Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 03/14/2025 Last Data Refresh: 03/13/2025 Report Generated from DOPPLER | |||||||||||
District | Northeast | Type | Local Government | ||||||||
County | Duval | Status | OPEN | ||||||||
ID | 8521409 | Latitude | 30° 19' 29.2636 | ||||||||
Name |
JACKSONVILLE CITY-FLEET MGMT DIV 501 E BAY ST |
Longitude | 81° 39' 1.0523 | ||||||||
JACKSONVILLE, FL 32202-2975 | LL Method | DPHO | |||||||||
Contact | J LOPEZ | LL Status | REVIEWED | ||||||||
Phone | (904) 509-3084 | Status Date | 06/11/2003 | ||||||||
Account Owner Information | |||||||||||
Name | JACKSONVILLE CITY-FLEET MGMT 2581 COMMONWEALTH AVE JACKSONVILLE, FL 32254-2013 |
Effective Date | 05/20/1994 | ||||||||
Contact | ERIK PREACHER/ JOSE LOPEZ (904) 381-8285 / MIYATA | ||||||||||
Phone | (904) 255-7434 | ||||||||||
JLOPEZ@COJ.NET | |||||||||||
Placard # / Date | 691327 - 06/19/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | JACKSONVILLE CITY-FLEET MGMT 2581 COMMONWEALTH AVE JACKSONVILLE, FL 32254-2013 |
Effective Date | 02/09/2012 | ||||||||
Contact | ERIK PREACHER/ JOSE LOPEZ (904) 381-8285 / MIYATA | ||||||||||
Phone | (904) 255-7434 | ||||||||||
JLOPEZ@COJ.NET | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
11 | 8000 | Emerg Generator Diesel (G) | 04/01/1993 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(I) Suction piping system (M) Double wall - pipe jacket (N) Approved synthetic material |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (F) Monitor dbl wall tank space (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
8 | 20000 | Unleaded Gas (B) | 04/01/1993 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
9 | 20000 | Unleaded Gas (B) | 04/01/1993 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (I) Double wall (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 10000 | Unleaded Gas (B) | 06/01/1974 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
10 | 1000 | New/Lube Oil (O) | 04/01/1993 | UNDERGROUND | Out of Service (T) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (L) Compartmented (M) Spill containment bucket (O) Tight fill (P) Level gauges/alarms |
(I) Suction piping system (M) Double wall - pipe jacket (N) Approved synthetic material |
(1) Continuous electronic sensing (2) Visual inspect pipe sumps (3) Electronic monitor pipe sumps (F) Monitor dbl wall tank space (K) Monitor dbl wall pipe space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 10000 | Unleaded Gas (B) | 06/01/1974 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 10000 | Unleaded Gas (B) | 06/01/1974 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 10000 | Fuel Oil - Onsite Heat (M) | 08/01/1975 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (A) Abv, no soil contact | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 560 | New/Lube Oil (O) | 08/01/1975 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (I) Suction piping system | (M) Manual tank gauging - USTs | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 560 | New/Lube Oil (O) | 08/01/1975 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (I) Suction piping system | (M) Manual tank gauging - USTs | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 8000 | Emerg Generator Diesel (G) | 01/01/1977 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (C) Groundwater Monitoring Plan | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
LOCAL GOVERNMENTS - FINANCIAL TEST | 10/01/2021 | 09/30/2022 | |||||||||
LOCAL GOVERNMENTS - FINANCIAL TEST | 10/01/2019 | 03/28/2021 | |||||||||
LOCAL GOVERNMENTS - FINANCIAL TEST | 10/01/2018 | 03/28/2020 | |||||||||
LOCAL GOVERNMENTS - BOND RATING TEST | 01/28/2014 | 08/23/2019 | |||||||||
LOCAL GOVERNMENTS - BOND RATING TEST | 09/22/2004 | 10/01/2030 | |||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
TCI | 04/19/2005 | 05/03/2005 | IN-COMPLIANCE | GARBEE_M | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes LINES TESTED 2/10/05 BY MECO. LLD FAILED TEST AND WAS REPLACED WITH NEW LLD THAT PASSED MONTHLY INSPECTIONS.POTENTIAL GROWTH ON ENVIRON PIPING NEEDS TO BE MONITORED CLOSELY FOR LOSS OF INTEGRITY. | |||||||||||
TXI | 01/13/2005 | 02/11/2005 | IN-COMPLIANCE | LEIGHTON | 0/1 | COMPLIANCE ASSURANCE | |||||
Completion Notes REMOTE FILL PIPING CLOSED IN PLACE, FILL PORTS WERE CONCRETED OVER IN MARCH 03. NO TCAR REQ'D PER DEP/NED BECAUSE PIPE WAS NEVER USED | |||||||||||
TCI | 03/25/2004 | 04/09/2004 | IN-COMPLIANCE | GARBEE_M | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes 2005 INSPECTION: REQUEST BARRIERS BE PLACED AROUND LUBE OIL TANK AND 20K UST, DAY BEFORE INSPECTION TO ENSURE ACCESS. | |||||||||||
RRBD | 09/03/2003 | 09/15/2003 | DEFALCO_L | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED DOC FROM TALLY RE F R. ALL OK. RECORDS OK ALSO. | |||||||||||
RRBD | 07/22/2003 | 08/18/2003 | DEFALCO_L | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes MTG W/ HARRY LYONS TO DISCUSS STATUS, LLD TESTING 7/16/03 PASSED | |||||||||||
TCI | 05/13/2003 | 05/30/2003 | MINOR OUT-OF-COMPLIANCE | DEFALCO_L | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes LLD TEST DUE, CLOSURE OF REMOTE FILL PIPING NOW DUE 12/04; DOC OF FR SELF INSURED STATUS DUE. | |||||||||||
RRBD | 11/21/2002 | 06/11/2003 | DEFALCO_L | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes UPDATE LTR REMOTEFILL PIPING CLOSED, NEED CLOSURE ASSESS. | |||||||||||
RRBD | 07/18/2002 | 07/25/2002 | DEFALCO_L | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes TCI ISSUES- OF AND LLD RESOLVED | |||||||||||
NCLI | 03/11/2002 | 03/11/2002 | DEFALCO_L | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RD,OVERFILL,ANNUAL LLD TESTING | |||||||||||
TCI | 02/21/2002 | 03/11/2002 | SIGNIFICANT OUT-OF-COMPLIANCE | DEFALCO_L | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes ANNUAL LLD, MON RD DOC , OVERFILL | |||||||||||
TCI | 08/03/2001 | 08/07/2001 | IN-COMPLIANCE | LUBINSKI | 0/4 | COMPLIANCE ASSURANCE | |||||
No Compliance Activity Data Found | |||||||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
11/15/2022 | 6024 | Minor | 2.2 Integrity test not performed on storage tank, integral piping, single-walled spill containment system, double-walled spill containment system, or doubled-walled sump prior to placing into service. | Perform containment integrity testing for Tank 8, 9, and 11 STP sumps, the regular gasoline transition sump, and 1/2, and 3/4 dispenser sumps. Submit results to the Department for review. | |||||||
11/09/2022 | 6006 | Minor | 2.5 Placard not displayed (or available upon request). | Display registration placard in plain view and submit a photograph of the posted placard to the Department for review. | |||||||
11/09/2022 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Provide an current alarm history print out to the Department for review. | |||||||
11/09/2022 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Remove and properly dispose of the liquid from the Tank 10 STP sumps as petroleum contact water (PCW). Provide after PCW removal photographs that clearly show the boots and piping in the sumps and PCW disposal manifest/documentation to the Department for review. | |||||||
11/09/2022 | 6023 | Minor | 4.1 Secondary containment or integral piping not installed to allow for monitoring point. | Have a qualified contractor investigate the construction of integral piping for Tank 11 and determine if there is a low point monitoring system installed. Submit documentation to the Department for review. If it is determined that a low point monitoring system in not installed, modification to the system to allow monitoring may be needed. | |||||||
11/09/2022 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Address the surface corrosion observed in the Tank 9 STP sump. Submit after repair photographs and a work order to the Department for review. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
04/05/1993 | COMPLETED | 60 | PETROLEUM CLEANUP PARTICIPATION PROGRAM-ELIGIBLE | ||||||||