Compliance
 
Letter 06/25/2009 Satisfied PERRY_JF Non-Compliance
 
Site Inspection 06/16/2009 Minor Out of Compliance BAUTISTA_E_1 0/1 Non-Compliance
 
Letter 03/30/2009 Satisfied PERRY_JF Non-Compliance
 
Site Inspection 03/16/2009 Major Out of Compliance BAUTISTA_E_1 0/1 Routine Compliance
 
Record Document 03/28/2008 Satisfied JONES_FH Enforcement
 
Letter 03/28/2008 Satisfied PERRY_JF Non-Compliance
 
Site Inspection 03/27/2008 Major Out of Compliance JONES_FH 0/1 Enforcement
 
Site Inspection 03/20/2008 Major Out of Compliance BAUTISTA_E_1 0/1 Routine Compliance
 
Enforcement Referral 08/20/2007 Accepted JONES_FH Enforcement
 
Site Inspection 03/15/2007 Major Out of Compliance BAUTISTA_E_1 0/1 Routine Compliance
 
Emergency Preparedness Information 02/07/2007 Satisfied PERRY_JF Routine Compliance
 
Site Inspection 12/07/2006 Major Out of Compliance JONES_FH 0/1 Enforcement
 
Emergency Preparedness Information 09/22/2006 Satisfied PERRY_JF Routine Compliance
 
Issue Document 09/06/2006 Satisfied PERRY_JF Enforcement
 
Site Inspection 08/23/2006 Major Out of Compliance BAUTISTA_E_1 0/1 Non-Compliance
 
Letter 07/05/2006 Satisfied PERRY_JF Non-Compliance
 
Site Inspection 06/26/2006 Major Out of Compliance BAUTISTA_E_1 0/1 Non-Compliance
 
Site Inspection 05/19/2006 Major Out of Compliance BAUTISTA_E_1 0/2 Non-Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
05/13/2024 6002 Minor 2.1 Operator Training records not available. Please provide A/B/C operator training certificates for review.
 
05/09/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Please provide integrity testing records for review.
 
05/09/2024 6062 Minor 2.5 Release detection devices not tested annually. Please provide operability testing records for your release detection devices. 1) Line leak detectors 2) Interstitial vacuum gauge
 
05/09/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Please provide annual operability testing records for your overfill protection devices.
 
05/09/2024 6001 Minor 2.1 No reasonable access provided. Please schedule a re-inspection or provide a time stamped picture of the UST's interstitial monitoring gauge.
 
02/09/2022 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. 1) Please have a certified petroleum contractor properly replace your premium unleaded spill bucket. During the removal, soil sampling will need to be conducted in order to determine whether or not a release has occurred. 2) Have your contractor properly position test boots throughout the site.
 
02/08/2022 6012 SNC-A 2.9 No financial responsibility instrument or expired instrument for > 180 days. Financial responsibility has not been provided to the county or Department since the date of the inspection. Please share copies of your financial responsibility paperwork with FDEP personnel for the years 2019, 2020, and 2021.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
09/21/2022   ACTIVE
 
03/30/2016   ACTIVE
 
10/11/1993   INACTIVE 6 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE Burkard, Beth M. M 4078361459