Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||
Cover Page Report | |||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||
District | Southwest | Type | Retail Station | ||||
County | Pinellas | Status | OPEN | ||||
ID | 8623571 | Latitude | 27° 46' 16.9154 | ||||
Name |
SHELL-SAM'S 1517 CENTRAL AVE |
Longitude | 82° 39' 16.7622 | ||||
SAINT PETERSBURG, FL 33705-1657 | LL Method | DPHO | |||||
Contact | AMANI NAGIB | LL Status | REVIEWED | ||||
Phone | (727) 823-0960 | Status Date | 09/30/2003 | ||||
Account Owner Information | |||||||
Name | SHELL STATION 1517 CENTRAL AVE SAINT PETERSBURG, FL 33705-1657 |
Effective Date | 03/29/1991 | ||||
Contact | AMANI NAGIB | ||||||
Phone | (727) 409-4177 | ||||||
AMY.W.0521@GMAIL.COM | |||||||
Placard # / Date | 680354 - 06/05/2024 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
6 | 30000 | Unleaded Gas (B) | 04/01/2006 | UNDERGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(F) Fiberglass clad steel (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 4000 | Unleaded Gas (B) | 05/01/1963 | UNDERGROUND | Closed In Place (A) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (B) Internal lining (C) Steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (E) Cathodic protection (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
2 | 3000 | Unleaded Gas (B) | 05/01/1963 | UNDERGROUND | Closed In Place (A) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (B) Internal lining (C) Steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (E) Cathodic protection (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
3 | 4000 | Unleaded Gas (B) | 05/01/1963 | UNDERGROUND | Closed In Place (A) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (B) Internal lining (C) Steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (E) Cathodic protection (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
4 | 5000 | Unleaded Gas (B) | 07/01/1972 | UNDERGROUND | Closed In Place (A) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (B) Internal lining (C) Steel (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (E) Cathodic protection (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
5 | 550 | Waste Oil (L) | 05/01/1963 | UNDERGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel | (D) External protective coating | (M) Manual tank gauging - USTs | |||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
INSURANCE | 06/30/2023 | 06/30/2024 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||
INSURANCE | 06/30/2022 | 06/30/2023 | COMMERCE & INDUSTRY INSURANCE CO | ||||
INSURANCE | 06/30/2021 | 06/30/2022 | COMMERCE & INDUSTRY INSURANCE CO | ||||
INSURANCE | 06/30/2020 | 06/30/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||
INSURANCE | 06/30/2019 | 06/30/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||
INSURANCE | 06/30/2017 | 06/30/2018 | COMMERCE & INDUSTRY | ||||
INSURANCE | 06/30/2016 | 06/30/2017 | COMMERCE & INDUSTRY | ||||
INSURANCE | 06/30/2015 | 06/30/2016 | COMMERCE & INDUSTRY | ||||
INSURANCE | 06/30/2014 | 06/30/2015 | COMMERCE & INDUSTRY | ||||
INSURANCE | 06/30/2013 | 06/30/2014 | COMMERCE & INDUSTRY | ||||
INSURANCE | 06/30/2012 | 06/30/2013 | ZURICH-AMERICAN | ||||
INSURANCE | 06/30/2011 | 06/30/2012 | ZURICH-AMERICAN | ||||
INSURANCE | 06/30/2010 | 06/30/2011 | ZURICH-AMERICAN | ||||
INSURANCE | 06/30/2009 | 06/30/2010 | ZURICH-AMERICAN | ||||
INSURANCE | 06/30/2008 | 06/30/2009 | ZURICH-AMERICAN | ||||
Legacy Compliance Activity Information | |||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |
LTR | 03/29/2006 | 03/29/2006 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||
TXI | 03/23/2006 | 03/29/2006 | IN-COMPLIANCE | FRAZIER | 0/4 | COMPLIANCE ASSURANCE | |
Completion Notes 4 USTS FILLED IN PLACE W/FLOWABLE MATERIAL | |||||||
RRBD | 12/21/2005 | 12/21/2005 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||
RRBD | 12/07/2005 | 12/30/2005 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes NO CORRECTIONS ENTERED; VIOLATIONS ALREADY CLOSED | |||||||
NCLI | 11/17/2005 | 11/21/2005 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 11/17/2005 | 11/21/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | FRAZIER | 0/4 | COMPLIANCE ASSURANCE | |
RRBD | 10/20/2004 | 10/20/2004 | COMPLIANCE ASSURANCE | ||||
TCI | 08/10/2004 | 08/31/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | BARNETT | 0/4 | COMPLIANCE ASSURANCE | |
NCLI | 08/10/2004 | 08/31/2004 | BARNETT | 0/0 | COMPLIANCE ASSURANCE | ||
LTR | 12/22/2003 | 12/29/2003 | PINK | 0/0 | COMPLIANCE ASSURANCE | ||
TCR | 12/19/2003 | 12/29/2003 | IN-COMPLIANCE | PINK | 0/4 | COMPLIANCE ASSURANCE | |
RRBD | 12/17/2003 | 12/29/2003 | PINK | 0/0 | COMPLIANCE ASSURANCE | ||
NCLI | 12/15/2003 | 12/17/2003 | PINK | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 12/12/2003 | 12/17/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | PINK | 0/4 | COMPLIANCE ASSURANCE | |
Completion Notes PIPING TYPE NOT VISIBLE | |||||||
RRBD | 08/01/2002 | 08/29/2002 | COMPLIANCE ASSURANCE | ||||
NCLI | 07/05/2002 | 07/09/2002 | STRAUSS | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 07/02/2002 | 07/09/2002 | MINOR OUT-OF-COMPLIANCE | STRAUSS | 0/4 | COMPLIANCE ASSURANCE | |
TCR | 10/12/2001 | 10/29/2001 | IN-COMPLIANCE | TAM | 0/4 | COMPLIANCE ASSURANCE | |
NCLI | 07/30/2001 | 07/30/2001 | COMPLIANCE ASSURANCE | ||||
RRBD | 07/26/2001 | 07/30/2001 | COMPLIANCE ASSURANCE | ||||
RRBD | 07/11/2001 | 07/17/2001 | COMPLIANCE ASSURANCE | ||||
TCI | 07/03/2001 | 07/09/2001 | SIGNIFICANT OUT-OF-COMPLIANCE | SOWERS | 0/4 | COMPLIANCE ASSURANCE | |
RRBD | 02/13/2001 | 02/15/2001 | COMPLIANCE ASSURANCE | ||||
TCI | 10/16/2000 | 10/17/2000 | SIGNIFICANT OUT-OF-COMPLIANCE | CASTOR | 0/5 | COMPLIANCE ASSURANCE | |
RRBD | 07/06/2000 | 08/17/2000 | SOWERS | 0/0 | COMPLIANCE ASSURANCE | ||
RRBD | 12/13/1999 | 02/15/2000 | CASTOR | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 11/15/1999 | 11/22/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | CASTOR | 0/4 | COMPLIANCE ASSURANCE | |
TCI | 04/06/1999 | 04/06/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | SOWERS | 0/4 | COMPLIANCE ASSURANCE | |
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Site Inspection | 04/22/2024 | Major Out of Compliance | PUHR_NM_1 | 0/1 | Routine Compliance | ||
Letter | 04/22/2024 | Satisfied | PUHR_NM_1 | Compliance Assistance | |||
Incident | 02/23/2023 | Has not led to Discharge | COLSON_NJ_1 | Incident | |||
TCAR | 06/09/2022 | Satisfied | COLSON_NJ_1 | Closure | |||
Letter | 06/09/2022 | Satisfied | COLSON_NJ_1 | Closure | |||
Discharge Reporting | 06/09/2022 | Satisfied | COLSON_NJ_1 | Discharge | |||
Record Document | 06/06/2022 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Electronic Communication | 06/01/2022 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||
Site Inspection | 05/31/2022 | Major Out of Compliance | COLSON_NJ_1 | 0/1 | Routine Compliance | ||
Letter | 05/31/2022 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Document Management | 02/11/2022 | Satisfied | WESTERVELT_H | Enforcement | |||
Record Document | 10/25/2021 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Document Management | 07/14/2021 | Satisfied | WESTERVELT_H | Enforcement | |||
Site Inspection | 06/29/2021 | Major Out of Compliance | COLSON_NJ_1 | 0/1 | Component Closure | ||
Site Inspection | 06/29/2021 | Major Out of Compliance | COLSON_NJ_1 | 0/1 | Component Installation | ||
Site Inspection | 05/15/2020 | Major Out of Compliance | COLSON_NJ_1 | 0/1 | Routine Compliance | ||
Letter | 05/15/2020 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Electronic Communication | 04/23/2020 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||
Letter | 02/27/2020 | Satisfied | WESTERVELT_H | Enforcement | |||
Phone Conversation | 04/09/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Record Document | 04/09/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Electronic Communication | 04/02/2018 | Satisfied | WESTERVELT_H | Enforcement | |||
Enforcement Referral | 03/26/2018 | Accepted | COLSON_NJ_1 | Enforcement | |||
Site Inspection | 03/16/2018 | Major Out of Compliance | COLSON_NJ_1 | 0/1 | Compliance Assistance | ||
Electronic Communication | 03/16/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Phone Conversation | 02/26/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Letter | 01/22/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Site Inspection | 01/22/2018 | Major Out of Compliance | COLSON_NJ_1 | 0/1 | Compliance Assistance | ||
Letter | 12/19/2017 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Site Inspection | 12/19/2017 | Major Out of Compliance | COLSON_NJ_1 | 0/1 | Routine Compliance | ||
Electronic Communication | 12/18/2017 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||
Record Document | 07/05/2016 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||
Site Inspection | 06/29/2016 | Minor Out of Compliance | COLSON_NJ_1 | 0/1 | Non-Compliance | ||
Letter | 06/29/2016 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||
Site Inspection | 12/14/2015 | Minor Out of Compliance | COLSON_NJ_1 | 0/1 | Routine Compliance | ||
Letter | 12/14/2015 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||
Electronic Communication | 11/09/2015 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||
TCAR | 03/10/2014 | Satisfied | STRAUSS_RH_1 | Closure | |||
Document Management | 03/10/2014 | Complete | STRAUSS_RH_1 | Closure | |||
Incident | 03/10/2014 | Has not led to Discharge | STRAUSS_RH_1 | Incident | |||
Site Inspection | 01/06/2014 | In Compliance | STRAUSS_RH_1 | 0/1 | Installation | ||
Issue Document | 01/06/2014 | Satisfied | STRAUSS_RH_1 | Closure | |||
Site Inspection | 01/06/2014 | In Compliance | STRAUSS_RH_1 | 0/1 | Non-Compliance | ||
Issue Document | 01/06/2014 | Satisfied | STRAUSS_RH_1 | Installation | |||
Issue Document | 01/06/2014 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Site Inspection | 01/06/2014 | In Compliance | STRAUSS_RH_1 | 0/1 | Closure | ||
Document Management | 11/07/2013 | Complete | STRAUSS_RH_1 | Incident | |||
Letter | 11/07/2013 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Site Inspection | 11/07/2013 | Minor Out of Compliance | STRAUSS_RH_1 | 0/1 | Routine Compliance | ||
Record Document | 05/22/2013 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Site Inspection | 03/11/2013 | Major Out of Compliance | STRAUSS_RH_1 | 0/1 | Routine Compliance | ||
Letter | 03/11/2013 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Letter | 01/12/2012 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Site Inspection | 01/12/2012 | Minor Out of Compliance | STRAUSS_RH_1 | 0/1 | Routine Compliance | ||
Site Inspection | 01/05/2011 | In Compliance | STRAUSS_RH_1 | 0/1 | Routine Compliance | ||
Record Document | 05/05/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Letter | 01/29/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Site Inspection | 01/29/2010 | Major Out of Compliance | STRAUSS_RH_1 | 0/1 | Routine Compliance | ||
Emergency Preparedness Information | 01/29/2010 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||
Site Inspection | 12/10/2009 | In Compliance | ROGGELIN_EM_1 | 0/1 | Installation | ||
Site Inspection | 12/10/2009 | In Compliance | ROGGELIN_EM_1 | 0/1 | Closure | ||
Site Inspection | 08/04/2008 | In Compliance | BARNETT_JX | 0/1 | Non-Compliance | ||
Emergency Preparedness Information | 07/29/2008 | Satisfied | BARNETT_JX | Routine Compliance | |||
Letter | 07/29/2008 | Satisfied | BARNETT_JX | Non-Compliance | |||
Site Inspection | 07/29/2008 | Major Out of Compliance | BARNETT_JX | 0/1 | Routine Compliance | ||
Record Document | 12/27/2007 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Record Document | 12/19/2007 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||
Record Document | 12/19/2007 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Letter | 10/01/2007 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||
Site Inspection | 09/11/2007 | Major Out of Compliance | LONGEN_JL_1 | 0/1 | Routine Compliance | ||
Phone Conversation | 02/15/2007 | Satisfied | ROGGELIN_EM_1 | Installation | |||
Emergency Preparedness Information | 02/09/2007 | Satisfied | LONGEN_JL_1 | Routine Compliance | |||
TCAR | 11/09/2006 | Satisfied | STRAUSS_RH_1 | Closure | |||
Emergency Preparedness Information | 09/20/2006 | Satisfied | LONGEN_JL_1 | Routine Compliance | |||
No Open AOCs Found | |||||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
04/22/2024 | 6074 | Minor | 2.8 Improper maintenance of records. Records requiring to be maintained for 3 years or for the life of the system not kept by facility. Records not provided within 5 business days. | *Submit the missing records if found. Otherwise, begin including the conditions (dry/liquid present) of the STP sumps every 6 months. Submit a monthly visual record with the STP sump conditions noted and be sure to record STP sump conditions at least once every 6 months. | |||
04/22/2024 | 6066 | Minor | 4.4 Not repaired per applicable standards. | *Need to treat/repair electrical conduit piping in the RUL STP Sump and continue to monitor the other sumps for worsening corrosion. Provide documentation of the repair to this office for review. | |||
04/22/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Submit past records if found; otherwise submit current operability testing for the spill bucket VisiGauges. | |||
12/19/2017 | 4016 | SNC-B | 2.5 Incident investigation not initiated within 24-hours of discovery. | Submit an INF, if an investigation of the incident(s) was not performed within 24 hours of the tank interstice alarm(s). Provide investigation documentation, including any integrity testing performed on the tank interstice. | |||
12/19/2017 | 4063 | SNC-B | 4.7 Release detection not constructed and installed so that groundwater, rainfall, or soil moisture will not render the release detection method used inoperable. | Be sure to investigate all alarms immediately. Maintain resolution documentation for the life of the storage tank system. Submit an Incident Notification Form. Remove the accumulated liquid from the tank interstice. Test the tank interstice to determine the integrity of the storage tank system. Submit test results to this office once completed. | |||
Discharge Information | |||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||
05/05/1986 | ACTIVE | 12 | EARLY DETECTION INCENTIVE-ELIGIBLE | ||||