Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/10/2025 Last Data Refresh: 05/09/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Retail Station | ||||||||
County | Pinellas | Status | OPEN | ||||||||
ID | 8623702 | Latitude | 27° 50' 47.8947 | ||||||||
Name |
CIRCLE K #4917 8201 66TH ST N |
Longitude | 82° 43' 42.003 | ||||||||
PINELLAS PARK, FL 33781 | LL Method | DPHO | |||||||||
Contact | GRAHAM BIGGS | LL Status | REVIEWED | ||||||||
Phone | (919) 774-6700 | Status Date | 10/07/2003 | ||||||||
Account Owner Information | |||||||||||
Name | CIRCLE K STORES INC 1100 Situs Ct Raleigh, NC 27606-5446 |
Effective Date | 05/20/1994 | ||||||||
Contact | IRA LEWIS | ||||||||||
Phone | (423) 400-2480 | ||||||||||
ILEWIS@CIRCLEK.COM | |||||||||||
Placard # / Date | 697692 - 06/28/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | CIRCLE K STORES INC 1100 Situs Ct Raleigh, NC 27606-5446 |
Effective Date | 05/20/1994 | ||||||||
Contact | IRA LEWIS | ||||||||||
Phone | (423) 400-2480 | ||||||||||
ILEWIS@CIRCLEK.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 10000 | Unleaded Gas (B) | 11/01/1987 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (S) DEP approved containment |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 10000 | Unleaded Gas (B) | 11/01/1987 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (S) DEP approved containment |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 10000 | Unleaded Gas (B) | 11/01/1987 | UNDERGROUND | Closed In Place (A) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (E) Fiberglass (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 5000 | Leaded Gas (A) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 5000 | Leaded Gas (A) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 5000 | Unleaded Gas (B) | UNDERGROUND | Removed from Site (B) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(Y) Unknown | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 5000 | Unleaded Gas (B) | UNDERGROUND | Closed In Place (A) | |||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (C) Fiberglass | (Y) Unknown | |||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
GUARANTEE | 04/28/2024 | 08/26/2025 | |||||||||
GUARANTEE | 04/30/2023 | 08/28/2024 | |||||||||
GUARANTEE | 04/24/2022 | 08/21/2023 | |||||||||
GUARANTEE | 04/25/2021 | 08/27/2022 | |||||||||
INSURANCE | 12/01/2020 | 12/01/2021 | NAVIGATORS SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2019 | 12/01/2020 | NAVIGATORS SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2018 | 12/01/2019 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2017 | 12/01/2018 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2016 | 12/01/2017 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2015 | 12/01/2016 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2014 | 12/01/2015 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2013 | 12/01/2014 | IRONSHORE SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/01/2011 | 12/01/2013 | CHUBB | ||||||||
INSURANCE | 12/01/2011 | 12/01/2012 | CHUBB | ||||||||
INSURANCE | 12/17/2010 | 12/17/2011 | CHUBB | ||||||||
INSURANCE | 12/17/2009 | 12/17/2010 | CHUBB | ||||||||
INSURANCE | 12/17/2008 | 12/17/2009 | AMERICAN INTERNATIONAL SPECIALTY LINES | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
LTR | 04/24/2006 | 04/26/2006 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||||||
TIN | 04/18/2006 | 04/26/2006 | IN-COMPLIANCE | FRAZIER | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes INSTALLATION OF A O SMITH DW FRP PIPING AND LINING OF TANKS | |||||||||||
LTR | 03/28/2006 | 03/28/2006 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||||||
TXI | 03/24/2006 | 03/28/2006 | IN-COMPLIANCE | FRAZIER | 0/4 | COMPLIANCE ASSURANCE | |||||
Completion Notes ONE 10,000G UST FILLED IN PLACE WITH FLOWABLE MATERIAL | |||||||||||
LTR | 02/22/2006 | 02/23/2006 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 02/21/2006 | 02/23/2006 | IN-COMPLIANCE | FRAZIER | 0/3 | COMPLIANCE ASSURANCE | |||||
CWOE | 08/12/2005 | 08/16/2005 | ROGGELIN | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 08/12/2005 | 08/16/2005 | COMPLIANCE ASSURANCE | ||||||||
NCLI | 07/11/2005 | 08/09/2005 | ROGGELIN | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 06/24/2005 | 07/01/2005 | MINOR OUT-OF-COMPLIANCE | ROGGELIN | 0/3 | COMPLIANCE ASSURANCE | |||||
DSUC | 07/19/2004 | 07/19/2004 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes STATUS TO BE DETERMINED BY DEP TALLAHASSEE CLEANUP | |||||||||||
SRRV | 07/15/2004 | 07/19/2004 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes DUE DILIGENCE REPORT | |||||||||||
LTR | 07/07/2004 | 07/11/2004 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes REQUESTED INFORMATION FROM CONOCO PHILLIPS | |||||||||||
LTR | 07/01/2004 | 07/11/2004 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes REQUESTED ANALYTICAL DATA & DRF FROM CIRCLE K | |||||||||||
RRBD | 06/25/2004 | 07/11/2004 | ROGGELIN | 0/0 | DISCHARGE PROJECT | ||||||
Completion Notes LTR FROM ATC ASSOCIATES - NO DRF & NO ANALYTICAL DATA | |||||||||||
TCR | 06/16/2004 | 06/24/2004 | IN-COMPLIANCE | PINK | 0/3 | COMPLIANCE ASSURANCE | |||||
NCLI | 06/16/2004 | 06/24/2004 | PINK | 0/0 | COMPLIANCE ASSURANCE | ||||||
LTR | 05/24/2004 | 06/01/2004 | ROGGELIN | 0/0 | COMPLIANCE ASSURANCE | ||||||
SV | 05/24/2004 | 06/01/2004 | ROGGELIN | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes DREW DIAGRAM OF SIX FORMER MONITORING WELLS; ALL CLOSED. | |||||||||||
LTR | 05/17/2004 | 05/23/2004 | ROGGELIN | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes LTD CLOSURE SUMMARY REPORT FOR VAPOR RECOVERY SPILL CONTAINMENT | |||||||||||
RRBD | 05/03/2004 | 05/23/2004 | COMPLIANCE ASSURANCE | ||||||||
NCLI | 04/23/2004 | 04/29/2004 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 04/20/2004 | 04/29/2004 | SIGNIFICANT OUT-OF-COMPLIANCE | FRAZIER | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 03/14/2003 | 04/07/2003 | COMPLIANCE ASSURANCE | ||||||||
NCLI | 02/10/2003 | 02/12/2003 | STRAUSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 02/04/2003 | 02/12/2003 | MINOR OUT-OF-COMPLIANCE | STRAUSS | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes SW AMERON FRP PIPE | |||||||||||
RRBD | 03/25/2002 | 04/09/2002 | COMPLIANCE ASSURANCE | ||||||||
NCLI | 03/14/2002 | 03/18/2002 | STRAUSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 03/12/2002 | 03/18/2002 | MINOR OUT-OF-COMPLIANCE | STRAUSS | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 02/22/2001 | 03/07/2001 | IN-COMPLIANCE | STRAUSS | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 05/09/2000 | 05/22/2000 | IN-COMPLIANCE | CASTOR | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 05/13/1999 | 06/13/1999 | IN-COMPLIANCE | DUGGAN | 0/0 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 09/12/2024 | Major Out of Compliance | PUHR_NM_1 | 0/2 | Routine Compliance | ||||||
Letter | 09/12/2024 | Satisfied | PUHR_NM_1 | Compliance Assistance | |||||||
Letter | 08/28/2024 | Satisfied | WIMBERLY_E | Enforcement | |||||||
Enforcement Referral | 10/18/2023 | Accepted | JUARISTIC_GK_1 | Enforcement | |||||||
Electronic Communication | 10/18/2023 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Electronic Communication | 10/05/2023 | Satisfied | JUARISTIC_GK_1 | Compliance Assistance | |||||||
Site Inspection | 04/11/2023 | Major Out of Compliance | COLSON_NJ_1 | 0/2 | Routine Compliance | ||||||
Letter | 04/11/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Electronic Communication | 12/09/2022 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Site Inspection | 05/06/2021 | Major Out of Compliance | COLSON_NJ_1 | 0/2 | Routine Compliance | ||||||
Letter | 05/06/2021 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Electronic Communication | 03/04/2021 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Letter | 12/10/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Record Document | 12/10/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Letter | 09/19/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Site Inspection | 09/19/2018 | Minor Out of Compliance | COLSON_NJ_1 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 09/06/2018 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Letter | 07/02/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Site Inspection | 07/02/2018 | In Compliance | COLSON_NJ_1 | 0/2 | Compliance Assistance | ||||||
Letter | 10/18/2016 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Site Inspection | 10/18/2016 | Minor Out of Compliance | COLSON_NJ_1 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 09/28/2016 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Electronic Communication | 08/26/2016 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Incident | 08/10/2015 | Has not led to Discharge | COLSON_NJ_1 | Incident | |||||||
Document Management | 08/10/2015 | Complete | COLSON_NJ_1 | Incident | |||||||
Site Inspection | 08/11/2014 | In Compliance | COLSON_NJ_1 | 0/2 | Routine Compliance | ||||||
Issue Document | 08/11/2014 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 08/11/2014 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Site Inspection | 02/04/2013 | In Compliance | SOWERS_JA_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 05/23/2012 | In Compliance | LONGEN_JL_1 | 0/2 | Non-Compliance | ||||||
Site Inspection | 05/03/2012 | Minor Out of Compliance | LONGEN_JL_1 | 0/2 | Non-Compliance | ||||||
Letter | 05/03/2012 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 03/02/2012 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 03/02/2012 | Minor Out of Compliance | LONGEN_JL_1 | 0/2 | Routine Compliance | ||||||
Letter | 03/02/2012 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Incident | 04/25/2011 | Has not led to Discharge | LONGEN_JL_1 | Incident | |||||||
Emergency Preparedness Information | 01/06/2011 | Satisfied | LONGEN_JL_1 | Routine Compliance | |||||||
Site Inspection | 01/06/2011 | In Compliance | LONGEN_JL_1 | 0/2 | Routine Compliance | ||||||
Incident | 11/12/2010 | Has not led to Discharge | LONGEN_JL_1 | Incident | |||||||
Record Document | 01/22/2010 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 01/16/2010 | Major Out of Compliance | LONGEN_JL_1 | 0/2 | Routine Compliance | ||||||
Letter | 01/16/2010 | Major Out of Compliance | LONGEN_JL_1 | Non-Compliance | |||||||
Record Document | 11/03/2009 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 06/15/2009 | In Compliance | SOWERS_JA_1 | 0/1 | Non-Compliance | ||||||
Letter | 05/29/2009 | Satisfied | BARNETT_JX | Non-Compliance | |||||||
Site Inspection | 05/29/2009 | Minor Out of Compliance | BARNETT_JX | 0/2 | Non-Compliance | ||||||
Record Document | 04/27/2009 | Satisfied | BARNETT_JX | Non-Compliance | |||||||
Letter | 04/24/2009 | Satisfied | BARNETT_JX | Non-Compliance | |||||||
Emergency Preparedness Information | 04/24/2009 | Satisfied | BARNETT_JX | Routine Compliance | |||||||
Site Inspection | 04/24/2009 | Minor Out of Compliance | BARNETT_JX | 0/2 | Routine Compliance | ||||||
Letter | 06/09/2008 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 06/09/2008 | Minor Out of Compliance | LONGEN_JL_1 | 0/2 | Routine Compliance | ||||||
Emergency Preparedness Information | 06/09/2008 | Satisfied | LONGEN_JL_1 | Routine Compliance | |||||||
Record Document | 03/05/2008 | Satisfied | ROGGELIN_EM_1 | Routine Compliance | |||||||
Record Document | 03/05/2008 | Satisfied | ROGGELIN_EM_1 | Routine Compliance | |||||||
Record Document | 01/31/2008 | Satisfied | SOWERS_JA_1 | Non-Compliance | |||||||
Site Inspection | 07/03/2007 | In Compliance | ROGGELIN_EM_1 | 0/2 | Non-Compliance | ||||||
Site Inspection | 02/06/2007 | Minor Out of Compliance | ROGGELIN_EM_1 | 0/2 | Routine Compliance | ||||||
Emergency Preparedness Information | 02/06/2007 | Satisfied | LONGEN_JL_1 | Routine Compliance | |||||||
Letter | 01/05/2007 | Satisfied | SOWERS_JA_1 | Non-Compliance | |||||||
Site Inspection | 01/04/2007 | Major Out of Compliance | SOWERS_JA_1 | 0/2 | Routine Compliance | ||||||
TCAR | 11/20/2006 | Satisfied | STRAUSS_RH_1 | Closure | |||||||
Emergency Preparedness Information | 09/25/2006 | Satisfied | BARNETT_JX | Routine Compliance | |||||||
Emergency Preparedness Information | 09/22/2006 | Satisfied | LONGEN_JL_1 | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
09/12/2024 | 6009 | Minor | 4.1 Incident Notification Form (INF) not received in a timely manner. | *Be sure to investigate incidents immediately. Submit explanations and resolution documentation for the historical tank interstice alarms. | |||||||
09/12/2024 | 6015 | Minor | 4.3 Incident investigation not completed within 14 days, and/or no DRF or written confirmation received at the end of the 14-day investigation period. | *Be sure to investigate incidents immediately. Submit explanations and resolution documentation for the historical tank interstice alarms.* | |||||||
09/12/2024 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | *Pump out the STP sumps and provide documentation to this office once completed. *Provide documentation that the monitoring point is open on the double walled pipe interstice in sumps. *Ensure sensor is properly positioned. *Pump out the Regular spill bucket and provide documentation to this office once completed. *Pump out the liquid from both dispensers and provide documentation to this office once completed. | |||||||
09/12/2024 | 6014 | SNC-B | 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. | *Be sure to investigate incidents immediately. Submit explanations and resolution documentation for the historical tank interstice alarms. | |||||||
04/10/2023 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Be sure to have the required integrity testing performed within 36 months of the last test date. Submit current integrity test results for the (2) STP sumps to this office for review. | |||||||
04/10/2023 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Remove & properly dispose of the accumulated liquid in the Premium spill bucket. Submit a pumpout receipt and/or photo to this office once corrected. | |||||||
04/10/2023 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Remove any accumulated liquid from the Secondary spill bucket. Repair or replace the illegible EZ Gauge. Vacuum test the Premium spill bucket per manufacturer specifications. Submit the test results to this office for review. | |||||||
04/10/2023 | 6017 | Minor | 4.4 All incident records, including test results not kept until storage tank system closure. | Be sure to investigate incidents immediately. Submit explanations and resolution documentation for the historical tank interstice alarms. | |||||||
04/10/2023 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Be sure to have the required integrity testing performed within 36 months of the last test date. Submit current integrity test results for the (2) dispenser liners to this office for review. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
12/19/1986 | COMPLETED | 10 | EARLY DETECTION INCENTIVE-ELIGIBLE | ||||||||