DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Retail Station
 
County Pinellas   Status    OPEN
 
ID 8623718   Latitude    28° 0' 51.3576
 
Name CIRCLE K #2704007
2521 MCMULLEN BOOTH RD
Longitude    82° 42' 30.6459
  SAFETY HARBOR, FL 33519 LL Method    DPHO
 
Contact GRAHAM BIGGS   LL Status    REVIEWED
 
Phone (919) 774-6700   Status Date    10/14/2003
 
Account Owner Information
 
Name CIRCLE K STORES INC
1100 Situs Ct
Raleigh, NC 27606-5446
Effective Date    05/20/1994
 
Contact IRA LEWIS
 
Phone (423) 400-2480
 
Email ILEWIS@CIRCLEK.COM
  Placard # / Date    697693 - 06/28/2024
No Property Owner Information Found
 
 
Tank Tank Size Content Installed Placement Status
1 10058 Unleaded Gas (B) 09/01/1983 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(H) Impressed current CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(S) DEP approved containment
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
2 10058 Unleaded Gas (B) 09/01/1983 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(H) Impressed current CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(S) DEP approved containment
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
3 10058 Unleaded Gas (B) 09/01/1983 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(H) Impressed current CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(S) DEP approved containment
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   04/30/2023 08/28/2024
INSURANCE   04/25/2021 08/27/2022 IRONSHORE SPECIALTY INSURANCE CO
GUARANTEE   12/03/2020 04/30/2023
INSURANCE   12/01/2018 12/01/2019 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2017 12/01/2018 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2016 12/01/2017 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2015 12/01/2016 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2013 12/01/2014 IRONSHORE SPECIALTY INSURANCE CO
INSURANCE   12/01/2011 12/01/2012 CHUBB
INSURANCE   12/17/2010 12/17/2011 CHUBB
INSURANCE   12/17/2009 12/17/2010 CHUBB
INSURANCE   12/17/2007 12/17/2008 AMERICAN INTERNATIONAL SPECIALTY LINES
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
RRBD 04/06/2006 04/17/2006 SOWERS 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes UPDATED TEST RESULTS SUBMITTED
 
LTR 03/28/2006 04/17/2006 SOWERS 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes EMAIL TO FRAN FRANCONI ABOUT NO LEAK RATE INIDICATED ON TEST RESULTS FOR L L D'S
 
RRBD 03/03/2006 04/17/2006 BARNETT 0/0 COMPLIANCE ASSURANCE
 
NCLI 03/01/2006 03/01/2006 BARNETT 0/3 COMPLIANCE ASSURANCE
 
TCI 02/27/2006 03/01/2006 MINOR OUT-OF-COMPLIANCE BARNETT 0/3 COMPLIANCE ASSURANCE
 
LTR 09/01/2005 09/01/2005 SOWERS 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes LETTER ISSUED THAT ACCEPTS CLOSURE REPORT - PLEASE SEE LETTER IN FILE FOR COMMENTS
 
RRBD 08/29/2005 09/01/2005 SOWERS 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes SUBMITTAL OF RESPONSE TO COMMENT LETTER
 
LTR 08/22/2005 08/22/2005 SOWERS 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes "NO RESPONSE" LETTER ISSUED WITH REGARD TO CLOSURE REPORT SUBMITTED 4/29/04
 
NCLI 07/11/2005 08/09/2005 ROGGELIN 0/0 COMPLIANCE ASSURANCE
 
TCI 06/22/2005 07/01/2005 IN-COMPLIANCE ROGGELIN 0/3 COMPLIANCE ASSURANCE
 
RRBD 07/19/2004 09/13/2004 BARNETT 0/0 COMPLIANCE ASSURANCE
 
LTR 05/22/2004 07/09/2004 SOWERS 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes REVIEW LETTER FOR CLOSURE REPORT
 
RRBD 04/29/2004 08/22/2005 SOWERS 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes SUBMITTAL OF CLOSURE REPORT
 
NCLI 04/23/2004 04/29/2004 BARNETT 0/0 COMPLIANCE ASSURANCE
 
TCDI 04/16/2004 04/29/2004 SIGNIFICANT OUT-OF-COMPLIANCE ROGGELIN 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes AO SMITH DW FRP PIPE
 
LTR 11/03/2002 11/05/2002 TAM 0/0 COMPLIANCE ASSURANCE
 
TCI 11/01/2002 11/05/2002 IN-COMPLIANCE TAM 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes AO SMITH DW FRP PIPE
 
TCI 09/04/2001 09/09/2001 IN-COMPLIANCE HALSCOTT 0/3 COMPLIANCE ASSURANCE
 
RRBD 10/19/2000 10/26/2000 HALSCOTT 0/0 COMPLIANCE ASSURANCE
 
TCI 10/05/2000 10/17/2000 MINOR OUT-OF-COMPLIANCE HALSCOTT 0/3 COMPLIANCE ASSURANCE
 
TCI 05/10/2000 05/22/2000 IN-COMPLIANCE CASTOR 0/3 COMPLIANCE ASSURANCE
 
RRBD 01/28/1999 03/02/1999 PUGH 0/3 COMPLIANCE ASSURANCE
 
TCI 01/15/1999 02/25/1999 MINOR OUT-OF-COMPLIANCE PUGH_R 0/3 COMPLIANCE ASSURANCE
 
UTDI 11/25/1997 12/02/1997 MINOR OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Letter 08/28/2024 Satisfied WIMBERLY_E Enforcement
 
Enforcement Referral 06/19/2024 Accepted TUCKER_SX_1 Enforcement
 
Record Document 06/14/2024 Satisfied TUCKER_SX_1 Compliance Assistance
 
Record Document 06/14/2024 Satisfied TUCKER_SX_1 Compliance Assistance
 
Record Document 06/14/2024 Satisfied TUCKER_SX_1 Compliance Assistance
 
Electronic Communication 06/04/2024 Satisfied TUCKER_SX_1 Routine Compliance
 
Letter 03/08/2024 Satisfied TUCKER_SX_1 Compliance Assistance
 
Site Inspection 02/29/2024 Major Out of Compliance TUCKER_SX_1 0/3 Routine Compliance
 
Electronic Communication 12/18/2023 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Record Document 09/16/2022 Satisfied SHOCK_E_1 Compliance Assistance
 
Letter 09/06/2022 Satisfied SHOCK_E_1 Compliance Assistance
 
Record Document 08/29/2022 Satisfied SHOCK_E_1 Compliance Assistance
 
Record Document 02/23/2022 Satisfied SHOCK_E_1 Compliance Assistance
 
Site Inspection 02/22/2022 Minor Out of Compliance SHOCK_E_1 0/3 Routine Compliance
 
Letter 02/22/2022 Satisfied SHOCK_E_1 Compliance Assistance
 
Electronic Communication 12/29/2021 Satisfied JUARISTIC_GK_1 Routine Compliance
 
Incident 09/24/2019 Has not led to Discharge STRAUSS_RH_1 Incident
 
Document Management 09/24/2019 Satisfied STRAUSS_RH_1 Incident
 
Record Document 06/04/2019 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Letter 06/04/2019 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Site Inspection 02/26/2019 Minor Out of Compliance STRAUSS_RH_1 0/3 Routine Compliance
 
Letter 02/26/2019 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Electronic Communication 02/11/2019 Satisfied STRAUSS_RH_1 Routine Compliance
 
Incident 04/30/2018 Has not led to Discharge STRAUSS_RH_1 Incident
 
Document Management 02/16/2018 Satisfied STRAUSS_RH_1 Incident
 
Site Inspection 06/26/2017 In Compliance STRAUSS_RH_1 0/3 Compliance Assistance
 
Electronic Communication 06/26/2017 Satisfied STRAUSS_RH_1 Compliance Assistance
 
Site Inspection 05/23/2017 Major Out of Compliance STRAUSS_RH_1 0/3 Non-Compliance
 
Letter 05/23/2017 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 11/09/2016 Major Out of Compliance STRAUSS_RH_1 0/3 Routine Compliance
 
Letter 11/09/2016 Satisfied STRAUSS_RH_1 Non-Compliance
 
Electronic Communication 10/04/2016 Satisfied STRAUSS_RH_1 Routine Compliance
 
Emergency Preparedness Information 09/29/2014 Satisfied STRAUSS_RH_1 Routine Compliance
 
Site Inspection 08/13/2014 In Compliance STRAUSS_RH_1 0/3 Non-Compliance
 
Site Inspection 07/10/2014 Minor Out of Compliance STRAUSS_RH_1 0/3 Routine Compliance
 
Letter 07/10/2014 Satisfied STRAUSS_RH_1 Non-Compliance
 
Incident 04/02/2012 Has not led to Discharge LONGEN_JL_1 Incident
 
Record Document 04/02/2012 Satisfied LONGEN_JL_1 Non-Compliance
 
Letter 03/05/2012 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 03/05/2012 Minor Out of Compliance LONGEN_JL_1 0/3 Routine Compliance
 
Emergency Preparedness Information 03/05/2012 Satisfied LONGEN_JL_1 Routine Compliance
 
Record Document 01/19/2011 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 01/06/2011 Minor Out of Compliance LONGEN_JL_1 0/3 Routine Compliance
 
Emergency Preparedness Information 01/06/2011 Satisfied LONGEN_JL_1 Routine Compliance
 
Letter 01/06/2011 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 01/27/2010 In Compliance LONGEN_JL_1 0/3 Non-Compliance
 
Letter 01/21/2010 Minor Out of Compliance LONGEN_JL_1 Non-Compliance
 
Site Inspection 01/21/2010 Minor Out of Compliance LONGEN_JL_1 0/3 Routine Compliance
 
TCAR 03/16/2009 Satisfied STRAUSS_RH_1 Closure
 
Record Document 01/21/2009 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 12/04/2008 Minor Out of Compliance STRAUSS_RH_1 0/3 Installation
 
Letter 12/04/2008 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 12/04/2008 In Compliance LONGEN_JL_1 0/3 Closure
 
Site Inspection 02/08/2007 In Compliance ROGGELIN_EM_1 0/2 Non-Compliance
 
Emergency Preparedness Information 02/05/2007 Satisfied BARNETT_JX Routine Compliance
 
Letter 01/05/2007 Satisfied SOWERS_JA_1 Non-Compliance
 
Site Inspection 01/02/2007 Major Out of Compliance SOWERS_JA_1 0/3 Routine Compliance
 
Emergency Preparedness Information 09/20/2006 Satisfied BARNETT_JX Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/29/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Remove and properly dispose of the PCW in all three spill buckets.
 
02/29/2024 6029 Minor 4.1 Any component(s) of the storage tank system not installed according to manufacturer's instructions. Position the sensor per manufacturer specifications, vertically at the bottom of the sump.
 
02/29/2024 6024 Minor 2.2 Integrity test not performed on storage tank, integral piping, single-walled spill containment system, double-walled spill containment system, or doubled-walled sump prior to placing into service. Repair the PUL STP sump and provide post-repair passing integrity test results.
 
02/29/2024 6016 SNC-B 4.7 Removal of regulated substance from a release into secondary containment not initiated within three days and completed within 30 days of discovery. Provide maintenance records showing that the liquid was properly removed within 72-hours of each fuel alarm from 1/17/2023 to 12/18/2023.
 
02/29/2024 6056 SNC-B 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. Provide accurate release detection results for the next two consecutive months.
 
02/29/2024 6014 SNC-B 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. Provide investigation results for all reported fuel alarms between 1/17/2023 and 12/18/2023.
 
02/29/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Repair/replace the PUL STP.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
03/16/2004   COMPLETED 30
 
11/14/1997   COMPLETED
 
04/01/1997   COMPLETED
 
12/16/1996   COMPLETED
 
07/02/1990   COMPLETED 50 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE