Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/11/2025 Last Data Refresh: 05/10/2025 Report Generated from DOPPLER | |||||||||||
District | Northeast | Type | Fuel user/Non-retail | ||||||||
County | Duval | Status | OPEN | ||||||||
ID | 8521512 | Latitude | 30° 18' 47.0982 | ||||||||
Name |
CENTURY AMBULANCE SERVICE 740 GREELAND AVE |
Longitude | 81° 46' 52.0134 | ||||||||
JACKSONVILLE, FL 32221-4404 | LL Method | DPHO | |||||||||
Contact | Karen Robeson | LL Status | REVIEWED | ||||||||
Phone | (904) 545-3611 | Status Date | 05/03/2010 | ||||||||
Account Owner Information | |||||||||||
Name | RG AMBULANCE SERVICE INC 2766 NW 62ND ST MIAMI, FL 33147 |
Effective Date | 09/14/2023 | ||||||||
Contact | BOB BEERS | ||||||||||
Phone | (305) 308-8110 | ||||||||||
BBEERS@TRANSPORTATIONAMERICA.COM | |||||||||||
Placard # / Date | 705506 - 04/08/2025 | ||||||||||
Property Owner Information | |||||||||||
Name | RG AMBULANCE SERVICE INC 2766 NW 62ND ST MIAMI, FL 33147 |
Effective Date | 09/14/2023 | ||||||||
Contact | BOB BEERS | ||||||||||
Phone | (305) 308-8110 | ||||||||||
BBEERS@TRANSPORTATIONAMERICA.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 650 | Vehicular Diesel (D) | 02/01/2022 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket |
(X) No piping associated w/tank | (Q) Visual inspection of ASTs | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 55 | Misc Petrol-Based Product (X) | 01/01/1979 | UNDERGROUND | Unmaintained (F) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (J) Pressurized piping system | (I) Not required | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 550 | Waste Oil (L) | 10/01/1977 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (Y) Unknown | (I) Not required | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 550 | Emerg Generator Diesel (G) | 10/01/1977 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (I) Suction piping system (Z) DEP approved piping |
(I) Not required (X) None |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 12000 | Unleaded Gas (B) | 12/01/1979 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(D) Unknown | (J) Pressurized piping system | (Y) Unknown | |||||||||
No Insurance Documents Found | |||||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Referral | 04/10/2025 | Accepted | AMES_J | Enforcement | |||||||
Site Inspection | 03/31/2025 | Major Out of Compliance | WESTERMAN_ML_1 | 1/0 | Installation | ||||||
Letter | 03/31/2025 | Satisfied | WESTERMAN_ML_1 | Compliance Assistance | |||||||
Site Inspection | 03/31/2025 | Major Out of Compliance | WESTERMAN_ML_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 02/19/2025 | Satisfied | WESTERMAN_ML_1 | Compliance Assistance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
03/31/2025 | 7064 | Minor | 3.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | The facility must begin documenting monthly visual inspections and provide EQD with documentation upon three consecutive months of completed inspections. Keep inspection records on file for a minimum of three years. | |||||||
03/31/2025 | 7020 | Minor | 1.2 Integrity Testing of secondary containment systems and interstitial spaces not performed before being placed into service. | The facility must have an integrity test performed for the tank interstitial space and spill bucket and provide EQD with documentation. | |||||||
03/31/2025 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | The facility must provide EQD with documentation of Financial Responsibility for Tank 5. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
11/16/1988 | COMPLETED | 45 | EARLY DETECTION INCENTIVE-ELIGIBLE | ||||||||