DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Polk   Status    OPEN
 
ID 8623656   Latitude    28° 7' 17.4512
 
Name SUPER STAR FOOD STORE
1202 US HWY 17
Longitude    81° 38' 37.076
  HAINES CITY, FL 33844 LL Method    DPHO
 
Contact MAZIBUR RAHMAN   LL Status    REVIEWED
 
Phone (863) 421-7362   Status Date    12/04/2024
 
Account Owner Information
 
Name MEGHNA INVESTMENT LLC
1202 OLD POLK CITY RD
HAINES CITY, FL 33844
Effective Date    05/10/2011
 
Contact MAZIBUR RAHMAN
 
Phone (407) 361-0690
 
Email
  Placard # / Date    702662 - 10/28/2024
Property Owner Information
 
Name MEGHNA INVESTMENT LLC
1202 OLD POLK CITY RD
HAINES CITY, FL 33844
Effective Date    08/24/2015
 
Contact MAZIBUR RAHMAN
 
Phone (407) 361-0690
 
Email
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
3 4000 Vehicular Diesel (D) 04/01/1997 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(F) Fiberglass clad steel
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
 
 
Tank Tank Size Content Installed Placement Status
4 12000 Unleaded Gas (B) 12/01/2008 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(K) AST containment
  (C) Fiberglass
(F) Double wall
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
 
 
Tank Tank Size Content Installed Placement Status
1 8000 Unleaded Gas (B) 08/01/1976 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
2 8000 Unleaded Gas (B) 08/01/1976 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(B) Internal lining
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   10/15/2024 10/15/2025 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   10/15/2023 10/15/2024 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   10/15/2022 10/15/2023 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   10/15/2021 10/15/2022 COMMERCE AND INDUSTRY INSURANCE COMPANY
INSURANCE   10/15/2020 10/15/2021 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   10/15/2019 10/15/2020 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   10/15/2018 10/15/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   10/15/2017 10/15/2018 COMMERCE & INDUSTRY
INSURANCE   10/15/2016 10/15/2017 COMMERCE & INDUSTRY
INSURANCE   10/15/2014 10/15/2015 COMMERCE & INDUSTRY
INSURANCE   10/15/2012 10/15/2013 ZURICH-AMERICAN
INSURANCE   10/15/2011 10/15/2012 ZURICH-AMERICAN
INSURANCE   10/15/2010 10/15/2011 ZURICH-AMERICAN
INSURANCE   01/13/2010 01/13/2011 ZURICH-AMERICAN
INSURANCE   01/13/2009 01/13/2010 ZURICH-AMERICAN
INSURANCE   09/15/2003 09/15/2004 COMMERCE & INDUSTRY
INSURANCE   09/15/1995 09/15/1999 FPLIPA
INSURANCE   02/11/1994 02/11/1995 FPLIPA
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
LTR 01/09/2006 01/09/2006 HUGHES_J 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes VIOLATION RESOLUTION FOLLOW-UP LETTER.
 
NCLI 09/30/2005 10/09/2005 HUGHES_J 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes REQUESTED: COPY OF PLACARD.
 
TCI 09/09/2005 10/09/2005 MINOR OUT-OF-COMPLIANCE HUGHES_J 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes NO PHOTOS TAKEN. PIPING: UNDERGROUND DW FLEX AND GREEN FOR TANKS #1 & @. DW UNDERGORUND FIBERGLASS AMERON RIGID FOR TANK #3.
 
TIN 02/17/2005 04/14/2005 IN-COMPLIANCE CROWELL_M 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes 1 PHOTO TAKEN. PIPING: DOUBLE WALLED AMERON DUALOY 3000/LCX FIBERGLASS EQ-291& AMERON RIGID FIBERGLASS FOR DIESEL.
 
SV 02/15/2005 03/14/2005 CROWELL_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes 5 PHOTOS TAKEN. FINAL INSTALLATION OF REPLACED PIPING.
 
SV 02/14/2005 02/25/2005 SACLARIDES_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes 2 PHOTOS TAKEN. SECONDARY TEST. AMERON LCX D/W FIBERGLASS PIPING APPROXIMATELY 120 FT.
 
SV 02/11/2005 02/14/2005 NEWBERG_D 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes 4 PHOTOS TAKEN. PRIMARY & HYDRO TESTS. DAN BICKERT WITH GOLDEN FUEL INC. PCC048394.
 
TXI 02/10/2005 02/14/2005 IN-COMPLIANCE GONZALEZ_J 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes 7 PHOTOS TAKEN. CLOSED 2 DOUBLE-WALL FLEX LINES. DAN BICKERT PCC048394. NO CLOSURE ASSESSMENT DUE.
 
TCI 02/10/2005 02/13/2005 IN-COMPLIANCE GONZALEZ_J 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes 2 PHOTOS TAKEN. PIPING: DOUBLE WALLED AMERON DUALOY 3000/LCX FIBERGLASS EQ-291& AMERON RIGID FIBERGLAS FOR DIESEL. RESOLVES VIOLATION #9, 151, 157, & 160.
 
RRBD 06/16/2004 06/21/2004 SACLARIDES_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RECEIVED MONTHLY FACILITY INSPECTION RECORDS. RESOLVES VIOLATION #86.
 
LTR 04/23/2004 04/23/2004 SACLARIDES_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes 30 DAY VIOLATION LETTER.
 
NCLI 04/06/2004 04/06/2004 SACLARIDES_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes REQUESTED: 2 MONTHLY MONITORING INSPECTIONS, CP TEST RESULTS, ANNUAL OPERABILITY TEST RESULTS.
 
TCI 03/19/2004 04/06/2004 SIGNIFICANT OUT-OF-COMPLIANCE SACLARIDES_M 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes NO PHOTOS TAKEN. PIPING: DOUBLE WALLED GREEN FLEX FOR GAS TANKS & AMERON RIGID FIBERGLAS FOR DIESEL. RESOLVES VIOLATION #155.
 
RRBD 07/03/2003 07/15/2003 CROWELL_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RESOLVES VIOLATION #3.
 
NCLI 04/16/2003 04/18/2003 HUGHES_J 0/0 COMPLIANCE ASSURANCE
 
TCI 04/15/2003 04/18/2003 SIGNIFICANT OUT-OF-COMPLIANCE HUGHES_J 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes 2 PHOTOS TAKEN. CLOSES VIOLATION #95.
 
TCI 04/29/2002 05/06/2002 MINOR OUT-OF-COMPLIANCE SACLARIDES_M 0/3 COMPLIANCE ASSURANCE
 
RRBD 05/14/2001 05/15/2001 SACLARIDES_M 0/0 COMPLIANCE ASSURANCE
 
NCLI 03/07/2001 03/08/2001 SACLARIDES_M 0/0 COMPLIANCE ASSURANCE
 
TCI 02/15/2001 03/08/2001 SIGNIFICANT OUT-OF-COMPLIANCE SACLARIDES_M 0/3 COMPLIANCE ASSURANCE
 
RRBD 01/27/2000 01/31/2000 JENKINS_N 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes DROP VIOLATIONS #84,86,90,132,171,912,909 PER JON REEDER
 
RRBD 01/26/2000 01/31/2000 JENKINS_N 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes DROP VIOLATION #910 PER JON REEDER
 
RRBD 12/06/1999 12/09/1999 JENKINS_N 0/0 COMPLIANCE ASSURANCE
 
TCI 09/28/1999 10/13/1999 SIGNIFICANT OUT-OF-COMPLIANCE RONEY_B 0/3 COMPLIANCE ASSURANCE
 
UTCI 10/19/1998 11/10/1998 SIGNIFICANT OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 12/04/2024 Satisfied GLENN_LE_1 Routine Compliance
 
Electronic Communication 12/04/2024 Satisfied GLENN_LE_1 Compliance Assistance
 
Electronic Communication 12/04/2024 Satisfied GLENN_LE_1 Routine Compliance
 
Electronic Communication 12/04/2024 Satisfied GLENN_LE_1 Routine Compliance
 
Electronic Communication 12/04/2024 Satisfied GLENN_LE_1 Compliance Assistance
 
Letter 12/04/2024 Satisfied GLENN_LE_1 Compliance Assistance
 
Site Inspection 10/31/2024 Major Out of Compliance GLENN_LE_1 0/2 Routine Compliance
 
Letter 10/31/2024 Satisfied GLENN_LE_1 Compliance Assistance
 
Electronic Communication 08/08/2024 Satisfied ORHUE_OR_1 Compliance Assistance
 
Electronic Communication 08/11/2022 Satisfied HYPPOLITE_LX_1 Routine Compliance
 
Electronic Communication 06/20/2022 Satisfied CASSELS_CR_2 Compliance Assistance
 
Site Inspection 06/20/2022 Minor Out of Compliance GLENN_LE_1 0/2 Routine Compliance
 
Electronic Communication 06/20/2022 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 06/20/2022 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 06/24/2019 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 05/31/2019 Satisfied CASSELS_CR_2 Compliance Assistance
 
Letter 05/31/2019 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 05/31/2019 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 05/31/2019 Satisfied CASSELS_CR_2 Routine Compliance
 
Site Inspection 05/30/2019 Major Out of Compliance CASSELS_CR_2 0/2 Routine Compliance
 
Electronic Communication 03/29/2019 Satisfied CASSELS_CR_2 Routine Compliance
 
Electronic Communication 03/29/2019 Satisfied CASSELS_CR_2 Routine Compliance
 
Electronic Communication 11/27/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Site Inspection 11/27/2017 In Compliance WILLIAMSON_KE_1 0/2 Compliance Assistance
 
Letter 11/27/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Phone Conversation 11/20/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Electronic Communication 11/09/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Letter 01/20/2017 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Electronic Communication 01/20/2017 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Site Inspection 01/20/2017 Minor Out of Compliance WILLIAMSON_KE_1 0/2 Routine Compliance
 
Site Inspection 09/08/2015 In Compliance WILLIAMSON_KE_1 0/2 Non-Compliance
 
Issue Document 09/08/2015 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Meeting 09/08/2015 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Electronic Communication 08/27/2015 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Record Document 07/08/2015 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Issue Document 05/06/2015 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Site Inspection 04/30/2015 Minor Out of Compliance WILLIAMSON_KE_1 0/2 Routine Compliance
 
Letter 06/27/2013 Satisfied WINN_JP_1 Non-Compliance
 
Site Inspection 06/27/2013 Minor Out of Compliance WINN_JP_1 0/2 Routine Compliance
 
Enforcement Tracking 07/10/2012 Closed Without Enforcement MEETZE_A Enforcement
 
Record Document 07/03/2012 Satisfied MEETZE_A Enforcement
 
Record Document 06/11/2012 Satisfied MEETZE_A Enforcement
 
Phone Conversation 05/03/2012 Satisfied MEETZE_A Enforcement
 
Record Document 05/03/2012 Satisfied MEETZE_A Enforcement
 
Site Inspection 04/23/2012 Major Out of Compliance MEETZE_A 0/2 Enforcement
 
Letter 04/23/2012 Satisfied MEETZE_A Non-Compliance
 
Issue Document 04/05/2012 Satisfied MEETZE_A Enforcement
 
Enforcement Referral 04/04/2012 Accepted MEETZE_A Enforcement
 
Letter 03/06/2012 Satisfied DERY_WC_1 Non-Compliance
 
Phone Conversation 03/06/2012 Satisfied DERY_WC_1 Non-Compliance
 
Phone Conversation 03/06/2012 Satisfied DERY_WC_1 Non-Compliance
 
Record Document 03/06/2012 Satisfied DERY_WC_1 Non-Compliance
 
Site Inspection 12/13/2011 Major Out of Compliance SLAPPEY_WR_1 0/2 Routine Compliance
 
Letter 12/13/2011 Satisfied SLAPPEY_WR_1 Non-Compliance
 
Site Inspection 02/28/2011 Minor Out of Compliance WINN_JP_1 0/2 Routine Compliance
 
Letter 02/28/2011 Satisfied WINN_JP_1 Non-Compliance
 
Site Inspection 06/14/2010 In Compliance DERY_WC_1 0/2 Non-Compliance
 
Letter 05/28/2010 Satisfied DERY_WC_1 Non-Compliance
 
Record Document 05/14/2010 Satisfied DERY_WC_1 Non-Compliance
 
Site Inspection 04/13/2010 Major Out of Compliance DERY_WC_1 0/2 Routine Compliance
 
Letter 04/13/2010 Satisfied DERY_WC_1 Non-Compliance
 
Site Inspection 04/13/2010 Major Out of Compliance DERY_WC_1 0/2 Routine Compliance
 
Phone Conversation 03/26/2010 Satisfied DERY_WC_1 Routine Compliance
 
Site Inspection 06/15/2009 In Compliance DERY_WC_1 0/2 Routine Compliance
 
Phone Conversation 06/11/2009 Satisfied DERY_WC_1 Routine Compliance
 
Meeting 02/19/2009 Satisfied DERY_WC_1 Non-Compliance
 
TCAR 02/19/2009 Satisfied DERY_WC_1 Closure
 
Letter 02/05/2009 Satisfied DERY_WC_1 Non-Compliance
 
Site Inspection 12/31/2008 In Compliance WINN_JP_1 0/2 Installation
 
Site Inspection 12/10/2008 In Compliance NEWBERG_DR_1 0/2 Closure
 
Record Document 07/22/2008 Satisfied DERY_WC_1 Installation
 
Phone Conversation 04/23/2008 Satisfied DERY_WC_1 Non-Compliance
 
Record Document 04/23/2008 Satisfied DERY_WC_1 Non-Compliance
 
Record Document 04/23/2008 Satisfied DERY_WC_1 Routine Compliance
 
Record Document 04/17/2008 Satisfied DERY_WC_1 Non-Compliance
 
Issue Document 02/05/2008 Satisfied DERY_WC_1 Non-Compliance
 
Issue Document 01/03/2008 Satisfied DERY_WC_1 Non-Compliance
 
Issue Document 01/03/2008 Satisfied DERY_WC_1 Non-Compliance
 
Issue Document 01/03/2008 Satisfied DERY_WC_1 Non-Compliance
 
Site Inspection 10/28/2007 Major Out of Compliance DERY_WC_1 0/3 Routine Compliance
 
Letter 10/28/2007 Satisfied DERY_WC_1 Non-Compliance
 
Emergency Preparedness Information 02/09/2007 Satisfied DERY_WC_1 Routine Compliance
 
Site Inspection 02/01/2007 In Compliance NEWBERG_DR_1 0/3 Routine Compliance
 
Phone Conversation 01/29/2007 Satisfied NEWBERG_DR_1 Routine Compliance
 
Emergency Preparedness Information 09/26/2006 Satisfied SLAPPEY_WR_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
10/31/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. 2022 and 2024 testing records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department.
 
10/31/2024 6006 Minor 2.5 Placard not displayed (or available upon request). A copy of the Placard must be obtained and provided to the Department.
 
10/31/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Premium spill bucket interstice port must be repaired or replaced and the Department notified.
 
10/31/2024 6062 Minor 2.5 Release detection devices not tested annually. Test records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department.
 
10/31/2024 6062 Minor 2.5 Release detection devices not tested annually. 2022 and 2024 testing records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department.
 
10/31/2024 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. The next two months (November & December) of inspections including the vacuum gauge readings must be provided to the Department as they are performed.
 
10/31/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Electrical junction box must be sealed and the Department notified.
 
10/31/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. 2022 and 2024 testing records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department.
 
10/31/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Test records must be provided to the Department or testing must be performed immediately and a copy of the test results provided to the Department.
 
06/20/2022 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Access to the interstice must be obtained and the Department notified.
 
04/03/2019 4077 Minor 4.12 Spill containment, sumps, and interstices not accessible. Water/regulated substances not timely removed. Petroleum contact water not properly managed. All dirt/mud and debris must be removed from the STP sumps and dispenser liners and the Department notified.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
03/03/1987   COMPLETED 50 EARLY DETECTION INCENTIVE-ELIGIBLE