Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Retail Station | ||||||||
County | Pasco | Status | OPEN | ||||||||
ID | 8521491 | Latitude | 28° 14' 59.0295 | ||||||||
Name |
786 AABAAD INC 6226 ROWAN RD |
Longitude | 82° 41' 53.5141 | ||||||||
NEW PORT RICHEY, FL 34653 | LL Method | DPHO | |||||||||
Contact | AKBAR BARMANWALLA | LL Status | REVIEWED | ||||||||
Phone | (727) 848-2124 | Status Date | 08/30/2003 | ||||||||
Account Owner Information | |||||||||||
Name | 786 AABAAD INC 580 LK CYPRESS LN OLDSMAR, FL 34677 |
Effective Date | 11/18/2009 | ||||||||
Contact | AKBAR BARMANWALLA | ||||||||||
Phone | (727) 642-4847 | ||||||||||
AKBARBARMANWALLA@YAHOO.COM | |||||||||||
Placard # / Date | 698236 - 07/01/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | THE PANTRY INC 305 Gregson Dr Cary, NC 27511-6496 |
Effective Date | 07/28/2000 | ||||||||
Contact | BRENT PUZAK | RAMON INCIONG (386) 916-6267 | ||||||||||
Phone | (919) 774-6700 | ||||||||||
GBIGGS@CIRCLEK.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
8 | 20000 | Unleaded Gas (B) | 05/01/2009 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
9 | 10000 | Unleaded Gas (B) | 05/01/2009 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (I) Double wall (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 6000 | Unleaded Gas (B) | 11/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 10000 | Unleaded Gas (B) | 11/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 10000 | Unleaded Gas (B) | 11/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 6000 | Vehicular Diesel (D) | 11/01/1984 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 6000 | Gasohol (C) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel |
(C) Fiberglass | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 6000 | Unleaded Gas (B) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel |
(C) Fiberglass | (Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 6000 | Leaded Gas (A) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket (O) Tight fill |
(J) Pressurized piping system (K) Dispenser liners (M) Double wall - pipe jacket (N) Approved synthetic material |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (K) Monitor dbl wall pipe space (S) Statistical Inventory Reconcile |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 07/16/2022 | 07/16/2024 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 07/16/2021 | 07/16/2022 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 07/16/2020 | 07/16/2021 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 07/16/2019 | 07/16/2020 | ACE AMERICAN INSURANCE COMPANY | ||||||||
INSURANCE | 07/16/2018 | 07/16/2019 | ACE | ||||||||
INSURANCE | 07/16/2017 | 07/16/2018 | ACE | ||||||||
INSURANCE | 01/16/2017 | 01/16/2018 | ACE | ||||||||
INSURANCE | 07/16/2016 | 07/16/2017 | ACE | ||||||||
INSURANCE | 07/16/2015 | 07/16/2016 | ACE | ||||||||
INSURANCE | 07/16/2014 | 07/16/2015 | ACE | ||||||||
INSURANCE | 07/16/2013 | 07/16/2017 | ACE | ||||||||
INSURANCE | 07/16/2013 | 07/16/2014 | ACE | ||||||||
INSURANCE | 07/16/2012 | 07/16/2013 | ACE | ||||||||
INSURANCE | 07/16/2011 | 07/16/2012 | ACE | ||||||||
INSURANCE | 07/16/2010 | 07/16/2011 | ACE | ||||||||
INSURANCE | 07/16/2009 | 07/16/2010 | ZURICH-AMERICAN | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
NCLI | 04/19/2006 | 04/19/2006 | CONDOLEON, G J | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 04/18/2006 | 04/19/2006 | MINOR OUT-OF-COMPLIANCE | CONDOLEON, G J | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 03/15/2005 | 03/28/2005 | IN-COMPLIANCE | RODRIGUEZ, IVAN | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 02/17/2004 | 02/19/2004 | IN-COMPLIANCE | RODRIGUEZ, IVAN | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 03/12/2003 | 03/19/2003 | IN-COMPLIANCE | HANSEN, DAVE | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 03/26/2002 | 03/29/2002 | IN-COMPLIANCE | HANSEN, DAVID | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 05/16/2001 | 05/17/2001 | IN-COMPLIANCE | HANSEN | 0/4 | COMPLIANCE ASSURANCE | |||||
TIN | 05/05/2000 | 05/05/2000 | IN-COMPLIANCE | PETERSON | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 12/21/1999 | 12/22/1999 | IN-COMPLIANCE | HARRIS | 0/4 | COMPLIANCE ASSURANCE | |||||
TCI | 04/14/1999 | 04/19/1999 | IN-COMPLIANCE | PETERSON_JE | 0/4 | COMPLIANCE ASSURANCE | |||||
IRFR | 01/06/1999 | 09/13/1999 | JAN PETERSON | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes NO DISCHARGE | |||||||||||
UTCI | 03/24/1998 | 03/27/1998 | MINOR OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
Completion Notes ROUTINE COMPLIANCE | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Record Document | 05/21/2024 | Satisfied | MUSLIC_A_1 | Compliance Assistance | |||||||
Letter | 05/07/2024 | Satisfied | MUSLIC_A_1 | Compliance Assistance | |||||||
Site Inspection | 05/07/2024 | Major Out of Compliance | MUSLIC_A_1 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 03/04/2024 | Satisfied | MUSLIC_A_1 | Routine Compliance | |||||||
Record Document | 03/02/2022 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Letter | 11/04/2021 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Record Document | 11/04/2021 | Satisfied | JUARISTIC_GK_1 | Routine Compliance | |||||||
Site Inspection | 11/03/2021 | Major Out of Compliance | JUARISTIC_GK_1 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 08/02/2021 | Satisfied | JUARISTIC_GK_1 | Routine Compliance | |||||||
Letter | 08/22/2019 | Satisfied | BROWNLEE_S | Enforcement | |||||||
Record Document | 07/25/2019 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Enforcement Referral | 06/03/2019 | Accepted | JUARISTIC_GK_1 | Enforcement | |||||||
Electronic Communication | 05/30/2019 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Phone Conversation | 05/30/2019 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Phone Conversation | 05/30/2019 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Site Inspection | 03/01/2019 | Minor Out of Compliance | JUARISTIC_GK_1 | 0/2 | Routine Compliance | ||||||
Letter | 03/01/2019 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Electronic Communication | 02/13/2019 | Satisfied | JUARISTIC_GK_1 | Routine Compliance | |||||||
Site Inspection | 04/20/2017 | In Compliance | JUARISTIC_GK_1 | 0/2 | Closure | ||||||
Site Inspection | 04/20/2017 | In Compliance | JUARISTIC_GK_1 | 0/2 | Installation | ||||||
Phone Conversation | 04/12/2017 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Record Document | 03/17/2017 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Phone Conversation | 03/02/2017 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Electronic Communication | 03/02/2017 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Site Inspection | 01/30/2017 | Minor Out of Compliance | JUARISTIC_GK_1 | 0/2 | Routine Compliance | ||||||
Letter | 01/30/2017 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Phone Conversation | 01/05/2017 | Satisfied | JUARISTIC_GK_1 | Routine Compliance | |||||||
Site Inspection | 02/25/2015 | In Compliance | JUARISTIC_GK_1 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 02/25/2015 | Satisfied | JUARISTIC_GK_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 02/25/2015 | Satisfied | JUARISTIC_GK_1 | Routine Compliance | |||||||
Electronic Communication | 07/22/2014 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Site Inspection | 07/22/2014 | In Compliance | JUARISTIC_GK_1 | 0/2 | Non-Compliance | ||||||
Electronic Communication | 06/04/2014 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Letter | 05/29/2014 | Satisfied | JUARISTIC_GK_1 | Non-Compliance | |||||||
Site Inspection | 05/29/2014 | Minor Out of Compliance | JUARISTIC_GK_1 | 0/2 | Routine Compliance | ||||||
Record Document | 06/21/2013 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 05/10/2013 | Major Out of Compliance | LONGEN_JL_1 | 0/2 | Routine Compliance | ||||||
Letter | 05/10/2013 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 05/10/2013 | Satisfied | LONGEN_JL_1 | Routine Compliance | |||||||
Record Document | 09/19/2011 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Letter | 08/18/2011 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 08/18/2011 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Site Inspection | 08/18/2011 | Minor Out of Compliance | CONDOLEON_GJ_1 | 0/2 | Routine Compliance | ||||||
Letter | 08/06/2010 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Site Inspection | 08/06/2010 | Major Out of Compliance | CONDOLEON_GJ_1 | 0/2 | Routine Compliance | ||||||
Emergency Preparedness Information | 08/06/2010 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Site Inspection | 11/25/2009 | In Compliance | CONDOLEON_GJ_1 | 0/2 | Routine Compliance | ||||||
Record Document | 08/18/2009 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Letter | 07/29/2009 | Satisfied | CONDOLEON_GJ_1 | Closure | |||||||
TCAR | 07/15/2009 | Satisfied | CONDOLEON_GJ_1 | Closure | |||||||
Letter | 06/30/2009 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Site Inspection | 06/30/2009 | Major Out of Compliance | CONDOLEON_GJ_1 | 0/2 | Installation | ||||||
Site Inspection | 05/08/2009 | In Compliance | CONDOLEON_GJ_1 | 0/4 | Closure | ||||||
Record Document | 03/05/2009 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Record Document | 02/26/2009 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 02/26/2009 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Letter | 02/19/2009 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
Site Inspection | 02/19/2009 | Minor Out of Compliance | CONDOLEON_GJ_1 | 0/4 | Routine Compliance | ||||||
Site Inspection | 02/13/2008 | In Compliance | CONDOLEON_GJ_1 | 0/4 | Routine Compliance | ||||||
Emergency Preparedness Information | 02/13/2008 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Site Inspection | 02/21/2007 | In Compliance | CONDOLEON_GJ_1 | 0/4 | Routine Compliance | ||||||
Emergency Preparedness Information | 02/12/2007 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/27/2006 | Satisfied | CONDOLEON_GJ_1 | Routine Compliance | |||||||
Record Document | 06/20/2006 | Satisfied | CONDOLEON_GJ_1 | Non-Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
05/07/2024 | 6013 | Minor | 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. | Submit Part P financial responsibility documentation for period from 7/16/2022 to 7/16/2024. | |||||||
05/07/2024 | 6017 | Minor | 4.4 All incident records, including test results not kept until storage tank system closure. | Provide incident investigation results for the discovery of liquid in the RUL secondary spill bucket. Perform integrity test of the RUL spill bucket and submit test results to this office. | |||||||
05/07/2024 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | Submit monthly visual inspection and electronic release detection records for period from 10/1/2021 to 6/1/2022. | |||||||
05/07/2024 | 6075 | Minor | 2.9 Records of current training certificates for designated Class A, B, and C operators shall be maintained for as long as the operators are designated for that facility not kept. | Provide Class A/B and C training certificates. | |||||||
05/07/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Provide cover to electrical conduit box in RUL STP sump. | |||||||
05/07/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Perform annual operability testing on all release detection devices at intervals not exceeding 12 months. | |||||||
05/07/2024 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Perform annual operability test on the designated primary overfill protection device at intervals not exceeding 12 months. | |||||||
11/03/2021 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Release detection devices shall be tested annually. Facility was referred for enforcement in 2019 for same violation. | |||||||
11/03/2021 | 6002 | Minor | 2.1 Operator Training records not available. | Owners and operators of underground storage tank system facilities must maintain required training certification documentation as described in this rule on-site and must provide it upon request to the county or Department. Provide Class A/B and C training certification for store employees. | |||||||
03/01/2019 | 4067 | Minor | 4.2 Release detection devices not tested annually. | Test the MLLDs and submit the test results to this office. | |||||||
03/01/2019 | 4015 | Minor | 2.10 Incomplete documentation demonstrating financial responsibility. | Fill out the Part P form and submit to this office. | |||||||
03/01/2019 | 4001 | Minor | 2.2 Operator certification requirements not met. | Obtain proper certification and submit to this office. | |||||||
03/01/2019 | 4067 | Minor | 4.2 Release detection devices not tested annually. | Test the OPW VisiGauges and submit the test results to this office. | |||||||
03/01/2019 | 4068 | Minor | 4.3 Storage tank system has a not repaired component which has or could cause a release or discharge. | Address the corrosion in the RUL sump. | |||||||
03/01/2019 | 4057 | Minor | 4.31 Overfill protection devices not registered or tested annually. | Test the overfill protection devices and submit the test results to this office. | |||||||
03/01/2019 | 4076 | Minor | 4.11 Failure to conduct required periodic containment and interstitial integrity testing. | Perform the integrity test of the D/W SCUs and submit the test results to this office. | |||||||
03/01/2019 | 4067 | Minor | 4.2 Release detection devices not tested annually. | Test the liquid sensors and monitoring panel, and submit the test results to this office. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
04/28/1990 | COMPLETED | 95 | PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE | ||||||||