DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Pinellas   Status    OPEN
 
ID 8623571   Latitude    27° 46' 16.9154
 
Name SHELL-SAM'S
1517 CENTRAL AVE
Longitude    82° 39' 16.7622
  SAINT PETERSBURG, FL 33705-1657 LL Method    DPHO
 
Contact AMANI NAGIB   LL Status    REVIEWED
 
Phone (727) 823-0960   Status Date    09/30/2003
 
Account Owner Information
 
Name SHELL STATION
1517 CENTRAL AVE
SAINT PETERSBURG, FL 33705-1657
Effective Date    03/29/1991
 
Contact AMANI NAGIB
 
Phone (727) 409-4177
 
Email AMY.W.0521@GMAIL.COM
  Placard # / Date    680354 - 06/05/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
6 30000 Unleaded Gas (B) 04/01/2006 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 4000 Unleaded Gas (B) 05/01/1963 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
2 3000 Unleaded Gas (B) 05/01/1963 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
3 4000 Unleaded Gas (B) 05/01/1963 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
4 5000 Unleaded Gas (B) 07/01/1972 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(C) Steel
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
5 550 Waste Oil (L) 05/01/1963 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (D) External protective coating (M) Manual tank gauging - USTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   06/30/2023 06/30/2024 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   06/30/2022 06/30/2023 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   06/30/2021 06/30/2022 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   06/30/2020 06/30/2021 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   06/30/2019 06/30/2020 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   06/30/2017 06/30/2018 COMMERCE & INDUSTRY
INSURANCE   06/30/2016 06/30/2017 COMMERCE & INDUSTRY
INSURANCE   06/30/2015 06/30/2016 COMMERCE & INDUSTRY
INSURANCE   06/30/2014 06/30/2015 COMMERCE & INDUSTRY
INSURANCE   06/30/2013 06/30/2014 COMMERCE & INDUSTRY
INSURANCE   06/30/2012 06/30/2013 ZURICH-AMERICAN
INSURANCE   06/30/2011 06/30/2012 ZURICH-AMERICAN
INSURANCE   06/30/2010 06/30/2011 ZURICH-AMERICAN
INSURANCE   06/30/2009 06/30/2010 ZURICH-AMERICAN
INSURANCE   06/30/2008 06/30/2009 ZURICH-AMERICAN
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
LTR 03/29/2006 03/29/2006 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
TXI 03/23/2006 03/29/2006 IN-COMPLIANCE FRAZIER 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes 4 USTS FILLED IN PLACE W/FLOWABLE MATERIAL
 
RRBD 12/21/2005 12/21/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
RRBD 12/07/2005 12/30/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes NO CORRECTIONS ENTERED; VIOLATIONS ALREADY CLOSED
 
NCLI 11/17/2005 11/21/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
TCI 11/17/2005 11/21/2005 SIGNIFICANT OUT-OF-COMPLIANCE FRAZIER 0/4 COMPLIANCE ASSURANCE
 
RRBD 10/20/2004 10/20/2004 COMPLIANCE ASSURANCE
 
TCI 08/10/2004 08/31/2004 SIGNIFICANT OUT-OF-COMPLIANCE BARNETT 0/4 COMPLIANCE ASSURANCE
 
NCLI 08/10/2004 08/31/2004 BARNETT 0/0 COMPLIANCE ASSURANCE
 
LTR 12/22/2003 12/29/2003 PINK 0/0 COMPLIANCE ASSURANCE
 
TCR 12/19/2003 12/29/2003 IN-COMPLIANCE PINK 0/4 COMPLIANCE ASSURANCE
 
RRBD 12/17/2003 12/29/2003 PINK 0/0 COMPLIANCE ASSURANCE
 
NCLI 12/15/2003 12/17/2003 PINK 0/0 COMPLIANCE ASSURANCE
 
TCI 12/12/2003 12/17/2003 SIGNIFICANT OUT-OF-COMPLIANCE PINK 0/4 COMPLIANCE ASSURANCE
 
 Completion Notes PIPING TYPE NOT VISIBLE
 
RRBD 08/01/2002 08/29/2002 COMPLIANCE ASSURANCE
 
NCLI 07/05/2002 07/09/2002 STRAUSS 0/0 COMPLIANCE ASSURANCE
 
TCI 07/02/2002 07/09/2002 MINOR OUT-OF-COMPLIANCE STRAUSS 0/4 COMPLIANCE ASSURANCE
 
TCR 10/12/2001 10/29/2001 IN-COMPLIANCE TAM 0/4 COMPLIANCE ASSURANCE
 
NCLI 07/30/2001 07/30/2001 COMPLIANCE ASSURANCE
 
RRBD 07/26/2001 07/30/2001 COMPLIANCE ASSURANCE
 
RRBD 07/11/2001 07/17/2001 COMPLIANCE ASSURANCE
 
TCI 07/03/2001 07/09/2001 SIGNIFICANT OUT-OF-COMPLIANCE SOWERS 0/4 COMPLIANCE ASSURANCE
 
RRBD 02/13/2001 02/15/2001 COMPLIANCE ASSURANCE
 
TCI 10/16/2000 10/17/2000 SIGNIFICANT OUT-OF-COMPLIANCE CASTOR 0/5 COMPLIANCE ASSURANCE
 
RRBD 07/06/2000 08/17/2000 SOWERS 0/0 COMPLIANCE ASSURANCE
 
RRBD 12/13/1999 02/15/2000 CASTOR 0/0 COMPLIANCE ASSURANCE
 
TCI 11/15/1999 11/22/1999 SIGNIFICANT OUT-OF-COMPLIANCE CASTOR 0/4 COMPLIANCE ASSURANCE
 
TCI 04/06/1999 04/06/1999 SIGNIFICANT OUT-OF-COMPLIANCE SOWERS 0/4 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 04/22/2024 Major Out of Compliance PUHR_NM_1 0/1 Routine Compliance
 
Letter 04/22/2024 Satisfied PUHR_NM_1 Compliance Assistance
 
Incident 02/23/2023 Has not led to Discharge COLSON_NJ_1 Incident
 
TCAR 06/09/2022 Satisfied COLSON_NJ_1 Closure
 
Letter 06/09/2022 Satisfied COLSON_NJ_1 Closure
 
Discharge Reporting 06/09/2022 Satisfied COLSON_NJ_1 Discharge
 
Record Document 06/06/2022 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 06/01/2022 Satisfied COLSON_NJ_1 Routine Compliance
 
Site Inspection 05/31/2022 Major Out of Compliance COLSON_NJ_1 0/1 Routine Compliance
 
Letter 05/31/2022 Satisfied COLSON_NJ_1 Compliance Assistance
 
Document Management 02/11/2022 Satisfied WESTERVELT_H Enforcement
 
Record Document 10/25/2021 Satisfied COLSON_NJ_1 Compliance Assistance
 
Document Management 07/14/2021 Satisfied WESTERVELT_H Enforcement
 
Site Inspection 06/29/2021 Major Out of Compliance COLSON_NJ_1 0/1 Component Closure
 
Site Inspection 06/29/2021 Major Out of Compliance COLSON_NJ_1 0/1 Component Installation
 
Site Inspection 05/15/2020 Major Out of Compliance COLSON_NJ_1 0/1 Routine Compliance
 
Letter 05/15/2020 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 04/23/2020 Satisfied COLSON_NJ_1 Routine Compliance
 
Letter 02/27/2020 Satisfied WESTERVELT_H Enforcement
 
Phone Conversation 04/09/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Record Document 04/09/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 04/02/2018 Satisfied WESTERVELT_H Enforcement
 
Enforcement Referral 03/26/2018 Accepted COLSON_NJ_1 Enforcement
 
Site Inspection 03/16/2018 Major Out of Compliance COLSON_NJ_1 0/1 Compliance Assistance
 
Electronic Communication 03/16/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Phone Conversation 02/26/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Letter 01/22/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 01/22/2018 Major Out of Compliance COLSON_NJ_1 0/1 Compliance Assistance
 
Letter 12/19/2017 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 12/19/2017 Major Out of Compliance COLSON_NJ_1 0/1 Routine Compliance
 
Electronic Communication 12/18/2017 Satisfied COLSON_NJ_1 Routine Compliance
 
Record Document 07/05/2016 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 06/29/2016 Minor Out of Compliance COLSON_NJ_1 0/1 Non-Compliance
 
Letter 06/29/2016 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 12/14/2015 Minor Out of Compliance COLSON_NJ_1 0/1 Routine Compliance
 
Letter 12/14/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Electronic Communication 11/09/2015 Satisfied COLSON_NJ_1 Routine Compliance
 
TCAR 03/10/2014 Satisfied STRAUSS_RH_1 Closure
 
Document Management 03/10/2014 Complete STRAUSS_RH_1 Closure
 
Incident 03/10/2014 Has not led to Discharge STRAUSS_RH_1 Incident
 
Site Inspection 01/06/2014 In Compliance STRAUSS_RH_1 0/1 Installation
 
Issue Document 01/06/2014 Satisfied STRAUSS_RH_1 Closure
 
Site Inspection 01/06/2014 In Compliance STRAUSS_RH_1 0/1 Non-Compliance
 
Issue Document 01/06/2014 Satisfied STRAUSS_RH_1 Installation
 
Issue Document 01/06/2014 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 01/06/2014 In Compliance STRAUSS_RH_1 0/1 Closure
 
Document Management 11/07/2013 Complete STRAUSS_RH_1 Incident
 
Letter 11/07/2013 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 11/07/2013 Minor Out of Compliance STRAUSS_RH_1 0/1 Routine Compliance
 
Record Document 05/22/2013 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 03/11/2013 Major Out of Compliance STRAUSS_RH_1 0/1 Routine Compliance
 
Letter 03/11/2013 Satisfied STRAUSS_RH_1 Non-Compliance
 
Letter 01/12/2012 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 01/12/2012 Minor Out of Compliance STRAUSS_RH_1 0/1 Routine Compliance
 
Site Inspection 01/05/2011 In Compliance STRAUSS_RH_1 0/1 Routine Compliance
 
Record Document 05/05/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Letter 01/29/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 01/29/2010 Major Out of Compliance STRAUSS_RH_1 0/1 Routine Compliance
 
Emergency Preparedness Information 01/29/2010 Satisfied STRAUSS_RH_1 Routine Compliance
 
Site Inspection 12/10/2009 In Compliance ROGGELIN_EM_1 0/1 Installation
 
Site Inspection 12/10/2009 In Compliance ROGGELIN_EM_1 0/1 Closure
 
Site Inspection 08/04/2008 In Compliance BARNETT_JX 0/1 Non-Compliance
 
Emergency Preparedness Information 07/29/2008 Satisfied BARNETT_JX Routine Compliance
 
Letter 07/29/2008 Satisfied BARNETT_JX Non-Compliance
 
Site Inspection 07/29/2008 Major Out of Compliance BARNETT_JX 0/1 Routine Compliance
 
Record Document 12/27/2007 Satisfied STRAUSS_RH_1 Non-Compliance
 
Record Document 12/19/2007 Satisfied LONGEN_JL_1 Non-Compliance
 
Record Document 12/19/2007 Satisfied STRAUSS_RH_1 Non-Compliance
 
Letter 10/01/2007 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 09/11/2007 Major Out of Compliance LONGEN_JL_1 0/1 Routine Compliance
 
Phone Conversation 02/15/2007 Satisfied ROGGELIN_EM_1 Installation
 
Emergency Preparedness Information 02/09/2007 Satisfied LONGEN_JL_1 Routine Compliance
 
TCAR 11/09/2006 Satisfied STRAUSS_RH_1 Closure
 
Emergency Preparedness Information 09/20/2006 Satisfied LONGEN_JL_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
04/22/2024 6074 Minor 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. *Submit the missing records if found. Otherwise, begin including the conditions (dry/liquid present) of the STP sumps every 6 months. Submit a monthly visual record with the STP sump conditions noted and be sure to record STP sump conditions at least once every 6 months.
 
04/22/2024 6066 Minor 4.4 Not repaired per applicable standards. *Need to treat/repair electrical conduit piping in the RUL STP Sump and continue to monitor the other sumps for worsening corrosion. Provide documentation of the repair to this office for review.
 
04/22/2024 6062 Minor 2.5 Release detection devices not tested annually. Submit past records if found; otherwise submit current operability testing for the spill bucket VisiGauges.
 
12/19/2017 4016 SNC-B 2.5 Incident investigation not initiated within 24-hours of discovery. Submit an INF, if an investigation of the incident(s) was not performed within 24 hours of the tank interstice alarm(s). Provide investigation documentation, including any integrity testing performed on the tank interstice.
 
12/19/2017 4063 SNC-B 4.7 Release detection not constructed and installed so that groundwater, rainfall, or soil moisture will not render the release detection method used inoperable. Be sure to investigate all alarms immediately. Maintain resolution documentation for the life of the storage tank system. Submit an Incident Notification Form. Remove the accumulated liquid from the tank interstice. Test the tank interstice to determine the integrity of the storage tank system. Submit test results to this office once completed.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
05/05/1986   ACTIVE 12 EARLY DETECTION INCENTIVE-ELIGIBLE