Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||
Cover Page Report | |||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||
District | Southwest | Type | Collection Station | ||||
County | Pinellas | Status | OPEN | ||||
ID | 8624557 | Latitude | 27° 45' 41.2799 | ||||
Name |
HOWCO ENVIRONMENTAL SRVCS 843 43RD ST S |
Longitude | 82° 41' 32.1791 | ||||
SAINT PETERSBURG, FL 33711-1922 | LL Method | DPHO | |||||
Contact | LEE MORRIS | LL Status | REVIEWED | ||||
Phone | (727) 327-8467 | Status Date | 09/12/2003 | ||||
Account Owner Information | |||||||
Name | HOWCO ENVIRONMENTAL SERVICES INC 3701 CENTRAL AVE SAINT PETERSBURG, FL 33713-1922 |
Effective Date | 05/20/1994 | ||||
Contact | TIM HAGAN | ||||||
Phone | (727) 327-8467 | ||||||
RDILLEN@HOWCOUSA.COM | |||||||
Placard # / Date | 700280 - 07/29/2024 | ||||||
No Property Owner Information Found | |||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
105 | 3798 | Misc Petrol-Based Product (X) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment (M) Spill containment bucket |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
106 | 6950 | Misc Petrol-Based Product (X) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment (M) Spill containment bucket |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
120R1 | 20000 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
121 | 27989 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (S) DEP approved containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (M) Manual tank gauging - USTs (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
122 | 27989 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (S) DEP approved containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (M) Manual tank gauging - USTs (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
123 | 27989 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (S) DEP approved containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (M) Manual tank gauging - USTs (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
124 | 27989 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (S) DEP approved containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (M) Manual tank gauging - USTs (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
125 | 18040 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (S) DEP approved containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (M) Manual tank gauging - USTs (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
126 | 18565 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (S) DEP approved containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (M) Manual tank gauging - USTs (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
127 | 18565 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (S) DEP approved containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (M) Manual tank gauging - USTs (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
128R1 | 19470 | Waste Oil (L) | ABOVEGROUND | In Service (U) | |||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
129 | 21775 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (S) DEP approved containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (M) Manual tank gauging - USTs (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
130 | 7950 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
131 | 3950 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
132 | 3950 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
133 | 3950 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
134 | 3950 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
135 | 6000 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
136 | 10000 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
137 | 10570 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
151 | 15000 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
152 | 28130 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
153 | 20531 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
154 | 18172 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
155 | 20139 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
160 | 14792 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
161 | 14792 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment (M) Spill containment bucket |
(B) Steel/galvanized metal (I) Suction piping system |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
162 | 14792 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (K) AST containment (M) Spill containment bucket |
(B) Steel/galvanized metal (I) Suction piping system |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
163 | 14792 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
164 | 18832 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
165 | 18618 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
170 | 11000 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(A) Abv, no soil contact (C) Fiberglass (K) Dispenser liners |
(6) External piping monitoring (M) Manual tank gauging - USTs (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
180 | 56796 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(B) Steel/galvanized metal (I) Suction piping system |
(Q) Visual inspection of ASTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
181 | 2979 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (I) Suction piping system |
(6) External piping monitoring (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
191 | 7500 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
192 | 15000 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | In Service (U) | ||
Constructions | Pipings | Monitorings | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
100 | 27000 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | NonReg Use / Process (X) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(B) Steel/galvanized metal (I) Suction piping system |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
101 | 28500 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | NonReg Use / Process (X) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(B) Steel/galvanized metal (I) Suction piping system |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
120 | 21775 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (S) DEP approved containment |
(B) Steel/galvanized metal (I) Suction piping system |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
128 | 23792 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (S) DEP approved containment |
(B) Steel/galvanized metal (I) Suction piping system |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
140 | 30000 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | NonReg Use / Process (X) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
141 | 17432 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | NonReg Use / Process (X) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
142 | 17432 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | NonReg Use / Process (X) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
143 | 17013 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | NonReg Use / Process (X) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
144 | 18886 | Waste Oil (L) | 07/01/1980 | ABOVEGROUND | NonReg Use / Process (X) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(C) Fiberglass (K) Dispenser liners (M) Double wall - pipe jacket |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
150 | 15000 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | Out of Service (T) | ||
Constructions | Pipings | Monitorings | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
171 | 9607 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(A) Abv, no soil contact (C) Fiberglass (K) Dispenser liners |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
172 | 9703 | Other Non Regulated (Z) | 07/01/1980 | ABOVEGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(A) Abv, no soil contact (C) Fiberglass (K) Dispenser liners |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
173 | 5500 | Unleaded Gas (B) | 07/01/1980 | ABOVEGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(A) Abv, no soil contact (C) Fiberglass (K) Dispenser liners |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
174 | 2898 | Vehicular Diesel (D) | 07/01/1980 | ABOVEGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (C) Steel (K) AST containment |
(A) Abv, no soil contact (C) Fiberglass (K) Dispenser liners |
(M) Manual tank gauging - USTs | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
193 | 1000 | Vehicular Diesel (D) | 12/01/2007 | ABOVEGROUND | Out of Service (T) | ||
Constructions | Pipings | Monitorings | |||||
(C) Steel (M) Spill containment bucket (R) Double wall - tank jacket |
(A) Abv, no soil contact (B) Steel/galvanized metal |
(F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
3 | 3000 | Vehicular Diesel (D) | 07/01/1987 | ABOVEGROUND | Removed from Site (B) | ||
Constructions | Pipings | Monitorings | |||||
(A) Ball check valve (E) Fiberglass (K) AST containment |
(D) External protective coating | (8) Manually sampled wells (C) Groundwater Monitoring Plan |
|||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
1 | 2000 | Leaded Gas (A) | ABOVEGROUND | Removed from Site (B) | |||
Constructions | Pipings | Monitorings | |||||
(D) Unknown | (C) Fiberglass | (I) Not required | |||||
Tank | Tank Size | Content | Installed | Placement | Status | ||
2 | 4000 | Vehicular Diesel (D) | ABOVEGROUND | Removed from Site (B) | |||
Constructions | Pipings | Monitorings | |||||
(D) Unknown | (C) Fiberglass | (I) Not required | |||||
Insurance Documents | |||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||
INSURANCE | 06/28/2019 | 06/28/2020 | NAUTILUS INSURANCE COMPANY | ||||
INSURANCE | 06/28/2018 | 06/28/2019 | NAUTILUS INSURANCE COMPANY | ||||
INSURANCE | 07/02/2013 | 07/02/2014 | CHARTIS SPECIALTY INSURANCE CO | ||||
INSURANCE | 07/02/2012 | 07/02/2013 | CHARTIS SPECIALTY INSURANCE CO | ||||
INSURANCE | 07/02/2011 | 07/02/2012 | CHARTIS SPECIALTY INSURANCE CO | ||||
INSURANCE | 07/02/2010 | 07/02/2011 | CHARTIS SPECIALTY INSURANCE CO | ||||
INSURANCE | 07/02/2009 | 07/02/2010 | AMERICAN INTERNATIONAL SPECIALTY LINES | ||||
INSURANCE | 07/02/2008 | 07/02/2009 | AMERICAN INTERNATIONAL SPECIALTY LINES | ||||
Legacy Compliance Activity Information | |||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |
NCLI | 01/24/2006 | 02/03/2006 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 01/24/2006 | 02/03/2006 | MINOR OUT-OF-COMPLIANCE | FRAZIER | 21/0 | COMPLIANCE ASSURANCE | |
Completion Notes 105 & 106 TO BE UNREGISTERED. 130, 131, 132, 133, 134, 136, 140 & 141 TO BE RE-REGISTERED | |||||||
SV | 06/13/2005 | 06/14/2005 | BARNETT | 1/0 | COMPLIANCE ASSURANCE | ||
Completion Notes FOLLOWUP TO BER REFERRAL, SUBSEQUENT INFO FROM ST PETE FIRE. | |||||||
SV | 05/24/2005 | 06/14/2005 | BARNETT | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes REFERRAL FROM BER | |||||||
FR | 03/18/2005 | 03/18/2005 | STRAUSS | 0/0 | COMPLIANCE ASSURANCE | ||
Completion Notes CORRECTED 2004 - N HARPER DEP ENTERED CURRENT FR | |||||||
TCI | 01/18/2005 | 01/18/2005 | SIGNIFICANT OUT-OF-COMPLIANCE | BARNETT | 19/0 | COMPLIANCE ASSURANCE | |
NCLI | 01/18/2005 | 01/18/2005 | BARNETT | 0/0 | COMPLIANCE ASSURANCE | ||
NCLI | 05/23/2004 | 05/23/2004 | ROGGELIN | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 04/22/2004 | 05/23/2004 | MINOR OUT-OF-COMPLIANCE | ROGGELIN | 19/0 | COMPLIANCE ASSURANCE | |
Completion Notes WEST TANK FARM - LINER DELAMINATION | |||||||
LTR | 05/29/2003 | 06/02/2003 | STRAUSS | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 05/21/2003 | 06/02/2003 | IN-COMPLIANCE | STRAUSS | 25/0 | COMPLIANCE ASSURANCE | |
RRBD | 03/28/2002 | 04/08/2002 | TAM | 0/0 | COMPLIANCE ASSURANCE | ||
NCLI | 03/08/2002 | 03/18/2002 | TAM | 0/0 | COMPLIANCE ASSURANCE | ||
TCI | 03/07/2002 | 03/18/2002 | MINOR OUT-OF-COMPLIANCE | TAM | 47/0 | COMPLIANCE ASSURANCE | |
RRBD | 07/05/2001 | 07/09/2001 | COMPLIANCE ASSURANCE | ||||
TCI | 04/30/2001 | 05/30/2001 | MINOR OUT-OF-COMPLIANCE | STRAUSS | 24/0 | COMPLIANCE ASSURANCE | |
TCI | 06/02/2000 | 06/06/2000 | MINOR OUT-OF-COMPLIANCE | ROGGELIN/STRAUSS | 19/0 | COMPLIANCE ASSURANCE | |
RRBD | 04/25/2000 | 05/26/2000 | STRAUSS | 0/0 | COMPLIANCE ASSURANCE | ||
TXI | 02/07/2000 | 02/15/2000 | MINOR OUT-OF-COMPLIANCE | SRAUSS | 3/0 | COMPLIANCE ASSURANCE | |
TCI | 06/24/1999 | 06/28/1999 | MINOR OUT-OF-COMPLIANCE | ROGGELIN | 0/0 | COMPLIANCE ASSURANCE | |
ATCI | 03/31/1998 | 04/01/1998 | MINOR OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||
Compliance Activity Information | |||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||
Letter | 07/11/2024 | Satisfied | WIMBERLY_E | Enforcement | |||
Enforcement Referral | 02/27/2023 | Accepted | COLSON_NJ_1 | Enforcement | |||
Electronic Communication | 12/27/2022 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Site Inspection | 10/28/2022 | Major Out of Compliance | COLSON_NJ_1 | 22/0 | Routine Compliance | ||
Letter | 10/28/2022 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Electronic Communication | 09/22/2022 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||
Site Inspection | 03/10/2020 | Major Out of Compliance | COLSON_NJ_1 | 23/0 | Routine Compliance | ||
Letter | 03/10/2020 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Electronic Communication | 02/07/2020 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||
Enforcement Tracking | 08/27/2018 | Closed Without Enforcement | SELLERS_R | Enforcement | |||
Enforcement Referral | 02/28/2018 | Accepted | COLSON_NJ_1 | Enforcement | |||
Electronic Communication | 02/19/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Electronic Communication | 02/19/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||
Site Inspection | 05/31/2017 | Minor Out of Compliance | COLSON_NJ_1 | 23/0 | Routine Compliance | ||
Letter | 05/31/2017 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||
Electronic Communication | 05/11/2017 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||
Site Inspection | 06/19/2014 | In Compliance | STRAUSS_RH_1 | 23/0 | Non-Compliance | ||
Issue Document | 06/19/2014 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Letter | 05/20/2014 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Site Inspection | 05/20/2014 | Minor Out of Compliance | STRAUSS_RH_1 | 23/0 | Routine Compliance | ||
Letter | 05/31/2013 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Site Inspection | 05/31/2013 | Minor Out of Compliance | STRAUSS_RH_1 | 23/0 | Routine Compliance | ||
Site Inspection | 08/01/2011 | In Compliance | STRAUSS_RH_1 | 23/0 | Non-Compliance | ||
Letter | 02/28/2011 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Site Inspection | 02/28/2011 | Minor Out of Compliance | STRAUSS_RH_1 | 23/0 | Routine Compliance | ||
Site Inspection | 06/11/2010 | In Compliance | STRAUSS_RH_1 | 23/0 | Non-Compliance | ||
Issue Document | 06/11/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Record Document | 06/11/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Letter | 04/28/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Site Inspection | 04/28/2010 | Minor Out of Compliance | STRAUSS_RH_1 | 23/0 | Non-Compliance | ||
Record Document | 03/12/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Enforcement Tracking | 02/19/2010 | Closed With Enforcement | MEETZE_A | Enforcement | |||
Letter | 12/29/2009 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Site Inspection | 12/29/2009 | Major Out of Compliance | STRAUSS_RH_1 | 23/0 | Routine Compliance | ||
Issue Document | 10/23/2009 | Satisfied | MEETZE_A | Enforcement | |||
Issue Document | 08/31/2009 | Satisfied | MEETZE_A | Enforcement | |||
Enforcement Referral | 07/02/2009 | Accepted | MEETZE_A | Enforcement | |||
Letter | 04/22/2009 | Satisfied | BARNETT_JX | Non-Compliance | |||
Site Inspection | 04/22/2009 | Major Out of Compliance | BARNETT_JX | 5/0 | Non-Compliance | ||
Letter | 04/07/2009 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Record Document | 04/07/2009 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||
Record Document | 01/28/2009 | Satisfied | BARNETT_JX | Non-Compliance | |||
Site Inspection | 01/08/2009 | Major Out of Compliance | BARNETT_JX | 23/0 | Routine Compliance | ||
Letter | 01/08/2009 | Satisfied | BARNETT_JX | Non-Compliance | |||
Letter | 08/24/2007 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||
Site Inspection | 07/09/2007 | Major Out of Compliance | LONGEN_JL_1 | 20/0 | Routine Compliance | ||
No Open AOCs Found | |||||||
Open Violations | |||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||
10/28/2022 | 7022 | Minor | 3.4 Secondary containment constructed of concrete not in accordance with standards or not impervious. | Recoat the worn areas of concrete containment for the East Tank Farm and Water Plant Area. Provide documentation of State approved coating used and notice of work completion. | |||
03/10/2020 | 5012 | Minor | 1.7 Incomplete documentation demonstrating financial responsibility. | Submit the schedule of covered storage tanks for the current insurance policy. | |||
03/10/2020 | 5002 | Minor | 1.2 Registration Form not submitted for change in service or closure. | Submit an updated registration form to correct the Content of Tank 170 & the Status of Tank 193. | |||
03/10/2020 | 5154 | SNC-B | 5.18 Limited Closure Report not provided within 60 days of closure for shop fabricated storage tank systems. | Fill out & submit the Limited Closure Report Form to this office for review. | |||
03/10/2020 | 5011 | SNC-B | 1.6 Failure to maintain and demonstrate financial responsibility. | Provide documentation of past storage tank pollution liability coverage. | |||
Discharge Information | |||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||
01/10/1997 | INACTIVE | 9 | |||||
01/06/1996 | COMPLETED | 9 | |||||
06/23/1993 | INACTIVE | 9 | |||||
06/25/1992 | COMPLETED | 9 | |||||
10/14/1991 | INACTIVE | 9 | |||||
10/14/1991 | INACTIVE | 9 | |||||