District Southwest   Type    Retail Station
 
County Polk   Status    OPEN
 
ID 8624000   Latitude    28° 2' 4.4079
 
Name R S PETRO LAKE
825 S FLORIDA AVE
Longitude    81° 57' 26.8814
  LAKELAND, FL 33801-5234 LL Method    DPHO
 
Contact SHAHID RAHMAN   LL Status    REVIEWED
 
Phone (863) 816-3374   Status Date    02/12/2024
 
Account Owner Information
 
Name PATEL, MAYUR
825 S FLORIDA AVE
LAKELAND, FL 33801
Effective Date    04/13/2001
 
Contact MAYUR PATEL
 
Phone (863) 670-7801
 
Email
  Placard # / Date    699114 - 07/09/2024
Property Owner Information
 
Name PATEL, MAYUR
825 S FLORIDA AVE
LAKELAND, FL 33801
Effective Date    04/13/2001
 
Contact MAYUR PATEL
 
Phone (863) 670-7801
 
Email
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
7 20000 Unleaded Gas (B) 03/01/2009 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(L) Compartmented
(M) Spill containment bucket
(O) Tight fill
(P) Level gauges/alarms
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(1) Continuous electronic sensing
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
1 15546 Unleaded Gas (B) 07/01/1960 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve   (B) Steel/galvanized metal (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
2 15546 Unleaded Gas (B) 07/01/1960 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve   (B) Steel/galvanized metal (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
3 9988 Unleaded Gas (B) 07/01/1960 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve   (B) Steel/galvanized metal (8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
4 8000 Unleaded Gas (B) 02/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
5 8000 Unleaded Gas (B) 02/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
6 8000 Unleaded Gas (B) 02/01/1989 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(E) Fiberglass
(M) Spill containment bucket
(O) Tight fill
  (C) Fiberglass
(J) Pressurized piping system
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   03/04/2021 03/04/2022 ACE AMERICAN INSURANCE COMPANY
INSURANCE   03/04/2020 03/04/2021 ACE AMERICAN INSURANCE COMPANY
INSURANCE   03/04/2019 03/04/2020 ACE AMERICAN INSURANCE COMPANY
INSURANCE   03/04/2018 03/04/2019 ACE AMERICAN INSURANCE COMPANY
INSURANCE   03/04/2018 03/04/2019 ACE
INSURANCE   03/04/2017 03/04/2018 ACE AMERICAN INSURANCE COMPANY
INSURANCE   03/04/2017 05/04/2018 ACE
INSURANCE   03/04/2016 03/04/2017 ACE
INSURANCE   02/04/2014 02/04/2015 NAUTILUS INSURANCE COMPANY
INSURANCE   02/04/2013 02/04/2014 NAUTILUS INSURANCE COMPANY
INSURANCE   07/22/2011 07/22/2012 ZURICH-AMERICAN
INSURANCE   07/22/2011 07/22/2012 ZURICH-AMERICAN
INSURANCE   07/22/2010 07/22/2011 ZURICH-AMERICAN
INSURANCE   07/22/2008 07/22/2009 ZURICH-AMERICAN
INSURANCE   07/29/2000 07/29/2001 ZURICH-AMERICAN
INSURANCE   01/26/1999 12/26/1999 COMMERCE & INDUSTRY
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
NCLI 06/21/2005 06/21/2005 CROWELL_M 0/0 COMPLIANCE ASSURANCE
 
RRBD 06/15/2005 08/18/2005 CROWELL_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RESOLVES VIOLATION #1077, 1103, 1122, 1123.
 
TCI 05/24/2005 06/21/2005 SIGNIFICANT OUT-OF-COMPLIANCE CROWELL_M 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes 1 PHOTO TAKEN.
 
TCI 04/29/2004 05/12/2004 IN-COMPLIANCE HUGHES_J 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes NO PHOTOS TAKEN. PIPING: SINGLE WALLED RIGID FIBERGLASS PIPING-UNABLE TO DETERMINE IF ABOVE GROUND OR UNDER GROUND OR WHAT MAKER. RESOLVES VIOLATION #87.
 
CWOE 04/29/2004 05/12/2004 HUGHES_J 0/0 COMPLIANCE ASSURANCE
 
RRBD 06/12/2003 06/16/2003 SACLARIDES_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RESOLVES VIOLATION #103.
 
RRBD 06/10/2003 06/16/2003 SACLARIDES_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RESOLVES VIOLATION #3.
 
RRBD 06/09/2003 06/16/2003 SACLARIDES_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RESOLVES VIOLATION #157, #110, & #142
 
RRBD 04/23/2003 06/16/2003 SACLARIDES_M 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes RESOLVES VIOLATION #95.
 
NCLI 04/08/2003 04/10/2003 SACLARIDES_M 0/0 COMPLIANCE ASSURANCE
 
TCI 03/26/2003 04/10/2003 SIGNIFICANT OUT-OF-COMPLIANCE SACLARIDES_M 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes ONE PHOTO TAKEN
 
RRBD 06/24/2002 06/25/2002 PEGUES_M 0/0 COMPLIANCE ASSURANCE
 
TCI 04/17/2002 04/22/2002 MINOR OUT-OF-COMPLIANCE PEGUES_M 0/3 COMPLIANCE ASSURANCE
 
NCLI 04/17/2002 04/22/2002 PEGUES_M 0/0 COMPLIANCE ASSURANCE
 
NCLI 03/09/2001 03/14/2001 MURRAY 0/0 COMPLIANCE ASSURANCE
 
TCI 03/01/2001 03/14/2001 MINOR OUT-OF-COMPLIANCE SACLARIDES 0/3 COMPLIANCE ASSURANCE
 
TCI 11/30/1999 12/02/1999 IN-COMPLIANCE HUGHES_J 0/3 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Phone Conversation 05/15/2024 Satisfied CASSELS_CR_2 Routine Compliance
 
Electronic Communication 05/15/2024 Satisfied CASSELS_CR_2 Routine Compliance
 
Phone Conversation 05/15/2024 Satisfied CASSELS_CR_2 Routine Compliance
 
Electronic Communication 05/15/2024 Satisfied CASSELS_CR_2 Routine Compliance
 
Phone Conversation 05/15/2024 Satisfied CASSELS_CR_2 Routine Compliance
 
Electronic Communication 04/28/2021 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 04/27/2021 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 04/27/2021 Satisfied CASSELS_CR_2 Routine Compliance
 
Site Inspection 04/27/2021 Major Out of Compliance CASSELS_CR_2 0/1 Routine Compliance
 
Letter 04/27/2021 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 04/27/2021 Satisfied CASSELS_CR_2 Routine Compliance
 
Electronic Communication 04/27/2021 Satisfied CASSELS_CR_2 Routine Compliance
 
Electronic Communication 06/24/2019 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 06/24/2019 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 02/27/2019 Satisfied CASSELS_CR_2 Routine Compliance
 
Letter 02/27/2019 Satisfied CASSELS_CR_2 Compliance Assistance
 
Electronic Communication 02/27/2019 Satisfied CASSELS_CR_2 Routine Compliance
 
Electronic Communication 02/27/2019 Satisfied CASSELS_CR_2 Compliance Assistance
 
Site Inspection 02/27/2019 Major Out of Compliance CASSELS_CR_2 0/1 Routine Compliance
 
Enforcement Tracking 05/11/2018 Closed Without Enforcement BROWNLEE_S Enforcement
 
Electronic Communication 05/10/2018 Satisfied BROWNLEE_S Enforcement
 
Electronic Communication 05/09/2018 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Letter 05/09/2018 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Site Inspection 05/09/2018 In Compliance WILLIAMSON_KE_1 0/1 Compliance Assistance
 
Phone Conversation 02/23/2018 Satisfied BROWNLEE_S Enforcement
 
Phone Conversation 12/29/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Electronic Communication 12/20/2017 Satisfied BROWNLEE_S Enforcement
 
Enforcement Referral 12/18/2017 Accepted WILLIAMSON_KE_1 Enforcement
 
Electronic Communication 12/12/2017 Satisfied WILLIAMSON_KE_1 Compliance Assistance
 
Letter 03/27/2017 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Electronic Communication 03/27/2017 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Electronic Communication 11/09/2016 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Letter 10/25/2016 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Site Inspection 10/25/2016 Minor Out of Compliance WILLIAMSON_KE_1 0/1 Routine Compliance
 
Electronic Communication 10/25/2016 Satisfied WILLIAMSON_KE_1 Non-Compliance
 
Electronic Communication 04/20/2015 Satisfied MERRYMAN_DT_1 Non-Compliance
 
Phone Conversation 04/20/2015 Satisfied MERRYMAN_DT_1 Non-Compliance
 
Electronic Communication 04/20/2015 Satisfied MERRYMAN_DT_1 Non-Compliance
 
Phone Conversation 04/20/2015 Satisfied MERRYMAN_DT_1 Non-Compliance
 
Record Document 04/20/2015 Satisfied MERRYMAN_DT_1 Non-Compliance
 
Phone Conversation 04/20/2015 Satisfied MERRYMAN_DT_1 Non-Compliance
 
Phone Conversation 04/17/2015 Satisfied MERRYMAN_DT_1 Non-Compliance
 
Phone Conversation 04/15/2015 Satisfied MERRYMAN_DT_1 Non-Compliance
 
Phone Conversation 04/15/2015 Satisfied MERRYMAN_DT_1 Non-Compliance
 
Site Inspection 05/28/2014 Major Out of Compliance NEWBERG_DR_1 0/1 Routine Compliance
 
Letter 05/28/2014 Satisfied NEWBERG_DR_1 Non-Compliance
 
Electronic Communication 05/28/2014 Satisfied NEWBERG_DR_1 Routine Compliance
 
Site Inspection 04/30/2013 Minor Out of Compliance WINN_JP_1 0/1 Routine Compliance
 
Letter 04/30/2013 Satisfied WINN_JP_1 Non-Compliance
 
Site Inspection 03/26/2012 In Compliance CASSELS_CR_1 0/1 Non-Compliance
 
Phone Conversation 03/20/2012 Satisfied CASSELS_CR_1 Non-Compliance
 
Electronic Communication 03/13/2012 Satisfied CASSELS_CR_1 Non-Compliance
 
Phone Conversation 03/13/2012 Satisfied CASSELS_CR_1 Non-Compliance
 
Phone Conversation 03/13/2012 Satisfied CASSELS_CR_1 Non-Compliance
 
Phone Conversation 03/13/2012 Satisfied CASSELS_CR_1 Non-Compliance
 
Site Inspection 02/10/2012 Major Out of Compliance CASSELS_CR_1 0/1 Routine Compliance
 
Letter 02/10/2012 Satisfied CASSELS_CR_1 Non-Compliance
 
TCAR 12/07/2011 Satisfied BELL_JM_1 Closure
 
Letter 12/07/2011 Satisfied BELL_JM_1 Discharge
 
TCAR 12/07/2011 Incomplete BELL_JM_1 Closure
 
Site Inspection 09/09/2011 In Compliance WINN_JP_1 0/1 Installation
 
Site Inspection 09/09/2011 In Compliance WINN_JP_1 0/1 Closure
 
Meeting 08/29/2011 Satisfied WINN_JP_1 Non-Compliance
 
Phone Conversation 08/23/2011 Satisfied DERY_WC_1 Non-Compliance
 
Phone Conversation 08/23/2011 Satisfied DERY_WC_1 Non-Compliance
 
Phone Conversation 08/09/2011 Satisfied DERY_WC_1 Non-Compliance
 
Phone Conversation 07/25/2011 Satisfied BELL_JM_1 Non-Compliance
 
Letter 07/15/2011 Satisfied BELL_JM_1 Non-Compliance
 
Letter 07/14/2011 Satisfied BELL_JM_1 Non-Compliance
 
Phone Conversation 06/20/2011 Satisfied BELL_JM_1 Non-Compliance
 
Letter 05/19/2011 Satisfied BELL_JM_1 Non-Compliance
 
Site Inspection 05/19/2011 Major Out of Compliance BELL_JM_1 0/1 Routine Compliance
 
Letter 06/23/2009 Satisfied CASSELS_CR_1 Closure
 
TCAR 06/23/2009 Satisfied CASSELS_CR_1 Closure
 
Letter 05/13/2009 Satisfied BELL_JM_1 Non-Compliance
 
Site Inspection 05/07/2009 In Compliance CASSELS_CR_1 0/1 Installation
 
Site Inspection 03/17/2009 In Compliance BELL_JM_1 0/4 Closure
 
Record Document 02/26/2009 Satisfied BELL_JM_1 Installation
 
Phone Conversation 02/26/2009 Satisfied BELL_JM_1 Installation
 
Phone Conversation 02/26/2009 Satisfied BELL_JM_1 Installation
 
Phone Conversation 01/08/2009 Satisfied CASSELS_CR_1 Installation
 
Phone Conversation 01/08/2009 Satisfied CASSELS_CR_1 Routine Compliance
 
Phone Conversation 01/08/2009 Satisfied CASSELS_CR_1 Closure
 
Site Inspection 01/22/2008 In Compliance SLAPPEY_WR_1 0/3 Routine Compliance
 
Site Inspection 05/01/2007 In Compliance RANDOLPH_L 0/3 QA/QC
 
Issue Document 05/01/2007 Satisfied RANDOLPH_L QA/QC
 
Record Document 03/23/2007 Satisfied NEWBERG_DR_1 Non-Compliance
 
Letter 02/21/2007 Satisfied NEWBERG_DR_1 Non-Compliance
 
Site Inspection 02/21/2007 Major Out of Compliance NEWBERG_DR_1 0/3 Non-Compliance
 
Record Document 02/21/2007 Satisfied NEWBERG_DR_1 Non-Compliance
 
Emergency Preparedness Information 02/12/2007 Satisfied NEWBERG_DR_1 Routine Compliance
 
Site Inspection 12/19/2006 Major Out of Compliance NEWBERG_DR_1 0/3 Routine Compliance
 
Letter 12/19/2006 Satisfied NEWBERG_DR_1 Non-Compliance
 
Phone Conversation 12/14/2006 Satisfied NEWBERG_DR_1 Routine Compliance
 
Emergency Preparedness Information 09/19/2006 Satisfied CASSELS_CR_1 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
05/16/2024 6062 Minor 2.5 Release detection devices not tested annually. The spill bucket interstitial gauge test records must be submitted to the Department. If the tests have not been completed, they must be completed immediately with a copy of the report submitted to the Department.
 
05/16/2024 6062 Minor 2.5 Release detection devices not tested annually. The line leak detector test records must be submitted to the Department. If the tests have not been completed, they must be completed immediately with a copy of the report submitted to the Department.
 
05/15/2024 6006 Minor 2.5 Placard not displayed (or available upon request). A current Storage Tank Registration Placard must be posted at all times. The current Placard must be printed and posted with a copy also submitted to the Department.
 
05/15/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. The overfill protection equipment test records must be submitted to the Department. If the tests have not been completed, they must be completed immediately with a copy of the report submitted to the Department.
 
05/15/2024 6062 Minor 2.5 Release detection devices not tested annually. The Veeder-Root electronic monitor test records must be submitted to the Department. If the test has not been completed, it must be completed immediately with a copy of the report submitted to the Department.
 
05/15/2024 6043 Minor 4.13 Fillbox covers not marked according to requirements. The diesel spill bucket cover must be properly marked yellow, and the two gasoline vapor port covers must be properly marked orange, per API RP 1637, and the Department notified.
 
05/15/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Access must be provided to all tank components. The Owner/Operator or contractor is responsible for setting up all protective cones, caution tape, flags, and/or barricades around all equipment for the duration of the inspection. The facility owner or operator shall provide an authorized facility representative to unlock and open any covers, manways, and release detection equipment associated with the storage tank system. When proper access can be provided, including all safety cones to block vehicle access, the Department must be notified.
 
05/15/2024 6013 Minor 2.10 Appropriate paperwork for financial responsibility improperly completed or maintained. The 2022-2023 and 2023-2024 Financial Responsibility documentation must be submitted to the Department. was submitted to the Department after the inspection.
 
04/27/2021 4015 Minor 2.10 Incomplete documentation demonstrating financial responsibility. A DEP Certification of Financial Responsibility (CFR) Form Part P must be completed for each policy period of the pollution liability insurance, with a copy of each submitted to the Department.
 
04/27/2021 4059 SNC-B 4.1 Release detection, including visual inspections not being conducted monthly (not to exceed 35 days.) For electronically monitored sumps, visual inspections not conducted every 6 months. This violation may lead to Placard Revocation and Delivery Prohibition. The monthly visual inspections must be completed once per month and not more than 35 days in between. Copies of the next two months of visual inspections must be submitted to the Department as each one is completed.
 
04/27/2021 4051 Minor 4.26 Dispenser sumps not installed to allow for release detection. The dispenser liner footprint must be large enough to encompass all dispenser mechanisms above it, in case of leakage, or a device must be installed to divert any leaking product into the liner, and the Department notified.
 
04/27/2021 4001 Minor 2.2 Operator certification requirements not met. The required Class C Operator Training & Certification program must be completed for the appropriate facility personnel immediately, and a copy of the Certificate submitted to the Department.
 
02/27/2019 4076 Minor 4.11 Failure to conduct required periodic containment and interstitial integrity testing. Have the STP sumps and dispenser liners integrity tested immediately and send a copy of the test report to the Department.
 
02/27/2019 4062 SNC-B 4.6 Electronic release detection devices not inspected monthly. Send copies of all (any) electronic monitoring records (Veeder Root tapes) from Nov & Dec 2016, all of 2017, Nov & Dec 2018, and Jan 2019 to the Department, if available. Send copies of the next two months electronic monitoring records to the Department.
 
02/27/2019 4076 Minor 4.11 Failure to conduct required periodic containment and interstitial integrity testing. Have the double-walled spill containment buckets integrity tested immediately and send a copy of the test report to the Department.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
08/25/2011   INACTIVE 9