DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 02/02/2025        Last Data Refresh: 02/01/2025        Report Generated from DOPPLER
 
District Central   Type    Fuel user/Non-retail
 
County Volusia   Status    OPEN
 
ID 8622747   Latitude    29° 10' 53.38
 
Name L AND S ENTERPRISES LLC
1630 S SEAGRAVE ST
Longitude    81° 0' 36.78
  DAYTONA BEACH, FL 32119 LL Method    DPHO
 
Contact LEONARD BLANTON   LL Status    REVIEWED
 
Phone (386) 214-7043   Status Date    07/18/2005
 
Account Owner Information
 
Name L AND S ENTERPRISES LLC
800 GATEPARK DR
DAYTONA BEACH, FL 32114
Effective Date    12/06/2022
 
Contact LEONARD BLANTON
 
Phone (386) 304-0722
 
Email LBLANTON@L-SENTERPRISES.COM
  Placard # / Date    702218 - 10/15/2024
Property Owner Information
 
Name 1630 SOUTH SEGRAVE LLC
125 NAUTICAL DR
SOUTH DAYTONA, FL 32119
Effective Date    12/06/2022
 
Contact LEONARD BLANTON
 
Phone (386) 214-7043
 
Email LBLANTON@L-SENTERPRISES.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
9 1000 Vehicular Diesel (D) 11/01/2022 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(G) Sacrificial anode CP
(I) Double wall
(P) Level gauges/alarms
  (B) Steel/galvanized metal
(D) External protective coating
(F) Double wall
(I) Suction piping system
(F) Monitor dbl wall tank space
 
 
Tank Tank Size Content Installed Placement Status
1 10000 Vehicular Diesel (D) 07/01/1968 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (B) Steel/galvanized metal (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
2 10000 Leaded Gas (A) 07/01/1968 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(D) Unknown   (B) Steel/galvanized metal (Y) Unknown
 
 
Tank Tank Size Content Installed Placement Status
3 8000 New/Lube Oil (O) 01/01/1986 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
  (C) Fiberglass
(I) Suction piping system
(8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
4 12000 Vehicular Diesel (D) 11/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(8) Manually sampled wells
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
5 12000 Vehicular Diesel (D) 11/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(8) Manually sampled wells
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
6 10000 Vehicular Diesel (D) 11/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
7 1000 Waste Oil (L) 11/01/1989 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(J) Pressurized piping system
(M) Double wall - pipe jacket
(I) Not required
 
 
Tank Tank Size Content Installed Placement Status
8 500 New/Lube Oil (O) 12/01/2009 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(N) Flow shut-Off
  (B) Steel/galvanized metal
(I) Suction piping system
(Q) Visual inspection of ASTs
(V) Suction pump check valve
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   10/01/2019 10/01/2020 ILLINOIS UNION INSURANCE COMPANY
INSURANCE   10/01/2018 10/01/2019 OLD REPUBLIC
INSURANCE   10/01/2017 10/01/2018 OLD REPUBLIC
INSURANCE   10/01/2015 10/01/2016 OLD REPUBLIC
INSURANCE   10/01/2014 10/01/2015 OLD REPUBLIC
INSURANCE   10/01/2013 10/01/2014 OLD REPUBLIC
INSURANCE   09/26/2011 09/26/2012 OLD REPUBLIC
INSURANCE   10/01/2010 10/01/2011 OLD REPUBLIC
INSURANCE   10/01/2009 10/01/2010 OLD REPUBLIC
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 07/18/2005 07/21/2005 IN-COMPLIANCE DJ 1/4 COMPLIANCE ASSURANCE
 
TCI 07/20/2004 08/03/2004 IN-COMPLIANCE MOSER_T 1/4 COMPLIANCE ASSURANCE
 
TCI 07/22/2003 07/23/2003 IN-COMPLIANCE DJ 1/4 COMPLIANCE ASSURANCE
 
RRBD 08/28/2002 08/29/2002 COMPLIANCE ASSURANCE
 
CALL 08/26/2002 08/26/2002 DJ 1/4 COMPLIANCE ASSURANCE
 
TCI 07/19/2002 07/19/2002 MINOR OUT-OF-COMPLIANCE DJ 1/4 COMPLIANCE ASSURANCE
 
TCI 07/19/2001 07/24/2001 IN-COMPLIANCE MOSER_T 1/4 COMPLIANCE ASSURANCE
 
TCI 08/03/2000 08/04/2000 IN-COMPLIANCE LLW 1/4 COMPLIANCE ASSURANCE
 
TCI 07/28/1999 08/02/1999 IN-COMPLIANCE VANDERBLEE_R 1/4 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 06/03/2024 Accepted GREGORY_JW_1 Enforcement
 
Electronic Communication 03/29/2024 Satisfied PIERCE_BN_1 Closure
 
Letter 03/27/2024 Satisfied GREGORY_JW_1 Compliance Assistance
 
Electronic Communication 03/25/2024 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 12/05/2023 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 11/08/2023 Satisfied PIERCE_BN_1 Compliance Assistance
 
Site Inspection 11/06/2023 Major Out of Compliance PIERCE_BN_1 1/0 Installation
 
Letter 11/06/2023 Satisfied PIERCE_BN_1 Compliance Assistance
 
Letter 11/01/2023 Satisfied PIERCE_BN_1 Compliance Assistance
 
Site Inspection 10/13/2023 Major Out of Compliance PIERCE_BN_1 1/0 Routine Compliance
 
Electronic Communication 09/19/2023 Satisfied PIERCE_BN_1 Routine Compliance
 
Electronic Communication 12/07/2022 Satisfied BECKER_GT_1 Installation
 
Document Management 08/10/2021 Satisfied RAUENZAHN_RA_1 Closure
 
Document Management 07/26/2021 Satisfied RAUENZAHN_RA_1 Closure
 
Letter 06/23/2020 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 06/23/2020 Satisfied PIERCE_BN_1 Compliance Assistance
 
Document Management 06/09/2020 Satisfied RAUENZAHN_RA_1 Closure
 
Record Document 04/27/2020 Satisfied PIERCE_BN_1 Closure
 
Letter 04/27/2020 Satisfied PIERCE_BN_1 Compliance Assistance
 
Record Document 04/27/2020 Satisfied PIERCE_BN_1 Closure
 
Site Inspection 04/27/2020 Minor Out of Compliance PIERCE_BN_1 1/3 Closure
 
Electronic Communication 04/06/2020 Satisfied PIERCE_BN_1 Closure
 
Electronic Communication 04/03/2020 Satisfied PIERCE_BN_1 Closure
 
Electronic Communication 03/17/2020 Satisfied BECKER_GT_1 Closure
 
Electronic Communication 03/17/2020 Satisfied BECKER_GT_1 Closure
 
Electronic Communication 02/25/2020 Satisfied BECKER_GT_1 Closure
 
Electronic Communication 02/25/2020 Satisfied BECKER_GT_1 Closure
 
Electronic Communication 01/07/2020 Satisfied SAVOY_JA_1 Installation
 
Electronic Communication 08/24/2018 Satisfied BECKER_GT_1 Installation
 
Site Inspection 01/30/2018 In Compliance PERRY_JF_2 2/3 Routine Compliance
 
Letter 01/30/2018 Satisfied PERRY_JF_2 Routine Compliance
 
Site Inspection 03/11/2016 In Compliance PERRY_JF_2 1/3 Routine Compliance
 
Document Management 12/07/2015 Complete BECKER_GT_1 Non-Compliance
 
Site Inspection 02/18/2015 In Compliance BECKER_GT_1 0/1 Installation
 
Site Inspection 02/18/2015 In Compliance BECKER_GT_1 0/1 Closure
 
Site Inspection 05/22/2014 In Compliance PERRY_JF_2 1/3 Routine Compliance
 
Emergency Preparedness Information 05/22/2014 Satisfied PERRY_JF_2 Routine Compliance
 
Site Inspection 12/15/2011 In Compliance COIL_JM_1 1/3 Routine Compliance
 
Record Document 02/21/2011 Satisfied COIL_JM_1 Non-Compliance
 
Letter 11/16/2010 Satisfied LEIGH_MM_1 Non-Compliance
 
Site Inspection 11/09/2010 Minor Out of Compliance COIL_JM_1 1/4 Routine Compliance
 
Document Management 06/08/2010 Complete LEIGH_MM_1 Discharge
 
Discharge Reporting 06/08/2010 Satisfied LEIGH_MM_1 Discharge
 
Document Management 05/25/2010 Complete LEIGH_MM_1 Closure
 
Letter 05/25/2010 Satisfied LEIGH_MM_1 Closure
 
TCAR 05/25/2010 Satisfied LEIGH_MM_1 Closure
 
Site Inspection 04/05/2010 In Compliance COIL_JM_1 1/4 Closure
 
Electronic Communication 02/22/2010 Satisfied STAFFORD_P_1 Closure
 
Meeting 12/17/2009 Satisfied STAFFORD_P_1 Closure
 
Phone Conversation 12/09/2009 Satisfied STAFFORD_P_1 Closure
 
Record Document 11/11/2009 Satisfied LEIGH_MM_1 Non-Compliance
 
Record Document 10/29/2009 Satisfied LEIGH_MM_1 Non-Compliance
 
Record Document 10/21/2009 Satisfied LEIGH_MM_1 Non-Compliance
 
Letter 10/14/2009 Satisfied COIL_JM_1 Non-Compliance
 
Site Inspection 10/12/2009 Minor Out of Compliance COIL_JM_1 1/4 Routine Compliance
 
Meeting 01/06/2009 Satisfied LEIGH_MM_1 Non-Compliance
 
Record Document 12/30/2008 Satisfied LEIGH_MM_1 Non-Compliance
 
Record Document 12/29/2008 Satisfied LEIGH_MM_1 Non-Compliance
 
Record Document 12/22/2008 Satisfied LEIGH_MM_1 Non-Compliance
 
Letter 12/12/2008 Satisfied LEIGH_MM_1 Non-Compliance
 
Record Document 10/23/2008 Satisfied LEIGH_MM_1 Non-Compliance
 
Letter 10/15/2008 Satisfied LEIGH_MM_1 Non-Compliance
 
Site Inspection 10/02/2008 Major Out of Compliance COIL_JM_1 0/4 Routine Compliance
 
Record Document 09/18/2007 Satisfied LEIGH_MM_1 Routine Compliance
 
Record Document 08/30/2007 Satisfied LEIGH_MM_1 Non-Compliance
 
Letter 08/29/2007 Satisfied LEIGH_MM_1 Non-Compliance
 
Record Document 08/29/2007 Satisfied LEIGH_MM_1 Non-Compliance
 
Site Inspection 08/20/2007 Major Out of Compliance SHIELDS_DJ 1/4 Routine Compliance
 
Record Document 07/25/2007 Satisfied LEIGH_MM_1 Non-Compliance
 
Record Document 06/20/2007 Satisfied LEIGH_MM_1 Discharge
 
Phone Conversation 06/20/2007 Satisfied MOSER_T Installation
 
Site Inspection 09/08/2006 Minor Out of Compliance MOSER_T 1/6 Installation
 
Letter 07/31/2006 Satisfied LEIGH_MM_1 Non-Compliance
 
Site Inspection 07/10/2006 Minor Out of Compliance SHIELDS_DJ 1/4 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
11/06/2023 7020 Minor 1.2 Integrity Testing of secondary containment systems and interstitial spaces not performed before being placed into service. Please have an approved spill containment bucket installed on the tank. Please have a hydrostatic test completed on the spill bucket & supply testing for review.
 
11/06/2023 7031 SNC-B 3.1 Any component(s) of storage tank system not installed according to manufacturer's instructions. An onsite breach of integrity test is required after the tank is set in place. All integrity tests should be conducted in accordance with manufacturer's specifications. This can be provided by: 1) The tank holding vacuum for at least one hour following being set in place 2) An onsite pressure testing showing the tank secondary holds for at least one hour *Please have the testing completed, or supply testing records from the time of installation.
 
11/06/2023 7110 Minor 1.16 Equipment not registered with DEP before installation or use. 1) Please reach out to the tank manufacturer requesting an updated equipment registration is submitted for the tank. 2) Please arrange for an approved spill containment bucket to be installed. Please supply the approved equipment # once complete. Approved equipment can be found at this link: https://floridadep.gov/waste/permitting-compliance-assistance/documents/storage-tank-equipment-approvalregistration-list.
 
11/03/2023 7050 SNC-B 3.7 Aboveground storage tank system relocation requirements not met, not properly recertified, or does not meet current standards. Please provide documentation that the AST has been installed in accordance with STI SP001 standards. The required SP001 form will be supplied to the facility contact.
 
10/13/2023 7043 Minor 1.11 Fillbox covers not marked according to requirements. Please label the AST with a "DIESEL" sign. Please supply a picture for review once complete.
 
10/13/2023 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. Please immediately begin completing the monthly visual inspections of the tank. A visual inspection form will be emailed to the facility contact. Please submit the next two months of inspections as completed. Visual inspections must be conducted & documented every 30-35 days. Please maintain records for up to three years for future inspection purposes.
 
10/13/2023 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Please supply post-installation testing, or arrange for current testing to be performed. Please supply records for review.
 
10/13/2023 7042 SNC-B 3.9 Storage tank system not installed with a spill containment system at each tank fill connection. Does not meet performance requirements. Please arrange for an approved spill containment bucket to be installed. A hydrostatic test is required for spill containment installations. Please supply testing and pictures of the new spill containment installed.
 
10/13/2023 7011 Minor 1.9 Appropriate paperwork for financial responsibility improperly completed or maintained. Please supply insurance coverage from the time of installation - present.
 
10/13/2023 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Please supply post-installation testing, or arrange for current testing to be performed. Please supply records for review.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
04/13/2007   COMPLETED 5
 
11/26/1989   INACTIVE 5 PETROLEUM CLEANUP PARTICIPATION PROGRAM-ELIGIBLE
 
11/26/1989   INACTIVE 5