Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Retail Station | ||||||||
County | Polk | Status | OPEN | ||||||||
ID | 8623656 | Latitude | 28° 7' 17.4512 | ||||||||
Name |
SUPER STAR FOOD STORE 1202 US HWY 17 |
Longitude | 81° 38' 37.076 | ||||||||
HAINES CITY, FL 33844 | LL Method | DPHO | |||||||||
Contact | MAZIBUR RAHMAN | LL Status | REVIEWED | ||||||||
Phone | (863) 421-7362 | Status Date | 12/04/2024 | ||||||||
Account Owner Information | |||||||||||
Name | MEGHNA INVESTMENT LLC 1202 OLD POLK CITY RD HAINES CITY, FL 33844 |
Effective Date | 05/10/2011 | ||||||||
Contact | MAZIBUR RAHMAN | ||||||||||
Phone | (407) 361-0690 | ||||||||||
Placard # / Date | 702662 - 10/28/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | MEGHNA INVESTMENT LLC 1202 OLD POLK CITY RD HAINES CITY, FL 33844 |
Effective Date | 08/24/2015 | ||||||||
Contact | MAZIBUR RAHMAN | ||||||||||
Phone | (407) 361-0690 | ||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 4000 | Vehicular Diesel (D) | 04/01/1997 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(F) Fiberglass clad steel (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 12000 | Unleaded Gas (B) | 12/01/2008 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (K) AST containment |
(C) Fiberglass (F) Double wall |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 8000 | Unleaded Gas (B) | 08/01/1976 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (B) Internal lining (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 8000 | Unleaded Gas (B) | 08/01/1976 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (B) Internal lining (M) Spill containment bucket (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 10/15/2024 | 10/15/2025 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 10/15/2023 | 10/15/2024 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 10/15/2022 | 10/15/2023 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 10/15/2021 | 10/15/2022 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
INSURANCE | 10/15/2020 | 10/15/2021 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/15/2019 | 10/15/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/15/2018 | 10/15/2019 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 10/15/2017 | 10/15/2018 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/15/2016 | 10/15/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/15/2014 | 10/15/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 10/15/2012 | 10/15/2013 | ZURICH-AMERICAN | ||||||||
INSURANCE | 10/15/2011 | 10/15/2012 | ZURICH-AMERICAN | ||||||||
INSURANCE | 10/15/2010 | 10/15/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 01/13/2010 | 01/13/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 01/13/2009 | 01/13/2010 | ZURICH-AMERICAN | ||||||||
INSURANCE | 09/15/2003 | 09/15/2004 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 09/15/1995 | 09/15/1999 | FPLIPA | ||||||||
INSURANCE | 02/11/1994 | 02/11/1995 | FPLIPA | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
LTR | 01/09/2006 | 01/09/2006 | HUGHES_J | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes VIOLATION RESOLUTION FOLLOW-UP LETTER. | |||||||||||
NCLI | 09/30/2005 | 10/09/2005 | HUGHES_J | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REQUESTED: COPY OF PLACARD. | |||||||||||
TCI | 09/09/2005 | 10/09/2005 | MINOR OUT-OF-COMPLIANCE | HUGHES_J | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO PHOTOS TAKEN. PIPING: UNDERGROUND DW FLEX AND GREEN FOR TANKS #1 & @. DW UNDERGORUND FIBERGLASS AMERON RIGID FOR TANK #3. | |||||||||||
TIN | 02/17/2005 | 04/14/2005 | IN-COMPLIANCE | CROWELL_M | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes 1 PHOTO TAKEN. PIPING: DOUBLE WALLED AMERON DUALOY 3000/LCX FIBERGLASS EQ-291& AMERON RIGID FIBERGLASS FOR DIESEL. | |||||||||||
SV | 02/15/2005 | 03/14/2005 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes 5 PHOTOS TAKEN. FINAL INSTALLATION OF REPLACED PIPING. | |||||||||||
SV | 02/14/2005 | 02/25/2005 | SACLARIDES_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes 2 PHOTOS TAKEN. SECONDARY TEST. AMERON LCX D/W FIBERGLASS PIPING APPROXIMATELY 120 FT. | |||||||||||
SV | 02/11/2005 | 02/14/2005 | NEWBERG_D | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes 4 PHOTOS TAKEN. PRIMARY & HYDRO TESTS. DAN BICKERT WITH GOLDEN FUEL INC. PCC048394. | |||||||||||
TXI | 02/10/2005 | 02/14/2005 | IN-COMPLIANCE | GONZALEZ_J | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes 7 PHOTOS TAKEN. CLOSED 2 DOUBLE-WALL FLEX LINES. DAN BICKERT PCC048394. NO CLOSURE ASSESSMENT DUE. | |||||||||||
TCI | 02/10/2005 | 02/13/2005 | IN-COMPLIANCE | GONZALEZ_J | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes 2 PHOTOS TAKEN. PIPING: DOUBLE WALLED AMERON DUALOY 3000/LCX FIBERGLASS EQ-291& AMERON RIGID FIBERGLAS FOR DIESEL. RESOLVES VIOLATION #9, 151, 157, & 160. | |||||||||||
RRBD | 06/16/2004 | 06/21/2004 | SACLARIDES_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RECEIVED MONTHLY FACILITY INSPECTION RECORDS. RESOLVES VIOLATION #86. | |||||||||||
LTR | 04/23/2004 | 04/23/2004 | SACLARIDES_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes 30 DAY VIOLATION LETTER. | |||||||||||
NCLI | 04/06/2004 | 04/06/2004 | SACLARIDES_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes REQUESTED: 2 MONTHLY MONITORING INSPECTIONS, CP TEST RESULTS, ANNUAL OPERABILITY TEST RESULTS. | |||||||||||
TCI | 03/19/2004 | 04/06/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | SACLARIDES_M | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes NO PHOTOS TAKEN. PIPING: DOUBLE WALLED GREEN FLEX FOR GAS TANKS & AMERON RIGID FIBERGLAS FOR DIESEL. RESOLVES VIOLATION #155. | |||||||||||
RRBD | 07/03/2003 | 07/15/2003 | CROWELL_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes RESOLVES VIOLATION #3. | |||||||||||
NCLI | 04/16/2003 | 04/18/2003 | HUGHES_J | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 04/15/2003 | 04/18/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | HUGHES_J | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes 2 PHOTOS TAKEN. CLOSES VIOLATION #95. | |||||||||||
TCI | 04/29/2002 | 05/06/2002 | MINOR OUT-OF-COMPLIANCE | SACLARIDES_M | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 05/14/2001 | 05/15/2001 | SACLARIDES_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
NCLI | 03/07/2001 | 03/08/2001 | SACLARIDES_M | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 02/15/2001 | 03/08/2001 | SIGNIFICANT OUT-OF-COMPLIANCE | SACLARIDES_M | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 01/27/2000 | 01/31/2000 | JENKINS_N | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes DROP VIOLATIONS #84,86,90,132,171,912,909 PER JON REEDER | |||||||||||
RRBD | 01/26/2000 | 01/31/2000 | JENKINS_N | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes DROP VIOLATION #910 PER JON REEDER | |||||||||||
RRBD | 12/06/1999 | 12/09/1999 | JENKINS_N | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 09/28/1999 | 10/13/1999 | SIGNIFICANT OUT-OF-COMPLIANCE | RONEY_B | 0/3 | COMPLIANCE ASSURANCE | |||||
UTCI | 10/19/1998 | 11/10/1998 | SIGNIFICANT OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Electronic Communication | 12/04/2024 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Electronic Communication | 12/04/2024 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 12/04/2024 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Electronic Communication | 12/04/2024 | Satisfied | GLENN_LE_1 | Routine Compliance | |||||||
Electronic Communication | 12/04/2024 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Letter | 12/04/2024 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Site Inspection | 10/31/2024 | Major Out of Compliance | GLENN_LE_1 | 0/2 | Routine Compliance | ||||||
Letter | 10/31/2024 | Satisfied | GLENN_LE_1 | Compliance Assistance | |||||||
Electronic Communication | 08/08/2024 | Satisfied | ORHUE_OR_1 | Compliance Assistance | |||||||
Electronic Communication | 08/11/2022 | Satisfied | HYPPOLITE_LX_1 | Routine Compliance | |||||||
Electronic Communication | 06/20/2022 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Site Inspection | 06/20/2022 | Minor Out of Compliance | GLENN_LE_1 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 06/20/2022 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 06/20/2022 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 06/24/2019 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 05/31/2019 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Letter | 05/31/2019 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 05/31/2019 | Satisfied | CASSELS_CR_2 | Compliance Assistance | |||||||
Electronic Communication | 05/31/2019 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Site Inspection | 05/30/2019 | Major Out of Compliance | CASSELS_CR_2 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 03/29/2019 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Electronic Communication | 03/29/2019 | Satisfied | CASSELS_CR_2 | Routine Compliance | |||||||
Electronic Communication | 11/27/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Site Inspection | 11/27/2017 | In Compliance | WILLIAMSON_KE_1 | 0/2 | Compliance Assistance | ||||||
Letter | 11/27/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Phone Conversation | 11/20/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Electronic Communication | 11/09/2017 | Satisfied | WILLIAMSON_KE_1 | Compliance Assistance | |||||||
Letter | 01/20/2017 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||||||
Electronic Communication | 01/20/2017 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||||||
Site Inspection | 01/20/2017 | Minor Out of Compliance | WILLIAMSON_KE_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 09/08/2015 | In Compliance | WILLIAMSON_KE_1 | 0/2 | Non-Compliance | ||||||
Issue Document | 09/08/2015 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||||||
Meeting | 09/08/2015 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||||||
Electronic Communication | 08/27/2015 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||||||
Record Document | 07/08/2015 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||||||
Issue Document | 05/06/2015 | Satisfied | WILLIAMSON_KE_1 | Non-Compliance | |||||||
Site Inspection | 04/30/2015 | Minor Out of Compliance | WILLIAMSON_KE_1 | 0/2 | Routine Compliance | ||||||
Letter | 06/27/2013 | Satisfied | WINN_JP_1 | Non-Compliance | |||||||
Site Inspection | 06/27/2013 | Minor Out of Compliance | WINN_JP_1 | 0/2 | Routine Compliance | ||||||
Enforcement Tracking | 07/10/2012 | Closed Without Enforcement | MEETZE_A | Enforcement | |||||||
Record Document | 07/03/2012 | Satisfied | MEETZE_A | Enforcement | |||||||
Record Document | 06/11/2012 | Satisfied | MEETZE_A | Enforcement | |||||||
Phone Conversation | 05/03/2012 | Satisfied | MEETZE_A | Enforcement | |||||||
Record Document | 05/03/2012 | Satisfied | MEETZE_A | Enforcement | |||||||
Site Inspection | 04/23/2012 | Major Out of Compliance | MEETZE_A | 0/2 | Enforcement | ||||||
Letter | 04/23/2012 | Satisfied | MEETZE_A | Non-Compliance | |||||||
Issue Document | 04/05/2012 | Satisfied | MEETZE_A | Enforcement | |||||||
Enforcement Referral | 04/04/2012 | Accepted | MEETZE_A | Enforcement | |||||||
Letter | 03/06/2012 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 03/06/2012 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Phone Conversation | 03/06/2012 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Record Document | 03/06/2012 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Site Inspection | 12/13/2011 | Major Out of Compliance | SLAPPEY_WR_1 | 0/2 | Routine Compliance | ||||||
Letter | 12/13/2011 | Satisfied | SLAPPEY_WR_1 | Non-Compliance | |||||||
Site Inspection | 02/28/2011 | Minor Out of Compliance | WINN_JP_1 | 0/2 | Routine Compliance | ||||||
Letter | 02/28/2011 | Satisfied | WINN_JP_1 | Non-Compliance | |||||||
Site Inspection | 06/14/2010 | In Compliance | DERY_WC_1 | 0/2 | Non-Compliance | ||||||
Letter | 05/28/2010 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Record Document | 05/14/2010 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Site Inspection | 04/13/2010 | Major Out of Compliance | DERY_WC_1 | 0/2 | Routine Compliance | ||||||
Letter | 04/13/2010 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Site Inspection | 04/13/2010 | Major Out of Compliance | DERY_WC_1 | 0/2 | Routine Compliance | ||||||
Phone Conversation | 03/26/2010 | Satisfied | DERY_WC_1 | Routine Compliance | |||||||
Site Inspection | 06/15/2009 | In Compliance | DERY_WC_1 | 0/2 | Routine Compliance | ||||||
Phone Conversation | 06/11/2009 | Satisfied | DERY_WC_1 | Routine Compliance | |||||||
Meeting | 02/19/2009 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
TCAR | 02/19/2009 | Satisfied | DERY_WC_1 | Closure | |||||||
Letter | 02/05/2009 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Site Inspection | 12/31/2008 | In Compliance | WINN_JP_1 | 0/2 | Installation | ||||||
Site Inspection | 12/10/2008 | In Compliance | NEWBERG_DR_1 | 0/2 | Closure | ||||||
Record Document | 07/22/2008 | Satisfied | DERY_WC_1 | Installation | |||||||
Phone Conversation | 04/23/2008 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Record Document | 04/23/2008 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Record Document | 04/23/2008 | Satisfied | DERY_WC_1 | Routine Compliance | |||||||
Record Document | 04/17/2008 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Issue Document | 02/05/2008 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Issue Document | 01/03/2008 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Issue Document | 01/03/2008 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Issue Document | 01/03/2008 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Site Inspection | 10/28/2007 | Major Out of Compliance | DERY_WC_1 | 0/3 | Routine Compliance | ||||||
Letter | 10/28/2007 | Satisfied | DERY_WC_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 02/09/2007 | Satisfied | DERY_WC_1 | Routine Compliance | |||||||
Site Inspection | 02/01/2007 | In Compliance | NEWBERG_DR_1 | 0/3 | Routine Compliance | ||||||
Phone Conversation | 01/29/2007 | Satisfied | NEWBERG_DR_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/26/2006 | Satisfied | SLAPPEY_WR_1 | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
10/31/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | 2022 and 2024 testing records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department. | |||||||
10/31/2024 | 6006 | Minor | 2.5 Placard not displayed (or available upon request). | A copy of the Placard must be obtained and provided to the Department. | |||||||
10/31/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Premium spill bucket interstice port must be repaired or replaced and the Department notified. | |||||||
10/31/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | Test records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department. | |||||||
10/31/2024 | 6062 | Minor | 2.5 Release detection devices not tested annually. | 2022 and 2024 testing records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department. | |||||||
10/31/2024 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | The next two months (November & December) of inspections including the vacuum gauge readings must be provided to the Department as they are performed. | |||||||
10/31/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Electrical junction box must be sealed and the Department notified. | |||||||
10/31/2024 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | 2022 and 2024 testing records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department. | |||||||
10/31/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Test records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department. | |||||||
06/20/2022 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Access to the interstice must be obtained and the Department notified. | |||||||
04/03/2019 | 4077 | Minor | 4.12 Spill containment, sumps, and interstices not accessible. Water/regulated substances not timely removed. Petroleum contact water not properly managed. | All dirt/mud and debris must be removed from the STP sumps and dispenser liners and the Department notified. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
03/03/1987 | COMPLETED | 50 | EARLY DETECTION INCENTIVE-ELIGIBLE | ||||||||