DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Pinellas   Status    OPEN
 
ID 8623615   Latitude    27° 46' 14.2905
 
Name CIRCLE K #2707684
5756 CENTRAL AVE
Longitude    82° 42' 42.956
  SAINT PETERSBURG, FL 33707-1719 LL Method    DPHO
 
Contact GRAHAM BIGGS   LL Status    REVIEWED
 
Phone (919) 774-6700   Status Date    06/19/2023
 
Account Owner Information
 
Name CIRCLE K STORES INC
1100 Situs Ct
Raleigh, NC 27606-5446
Effective Date    12/06/2006
 
Contact IRA LEWIS
 
Phone (423) 400-2480
 
Email ILEWIS@CIRCLEK.COM
  Placard # / Date    697688 - 06/28/2024
Property Owner Information
 
Name CIRCLE K STORES INC
1100 Situs Ct
Raleigh, NC 27606-5446
Effective Date    08/12/2020
 
Contact IRA LEWIS
 
Phone (423) 400-2480
 
Email ILEWIS@CIRCLEK.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
6 20000 Unleaded Gas (B) 01/01/2005 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
7 12000 Vehicular Diesel (D) 01/01/2005 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
8 10000 Unleaded Gas (B) 01/01/2005 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 6045 Unleaded Gas (B) 07/01/1970 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
1R1 10000 Unleaded Gas (B) 12/01/1985 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(8) Manually sampled wells
(H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
2 8060 Unleaded Gas (B) 07/01/1967 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
2R1 10000 Unleaded Gas (B) 12/01/1985 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(8) Manually sampled wells
(H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
3 5036 Leaded Gas (A) 07/01/1967 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
3R1 10000 Unleaded Gas (B) 12/01/1985 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(K) Dispenser liners
(8) Manually sampled wells
(H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
4 5036 Leaded Gas (A) 07/01/1967 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
4R1 550 Waste Oil (L) 07/01/1967 UNDERGROUND Closed In Place (A)
 
Constructions   Pipings Monitorings
(C) Steel   (Y) Unknown (I) Not required
 
 
Tank Tank Size Content Installed Placement Status
5 550 Other Non Regulated (Z) 11/01/1985 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(K) AST containment
  (C) Fiberglass
(G) Pipe trench liner
(8) Manually sampled wells
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
GUARANTEE   04/28/2024 08/26/2025
GUARANTEE   04/30/2023 08/28/2024
GUARANTEE   04/24/2022 08/21/2023
GUARANTEE   04/25/2021 08/27/2022
INSURANCE   12/01/2020 12/01/2021 NAVIGATORS SPECIALTY INSURANCE CO
INSURANCE   12/01/2019 12/01/2020 NAVIGATORS SPECIALTY INSURANCE CO
INSURANCE   12/01/2018 12/01/2019 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2017 12/01/2018 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2016 12/01/2017 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2015 12/01/2016 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2014 12/01/2015 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2013 12/01/2014 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2011 12/01/2013 CHUBB
INSURANCE   12/01/2011 12/01/2012 CHUBB
INSURANCE   12/17/2010 12/17/2011 CHUBB
INSURANCE   12/17/2009 12/17/2010 CHUBB
INSURANCE   12/17/2008 12/17/2009 AMERICAN INTERNATIONAL SPECIALTY LINES
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
TCI 10/18/2005 10/31/2005 MINOR OUT-OF-COMPLIANCE FRAZIER 0/3 COMPLIANCE ASSURANCE
 
NCLI 10/18/2005 10/31/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
EPI 06/21/2005 06/21/2005 REEDER_J 0/0 COMPLIANCE ASSURANCE
 
RRBD 05/03/2005 05/03/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
NCLI 01/25/2005 02/01/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
TIN 01/24/2005 02/01/2005 SIGNIFICANT OUT-OF-COMPLIANCE FRAZIER 0/3 COMPLIANCE ASSURANCE
 
LTR 12/22/2004 12/29/2004 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
TXI 12/01/2004 12/29/2004 IN-COMPLIANCE FRAZIER 0/3 COMPLIANCE ASSURANCE
 
LTR 11/24/2004 11/29/2004 BARNETT 0/0 COMPLIANCE ASSURANCE
 
TCI 11/22/2004 11/29/2004 IN-COMPLIANCE BARNETT 0/5 COMPLIANCE ASSURANCE
 
NCLI 04/26/2004 05/23/2004 ROGGELIN 0/0 DISCHARGE PROJECT
 
TDI 04/16/2004 05/23/2004 SIGNIFICANT OUT-OF-COMPLIANCE ROGGELIN 0/1 DISCHARGE PROJECT
 
 Completion Notes BREAK IN FRP LINE DURING INSTALL OF ISLAND BUMPER.
 
CNLI 04/08/2004 05/23/2004 ROGGELIN 0/0 DISCHARGE PROJECT
 
NCLI 01/13/2004 01/14/2004 PINK 0/0 COMPLIANCE ASSURANCE
 
TCI 01/09/2004 01/14/2004 MINOR OUT-OF-COMPLIANCE PINK 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes AMERON SW FRP PIPING
 
RRBD 11/22/2002 01/03/2003 COMPLIANCE ASSURANCE
 
NCLI 11/14/2002 11/15/2002 STRAUSS 0/0 COMPLIANCE ASSURANCE
 
TCI 11/06/2002 11/15/2002 MINOR OUT-OF-COMPLIANCE STRAUSS 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes SW AMERON FRP PIPE
 
RRBD 04/02/2002 04/08/2002 COMPLIANCE ASSURANCE
 
TCI 01/02/2002 01/04/2002 SIGNIFICANT OUT-OF-COMPLIANCE TAM 0/3 COMPLIANCE ASSURANCE
 
TCI 10/25/2000 10/25/2000 MINOR OUT-OF-COMPLIANCE CASTOR 0/3 COMPLIANCE ASSURANCE
 
RRBD 01/28/2000 02/03/2000 CASTOR 0/0 COMPLIANCE ASSURANCE
 
TCI 12/21/1999 01/03/2000 SIGNIFICANT OUT-OF-COMPLIANCE CASTOR 0/3 COMPLIANCE ASSURANCE
 
RRBD 05/10/1999 06/28/1999 SOWERS 0/0 COMPLIANCE ASSURANCE
 
TCI 01/19/1999 02/26/1999 SIGNIFICANT OUT-OF-COMPLIANCE SOWERS_J 0/3 COMPLIANCE ASSURANCE
 
UTCI 03/04/1998 03/19/1998 MINOR OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 09/19/2024 Satisfied PUHR_NM_1 Compliance Assistance
 
Site Inspection 09/19/2024 Major Out of Compliance PUHR_NM_1 0/3 Routine Compliance
 
Letter 08/28/2024 Satisfied WIMBERLY_E Enforcement
 
Enforcement Referral 10/18/2023 Accepted JUARISTIC_GK_1 Enforcement
 
Electronic Communication 10/18/2023 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Electronic Communication 10/05/2023 Satisfied JUARISTIC_GK_1 Compliance Assistance
 
Electronic Communication 02/09/2023 Satisfied COLSON_NJ_1 Routine Compliance
 
Letter 02/07/2023 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 02/06/2023 Minor Out of Compliance COLSON_NJ_1 0/3 Routine Compliance
 
Electronic Communication 08/19/2020 Satisfied COLSON_NJ_1 Compliance Assistance
 
Letter 08/19/2020 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 08/10/2020 Minor Out of Compliance COLSON_NJ_1 0/3 Routine Compliance
 
Letter 08/10/2020 Satisfied COLSON_NJ_1 Compliance Assistance
 
Electronic Communication 07/09/2020 Satisfied COLSON_NJ_1 Routine Compliance
 
Letter 12/10/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Record Document 12/10/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Letter 09/19/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 09/19/2018 Major Out of Compliance COLSON_NJ_1 0/3 Routine Compliance
 
Electronic Communication 09/06/2018 Satisfied COLSON_NJ_1 Routine Compliance
 
Issue Document 10/18/2016 Satisfied COLSON_NJ_1 Routine Compliance
 
Site Inspection 10/18/2016 In Compliance COLSON_NJ_1 0/3 Routine Compliance
 
Electronic Communication 09/28/2016 Satisfied COLSON_NJ_1 Routine Compliance
 
Electronic Communication 08/26/2016 Satisfied COLSON_NJ_1 Routine Compliance
 
Issue Document 05/01/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 05/01/2015 In Compliance COLSON_NJ_1 0/2 Non-Compliance
 
Site Inspection 04/02/2015 Minor Out of Compliance COLSON_NJ_1 0/3 Routine Compliance
 
Letter 04/02/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Emergency Preparedness Information 04/01/2015 Satisfied COLSON_NJ_1 Routine Compliance
 
Site Inspection 08/23/2013 In Compliance STRAUSS_RH_1 0/3 Installation
 
Record Document 08/23/2013 Satisfied STRAUSS_RH_1 Non-Compliance
 
Letter 07/24/2013 Satisfied ROGGELIN_EM_1 Closure
 
TCAR 07/24/2013 Satisfied ROGGELIN_EM_1 Closure
 
Document Management 07/24/2013 Complete ROGGELIN_EM_1 Closure
 
Letter 07/19/2013 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 07/19/2013 Minor Out of Compliance STRAUSS_RH_1 0/3 Closure
 
Site Inspection 02/04/2013 In Compliance SOWERS_JA_1 0/3 Routine Compliance
 
Incident 02/07/2012 Has not led to Discharge STRAUSS_RH_1 Incident
 
Site Inspection 02/07/2012 In Compliance STRAUSS_RH_1 0/3 Non-Compliance
 
Letter 02/03/2012 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 02/02/2012 Minor Out of Compliance STRAUSS_RH_1 0/3 Non-Compliance
 
Letter 01/09/2012 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 01/09/2012 Major Out of Compliance STRAUSS_RH_1 0/3 Routine Compliance
 
Site Inspection 02/16/2011 In Compliance STRAUSS_RH_1 0/3 Non-Compliance
 
Letter 02/14/2011 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 02/14/2011 Minor Out of Compliance STRAUSS_RH_1 0/3 Non-Compliance
 
Letter 01/07/2011 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 01/07/2011 Minor Out of Compliance STRAUSS_RH_1 0/3 Routine Compliance
 
Issue Document 04/23/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 04/23/2010 In Compliance STRAUSS_RH_1 0/1 Non-Compliance
 
Site Inspection 02/22/2010 Minor Out of Compliance STRAUSS_RH_1 0/3 Routine Compliance
 
Letter 02/22/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 06/05/2009 In Compliance BARNETT_JX 0/3 Routine Compliance
 
Record Document 03/06/2008 Satisfied ROGGELIN_EM_1 Routine Compliance
 
Site Inspection 09/25/2007 Minor Out of Compliance STRAUSS_RH_1 0/3 Non-Compliance
 
Letter 09/25/2007 Satisfied STRAUSS_RH_1 Non-Compliance
 
Letter 07/31/2007 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 06/04/2007 Major Out of Compliance LONGEN_JL_1 0/3 Routine Compliance
 
Emergency Preparedness Information 02/13/2007 Satisfied LONGEN_JL_1 Routine Compliance
 
Emergency Preparedness Information 09/20/2006 Satisfied SOWERS_JA_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
09/19/2024 6046 Minor 4.14 Dispensers not installed and maintained according to standards. *Tighten the bolt in dispenser 1/2 and provide documentation to this office for review.
 
09/18/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. *Remove the liquid and provide documentation.
 
09/18/2024 6023 Minor 4.1 Secondary containment or integral piping not installed to allow for monitoring point. *Need to verify that the double walled pipe interstice is open in the PUL STP sump in order to provide a monitoring point.
 
09/18/2024 6009 Minor 4.1 Incident Notification Form (INF) not received in a timely manner. *Be sure to investigate all alarms promptly & document the alarm resolution activities. Provide documentation to this office once completed.
 
09/18/2024 6015 Minor 4.3 Incident investigation not completed within 14 days, and/or no DRF or written confirmation received at the end of the 14-day investigation period. *Be sure to investigate all alarms promptly & document the alarm resolution activities. Provide documentation to this office once completed.
 
09/18/2024 6014 SNC-B 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. *Be sure to investigate all alarms promptly & document the alarm resolution activities. Provide documentation to this office once completed.
 
09/18/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. *Need to repair or replace the rusted piping in the RUL and PUL STP sumps. Provide documentation once completed.
 
02/06/2023 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Be sure to have the required integrity testing performed within 36 months of the last test date. Submit current integrity test results for the (8) dispenser liners to this office for review.
 
02/06/2023 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove the accumulated liquids from the sumps. Provide a work receipt and/or photos to this office once completed.
 
02/06/2023 6017 Minor 4.4 All incident records, including test results not kept until storage tank system closure. Be sure to investigate incidents immediately. Submit explanation and resolution documentation for the historical tank interstice alarm.
 
02/06/2023 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Be sure to have the required integrity testing performed within 36 months of the last test date. Submit current integrity test results for the (3) STP sumps to this office for review.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
03/26/2004   COMPLETED 11
 
03/12/1992   COMPLETED 11 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE