Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Central | Type | Retail Station | ||||||||
County | Volusia | Status | OPEN | ||||||||
ID | 8622851 | Latitude | 29° 7' 19.7 | ||||||||
Name |
VALERO 5145 N HWY 17 N |
Longitude | 81° 21' 5.48 | ||||||||
DELEON SPRINGS, FL 32130 | LL Method | DPHO | |||||||||
Contact | MOHAMMED UDDIN | LL Status | REVIEWED | ||||||||
Phone | (386) 985-0704 | Status Date | 07/18/2005 | ||||||||
Account Owner Information | |||||||||||
Name | MOHAMMED AZAM 5145 HWY 17 N DELEON SPRINGS, FL 32130 |
Effective Date | 11/06/2003 | ||||||||
Contact | MOHAMMED AZAM | ||||||||||
Phone | (386) 689-0178 | ||||||||||
ZAMAN1430@HOTMAIL.COM | |||||||||||
Placard # / Date | 700996 - 08/26/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | TRICIA AZAM & MOHAMMED UDDIN & MOSAMMAT YEASMIN 370 LAFAYETTE PL DELAND, FL 32720 |
Effective Date | 03/30/2017 | ||||||||
Contact | |||||||||||
Phone | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
8 | 18000 | Vehicular Diesel (D) | 04/01/2009 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (L) Compartmented (M) Spill containment bucket (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (I) Suction piping system (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (5) Electronic monitor dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
9 | 4000 | Unleaded Gas (B) | 05/01/2010 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (P) Level gauges/alarms (R) Double wall - tank jacket |
(A) Abv, no soil contact (B) Steel/galvanized metal (J) Pressurized piping system |
(3) Electronic monitor pipe sumps (F) Monitor dbl wall tank space (H) Mechanical line leak detector (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 3000 | Leaded Gas (A) | 07/01/1960 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 3000 | Leaded Gas (A) | 07/01/1960 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 4000 | Unleaded Gas (B) | 07/01/1960 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 4000 | Unleaded Gas (B) | 07/01/1975 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal | (8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 6000 | Unleaded Gas (B) | 06/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(H) Mechanical line leak detector (P) Vapor monitoring w/dilution |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 6000 | Unleaded Gas (B) | 06/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(H) Mechanical line leak detector (P) Vapor monitoring w/dilution |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 6000 | Vehicular Diesel (D) | 06/01/1989 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (F) Fiberglass clad steel (M) Spill containment bucket |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(H) Mechanical line leak detector (P) Vapor monitoring w/dilution |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 10/28/2023 | 10/28/2024 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 10/28/2022 | 10/28/2023 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 10/28/2021 | 10/28/2022 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/28/2020 | 10/28/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/28/2019 | 10/28/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/28/2018 | 10/28/2019 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/28/2017 | 10/28/2018 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/28/2016 | 10/28/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/28/2014 | 10/28/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/28/2011 | 10/28/2012 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/28/2010 | 10/28/2011 | GULF UNDERWRITERS | ||||||||
INSURANCE | 10/28/2008 | 10/28/2009 | ZURICH-AMERICAN | ||||||||
INSURANCE | 02/15/1992 | 03/15/1996 | FPLIPA | ||||||||
INSURANCE | 12/31/1990 | 12/31/1991 | FPLIPA | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
RRBD | 06/14/2005 | 06/14/2005 | COMPLIANCE ASSURANCE | ||||||||
RRBD | 06/10/2005 | 06/10/2005 | COMPLIANCE ASSURANCE | ||||||||
TCI | 05/31/2005 | 06/03/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | TLM | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes FINAN. RESPONS. NOT AVAILABLE. DIESEL AND ALL SWING JOINTS IN CONTACT. UNL SHEAR VALVE IN S. DISPENSER MAY NOT FUNCTION AS DESIGNED ON IMPACT. | |||||||||||
CWOE | 10/28/2004 | 10/28/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes ACCEPTED THE SUBMITTED SIRS FOR THE INVENTORY REPORT. NFA CONCERNING THE LATEST TCI. | |||||||||||
RRBD | 10/26/2004 | 10/28/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED SIR REPORTS FOR THE LAST 3 MONTHS. FACILITY JUST STARTED USING SIRS. | |||||||||||
WLI | 10/25/2004 | 10/26/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes COULD NOT GET THE PROPER INFO FROM FACILITY. | |||||||||||
RRBD | 10/22/2004 | 10/25/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED RD BOOKLET FOR FACILITY FROM IRA WILSON. RDRL AVAILABLE, VISUALS PROVIDED FOR 2004 ONLY. NEW OPERATOR, RECORDS NOT AVAILABLE FOR 2003. INVENTORY PROVIDED NOT ACCEPTABLE. SHOWS DELAND AND NOT DELEON SPRINGS FACILITY. | |||||||||||
RRBD | 09/26/2004 | 10/13/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED FAX INDICATING THE TANKS, LINES AND LLD'S WERE TESTED AND PASSED. | |||||||||||
WLI | 08/27/2004 | 08/27/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes NO FURTHER RESPONSE FROM FACILLITY. | |||||||||||
RRBD | 06/24/2004 | 06/24/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED LETTER FROM WILSON'S PUMP INDICATING THE NONCOMPLIANCE ITEMS WILL BE ADDRESSED WITHIN 2 WEEKS. | |||||||||||
NCLI | 06/08/2004 | 06/08/2004 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes MAILED NCLI - NO RESPONSE FDROM FACILITY. | |||||||||||
TCI | 06/03/2004 | 06/03/2004 | MINOR OUT-OF-COMPLIANCE | DJ | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO VISUAL RECORDS AVAILABLE PREVIOUS TO JAN. 2004. RDRL NOT AVAILABLE- PROVIDED FACILITY W/ BOOKLET. INVENTORY RECORDS AVAILABLE FROM DEC. 03 ONLY. LLD'S REQUIRE ANNUAL TEST. TANK TIGHTNESS TEST REQUIRED. | |||||||||||
TCR | 06/12/2003 | 06/12/2003 | IN-COMPLIANCE | DJ | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes REINSPECTION INDICATED THE GWMW'S WERE PROPERLY ABANDONED. NFA REQUIRED FOR THIS SITE PERTAINING TO THE NONCOMPLIANCE ISSUE OF THE WELLS. | |||||||||||
RRBD | 05/05/2003 | 05/07/2003 | DJ | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED DOCUMENTATION WORK TO BE COMPLETED AT FACILITY CONCERNING VIOLATIONS. FACILITY OPERATOR TO CONTACT THIS DEPT. WHEN COMPLETION OF WORK IS DONE. | |||||||||||
TCI | 04/10/2003 | 04/10/2003 | MINOR OUT-OF-COMPLIANCE | TM | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes GWMW'S ARE NOT USED FOR RELEASE DETECTION AND SHOULD BE ABANDONED. | |||||||||||
TCI | 04/23/2002 | 04/23/2002 | IN-COMPLIANCE | DJ | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 05/27/2001 | 06/05/2001 | COMPLIANCE ASSURANCE | ||||||||
TCI | 04/12/2001 | 04/26/2001 | MINOR OUT-OF-COMPLIANCE | LLW | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 06/22/2000 | 06/22/2000 | IN-COMPLIANCE | LLW | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 06/01/1999 | 07/06/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | MOSER_T | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 03/03/2025 | Satisfied | DEVICTORIA_F | Enforcement | |||||||
Enforcement Referral | 11/06/2024 | Accepted | RIVERA_JX_2 | Enforcement | |||||||
Electronic Communication | 08/22/2024 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Phone Conversation | 06/13/2024 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Letter | 04/22/2024 | Satisfied | COX_CD_1 | Compliance Assistance | |||||||
Site Inspection | 04/22/2024 | Minor Out of Compliance | COX_CD_1 | 1/1 | Routine Compliance | ||||||
Electronic Communication | 04/22/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 04/09/2024 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Phone Conversation | 03/19/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Phone Conversation | 03/19/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Phone Conversation | 03/19/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Electronic Communication | 03/15/2024 | Satisfied | COX_CD_1 | Routine Compliance | |||||||
Phone Conversation | 10/12/2022 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Electronic Communication | 10/11/2022 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Letter | 03/21/2022 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Site Inspection | 03/16/2022 | Minor Out of Compliance | PIERCE_BN_1 | 1/1 | Routine Compliance | ||||||
Electronic Communication | 03/01/2022 | Satisfied | PIERCE_BN_1 | Routine Compliance | |||||||
Letter | 03/08/2021 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Electronic Communication | 12/08/2020 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Electronic Communication | 07/09/2020 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Electronic Communication | 06/08/2020 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Letter | 03/02/2020 | Satisfied | PIERCE_BN_1 | Compliance Assistance | |||||||
Site Inspection | 02/18/2020 | Major Out of Compliance | PIERCE_BN_1 | 1/1 | Routine Compliance | ||||||
Electronic Communication | 01/31/2020 | Satisfied | PIERCE_BN_1 | Routine Compliance | |||||||
Site Inspection | 03/14/2017 | In Compliance | PERRY_JF_2 | 1/1 | Routine Compliance | ||||||
Electronic Communication | 02/22/2017 | Satisfied | PERRY_JF_2 | Routine Compliance | |||||||
Letter | 02/26/2015 | Satisfied | RAUENZAHN_RA_1 | Non-Compliance | |||||||
Site Inspection | 02/18/2015 | Minor Out of Compliance | PERRY_JF_2 | 1/1 | Routine Compliance | ||||||
Letter | 02/18/2015 | Satisfied | PERRY_JF_2 | Non-Compliance | |||||||
Emergency Preparedness Information | 02/04/2015 | Satisfied | PERRY_JF_2 | Routine Compliance | |||||||
Enforcement Tracking | 02/18/2013 | Closed Without Enforcement | MARTIN_G | Enforcement | |||||||
Site Inspection | 04/19/2012 | In Compliance | COIL_JM_1 | 1/1 | Routine Compliance | ||||||
Emergency Preparedness Information | 04/13/2012 | Satisfied | COIL_JM_1 | Routine Compliance | |||||||
Phone Conversation | 03/28/2012 | Satisfied | COIL_JM_1 | Routine Compliance | |||||||
Phone Conversation | 03/28/2012 | Satisfied | COIL_JM_1 | Routine Compliance | |||||||
Site Inspection | 10/28/2010 | In Compliance | CRAFT_TT_1 | 1/1 | Routine Compliance | ||||||
Site Inspection | 08/02/2010 | In Compliance | CRAFT_TT_1 | 0/1 | Installation | ||||||
Enforcement Referral | 11/16/2009 | Accepted | MARTIN_G | Enforcement | |||||||
Site Inspection | 08/07/2009 | Minor Out of Compliance | CRAFT_TT_1 | 0/1 | Routine Compliance | ||||||
Site Inspection | 08/07/2009 | In Compliance | CRAFT_TT_1 | 0/1 | Installation | ||||||
Phone Conversation | 07/22/2009 | Satisfied | STAFFORD_P_1 | Installation | |||||||
Record Document | 06/26/2009 | Satisfied | STAFFORD_P_1 | Installation | |||||||
Record Document | 04/23/2009 | Satisfied | STAFFORD_P_1 | Installation | |||||||
Record Document | 04/14/2009 | Satisfied | COIL_JM_1 | Non-Compliance | |||||||
Record Document | 03/31/2009 | Satisfied | STAFFORD_P_1 | Installation | |||||||
Site Inspection | 03/16/2009 | Minor Out of Compliance | STAFFORD_P_1 | 0/3 | Closure | ||||||
Phone Conversation | 01/29/2009 | Satisfied | LEIGH_MM_1 | Closure | |||||||
Record Document | 05/27/2008 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Record Document | 05/21/2008 | Satisfied | MARTIN_G | QA/QC | |||||||
Record Document | 05/16/2008 | Satisfied | LANGFORD_M | QA/QC | |||||||
Record Document | 05/14/2008 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Letter | 05/08/2008 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Site Inspection | 05/07/2008 | Major Out of Compliance | MARTIN_G | 0/3 | QA/QC | ||||||
Site Inspection | 04/10/2008 | Major Out of Compliance | MOSER_T | 0/3 | Routine Compliance | ||||||
Letter | 06/15/2007 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Site Inspection | 06/14/2007 | In Compliance | MOSER_T | 0/3 | Non-Compliance | ||||||
Record Document | 06/01/2007 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Site Inspection | 04/18/2007 | Major Out of Compliance | MOSER_T | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 02/14/2007 | Satisfied | LEIGH_MM_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/20/2006 | Satisfied | MOSER_T | Routine Compliance | |||||||
Letter | 08/04/2006 | Satisfied | LEIGH_MM_1 | Non-Compliance | |||||||
Site Inspection | 05/23/2006 | Minor Out of Compliance | MOSER_T | 0/3 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
04/22/2024 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Have the overfill protection for both tank systems tested; UST flapper valves and AST high level alarm. | |||||||
04/22/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Send proof of the required annual testing of the monitoring system and the line leak detectors. | |||||||
04/19/2024 | 7043 | Minor | 1.11 Fillbox covers not marked according to requirements. | Off road diesel should be labeled by a yellow circle with red "OFF" or the words "Off-Road". Non ethanol gasoline is labeled by a blue circle and white zero or the words "Midgrade E0 gasoline" or "Premium E0 gasoline"... | |||||||
04/19/2024 | 6013 | Minor | 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. | Forward proof of either form C or form D (depending on what you received from the insurance company) to Orange County. Fill out form P, based on the form C or D that you receive. Forward proof of this to Orange County. | |||||||
04/19/2024 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Remove the water from the regular STP sump. Remove approximately 2 inches of soil from around the sump lid to allow the lid to fit and water to absorb into the soil. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
06/05/1985 | ACTIVE | 56 | EARLY DETECTION INCENTIVE-ELIGIBLE | SWANSON, TINA | 3216332017 | ||||||