DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Pinellas   Status    OPEN
 
ID 8623466   Latitude    28° 4' 1.7873
 
Name CIRCLE K #7495
3414 TAMPA RD
Longitude    82° 43' 16.6789
  PALM HARBOR, FL 34684-3530 LL Method    DPHO
 
Contact Ira Lewis   LL Status    REVIEWED
 
Phone (984) 389-1300   Status Date    09/09/2024
 
Account Owner Information
 
Name CIRCLE K STORES INC
1100 Situs Ct
Raleigh, NC 27606-5446
Effective Date    05/20/1994
 
Contact IRA LEWIS
 
Phone (423) 400-2480
 
Email ILEWIS@CIRCLEK.COM
  Placard # / Date    697683 - 06/28/2024
Property Owner Information
 
Name CIRCLE K STORES INC
1100 Situs Ct
Raleigh, NC 27606-5446
Effective Date    11/20/2020
 
Contact IRA LEWIS
 
Phone (423) 400-2480
 
Email ILEWIS@CIRCLEK.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 10000 Unleaded Gas (B) 05/01/1985 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(H) Impressed current CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(S) DEP approved containment
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
2 10000 Unleaded Gas (B) 05/01/1985 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(H) Impressed current CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(S) DEP approved containment
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
3 10000 Unleaded Gas (B) 05/01/1985 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(H) Impressed current CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(S) DEP approved containment
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
4 10000 Unleaded Gas (B) 05/01/1985 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(H) Impressed current CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(S) DEP approved containment
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
FULLY FUNDED TRUST   08/21/2023 08/26/2025
GUARANTEE   04/24/2022 08/21/2023
GUARANTEE   04/25/2021 08/27/2022
INSURANCE   12/01/2020 12/01/2021 NAVIGATORS SPECIALTY INSURANCE CO
INSURANCE   12/01/2019 12/01/2020 NAVIGATORS SPECIALTY INSURANCE CO
INSURANCE   12/01/2018 12/01/2019 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2017 12/01/2018 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2016 12/01/2017 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2015 12/01/2016 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2011 12/01/2013 CHUBB
INSURANCE   12/17/2010 12/17/2011 CHUBB
INSURANCE   12/17/2009 12/17/2010 CHUBB
INSURANCE   12/17/2008 12/17/2009 AMERICAN INTERNATIONAL SPECIALTY LINES
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
RRBD 04/06/2006 04/17/2006 BARNETT 0/0 COMPLIANCE ASSURANCE
 
NCLI 03/01/2006 03/01/2006 BARNETT 0/0 COMPLIANCE ASSURANCE
 
TCI 02/27/2006 03/01/2006 SIGNIFICANT OUT-OF-COMPLIANCE BARNETT 0/4 COMPLIANCE ASSURANCE
 
LTR 07/11/2005 08/09/2005 ROGGELIN 0/0 COMPLIANCE ASSURANCE
 
TCI 06/22/2005 07/01/2005 IN-COMPLIANCE ROGGELIN 0/4 COMPLIANCE ASSURANCE
 
RRBD 05/21/2004 06/14/2004 BARNETT 0/0 COMPLIANCE ASSURANCE
 
NCLI 04/23/2004 04/29/2004 BARNETT 0/0 COMPLIANCE ASSURANCE
 
TCI 04/19/2004 04/29/2004 SIGNIFICANT OUT-OF-COMPLIANCE BARNETT 0/4 COMPLIANCE ASSURANCE
 
RRBD 12/11/2002 01/03/2003 COMPLIANCE ASSURANCE
 
NCLI 11/03/2002 11/05/2002 TAM 0/0 COMPLIANCE ASSURANCE
 
TCI 11/01/2002 11/05/2002 MINOR OUT-OF-COMPLIANCE TAM 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes AMERON DW FRP PIPE
 
TCI 09/04/2001 09/09/2001 IN-COMPLIANCE HALSCOTT 0/4 COMPLIANCE ASSURANCE
 
RRBD 10/06/2000 10/30/2000 HALSCOTT 0/0 COMPLIANCE ASSURANCE
 
TCI 10/05/2000 10/17/2000 MINOR OUT-OF-COMPLIANCE HALSCOTT 0/4 COMPLIANCE ASSURANCE
 
TCI 05/10/2000 05/22/2000 IN-COMPLIANCE CASTOR 0/4 COMPLIANCE ASSURANCE
 
RRBD 01/28/1999 03/02/1999 PUGH 0/4 COMPLIANCE ASSURANCE
 
TCI 01/15/1999 02/25/1999 MINOR OUT-OF-COMPLIANCE PUGH_R 0/4 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Record Document 10/04/2024 Satisfied MUSLIC_A_1 Compliance Assistance
 
Record Document 09/20/2024 Satisfied MUSLIC_A_1 Compliance Assistance
 
Letter 08/30/2024 Satisfied MUSLIC_A_1 Compliance Assistance
 
Site Inspection 08/30/2024 Major Out of Compliance MUSLIC_A_1 0/3 Routine Compliance
 
Letter 08/28/2024 Satisfied WIMBERLY_E Enforcement
 
Electronic Communication 07/31/2024 Satisfied MUSLIC_A_1 Routine Compliance
 
Incident 12/01/2023 Has not led to Discharge SHOCK_E_1 Incident
 
Record Document 09/19/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Enforcement Referral 08/24/2023 Accepted SHOCK_E_1 Enforcement
 
Electronic Communication 08/18/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Record Document 06/21/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Site Inspection 02/23/2023 Major Out of Compliance SHOCK_E_1 0/3 Routine Compliance
 
Letter 02/23/2023 Satisfied SHOCK_E_1 Compliance Assistance
 
Electronic Communication 01/30/2023 Satisfied SHOCK_E_1 Routine Compliance
 
Incident 01/10/2022 Has not led to Discharge HAUSCHILD_TW_1 Incident
 
Record Document 11/25/2020 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Letter 11/25/2020 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Document Management 11/20/2020 Satisfied STRAUSS_RH_1 Incident
 
Site Inspection 09/25/2020 Minor Out of Compliance STRAUSS_RH_1 0/3 Routine Compliance
 
Letter 09/25/2020 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Electronic Communication 09/18/2020 Satisfied STRAUSS_RH_1 Routine Compliance
 
Record Document 11/19/2018 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Letter 09/06/2018 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Site Inspection 05/02/2018 Minor Out of Compliance STRAUSS_RH_1 0/3 Routine Compliance
 
Letter 05/02/2018 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Electronic Communication 12/28/2015 Satisfied STRAUSS_RH_1 Installation
 
Site Inspection 12/28/2015 In Compliance STRAUSS_RH_1 0/3 Installation
 
Site Inspection 12/28/2015 In Compliance STRAUSS_RH_1 0/3 Closure
 
Incident 12/28/2015 Has not led to Discharge STRAUSS_RH_1 Incident
 
Electronic Communication 12/28/2015 Satisfied STRAUSS_RH_1 Closure
 
Electronic Communication 12/28/2015 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 12/28/2015 In Compliance STRAUSS_RH_1 0/3 Non-Compliance
 
Letter 12/03/2015 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 12/03/2015 Minor Out of Compliance STRAUSS_RH_1 0/3 Routine Compliance
 
Electronic Communication 11/30/2015 Satisfied STRAUSS_RH_1 Routine Compliance
 
Electronic Communication 10/17/2013 Satisfied JUEDES_HC_1 Non-Compliance
 
Site Inspection 10/17/2013 In Compliance JUEDES_HC_1 0/3 Non-Compliance
 
Letter 09/09/2013 Satisfied JUEDES_HC_1 Non-Compliance
 
Site Inspection 09/09/2013 Minor Out of Compliance JUEDES_HC_1 0/3 Routine Compliance
 
Emergency Preparedness Information 09/06/2013 Satisfied JUEDES_HC_1 Routine Compliance
 
Site Inspection 08/05/2011 In Compliance LONGEN_JL_1 0/3 Routine Compliance
 
Emergency Preparedness Information 08/05/2011 Satisfied LONGEN_JL_1 Routine Compliance
 
Record Document 09/03/2010 Satisfied LONGEN_JL_1 Non-Compliance
 
Incident 07/22/2010 Has not led to Discharge LONGEN_JL_1 Incident
 
Letter 07/16/2010 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 07/16/2010 Minor Out of Compliance LONGEN_JL_1 0/3 Routine Compliance
 
Record Document 05/29/2009 Satisfied LONGEN_JL_1 Non-Compliance
 
Letter 05/15/2009 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 05/15/2009 Minor Out of Compliance LONGEN_JL_1 0/3 Routine Compliance
 
Site Inspection 01/07/2008 In Compliance ROGGELIN_EM_1 0/4 Closure
 
Site Inspection 01/07/2008 In Compliance ROGGELIN_EM_1 0/3 Installation
 
TCAR 08/28/2007 Satisfied STRAUSS_RH_1 Closure
 
Emergency Preparedness Information 02/09/2007 Satisfied STRAUSS_RH_1 Routine Compliance
 
Site Inspection 02/07/2007 In Compliance ROGGELIN_EM_1 0/1 Non-Compliance
 
Letter 01/05/2007 Satisfied SOWERS_JA_1 Non-Compliance
 
Site Inspection 01/02/2007 Major Out of Compliance SOWERS_JA_1 0/4 Routine Compliance
 
Emergency Preparedness Information 09/19/2006 Satisfied BARNETT_JX Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
08/29/2024 6077 Minor 4.8 Out of service storage tank systems not tested annually for operability or interstice and liquid level not monitored annually. Remove all PCW from tank and submit proof of compliance (waste manifest, photo documentation, and liquid level documentation showing that the liquid level in Tank 1 is less than 1 inch). Alternatively, conduct system operability and integrity tests and change tank registration to in service status.
 
08/29/2024 6057 SNC-B 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. Properly position liquid sensor vertically on the bottom of the sump and submit photo documentation as proof of compliance.
 
02/23/2023 6003 Minor 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Confirm that the "Out of Service" status for FDEP Tank 1 is correct, or complete registration update to correct status. Also, update facility information contact.
 
02/23/2023 6057 SNC-B 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. The Veeder-Root sensor in the bottom of the RUL-W STP sump should be returned to, and maintained in, an upright position for proper function. Provide documentation that the sensor has been reset in a proper operating position. Complete an investigation to determine the cause for the recent alarms of the L1 sensor for the RUL-E Tank 1 interstice it was in alarm for most of the monthly inspections in 2022 and provide results. (This appears to be the tank that failed integrity testing twice in 2021.)
 
02/23/2023 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove liquids from PUL STP sump and the RUL-W secondary spill bucket. Complete an investigation to determine the contents of the liquid and the source. Confirm the integrity of the secondary containment and the operability of the sensor. Provide documentation of liquid removal and the results of the investigation.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
04/15/1997   COMPLETED 10
 
09/13/1988   COMPLETED 10 EARLY DETECTION INCENTIVE-ELIGIBLE