Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Southwest | Type | Fuel user/Non-retail | ||||||||
County | Pinellas | Status | OPEN | ||||||||
ID | 8624687 | Latitude | 27° 47' 9.4096 | ||||||||
Name |
TIMES DISTRIBUTION CENTER 1301 34TH ST N |
Longitude | 82° 40' 37.1932 | ||||||||
SAINT PETERSBURG, FL 33713-5405 | LL Method | DPHO | |||||||||
Contact | TIM THOMAS | LL Status | REVIEWED | ||||||||
Phone | (443) 829-2013 | Status Date | 10/22/2003 | ||||||||
Account Owner Information | |||||||||||
Name | TLH TAMPA BAY LLC 4010 W BOY SCOUT BLVD, SU#275 TAMPA, FL 33607 |
Effective Date | 09/23/2021 | ||||||||
Contact | CARYN CARREIRO | ||||||||||
Phone | (904) 612-1961 | ||||||||||
CARYN.CARREIRO@CUSHWAKE.COM | |||||||||||
Placard # / Date | 672662 - 05/09/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | TACONIC ASSET TRUST 300 MAIN STREET FLOOR 5 STAMFORD, CO 6901-3032 |
Effective Date | 01/18/2023 | ||||||||
Contact | TIM THOMAS | ||||||||||
Phone | (443) 829-2013 | ||||||||||
TTHOMAS@TWENTYLAKE.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
10 | 1200 | Emerg Generator Diesel (G) | 03/01/2007 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket (P) Level gauges/alarms |
(A) Abv, no soil contact (I) Suction piping system |
(F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 550 | Emerg Generator Diesel (G) | 06/01/1968 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (A) Abv, no soil contact (B) Steel/galvanized metal (I) Suction piping system |
(I) Not required (M) Manual tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 5000 | Misc Petrol-Based Product (X) | 07/01/1959 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (Y) Unknown | (X) None | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 5000 | Misc Petrol-Based Product (X) | 07/01/1959 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (Y) Unknown | (X) None | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 2000 | Fuel Oil - Onsite Heat (M) | 07/01/1959 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (Y) Unknown | (I) Not required | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 10000 | Vehicular Diesel (D) | 06/01/1975 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel | (B) Steel/galvanized metal (I) Suction piping system |
(8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
6 | 10000 | Unleaded Gas (B) | 06/01/1977 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (M) Spill containment bucket |
(B) Steel/galvanized metal (I) Suction piping system |
(8) Manually sampled wells | |||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
7 | 10000 | Unleaded Gas (B) | 01/01/1992 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
8 | 10000 | Vehicular Diesel (D) | 01/01/1992 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
9 | 10000 | Vehicular Diesel (D) | 01/01/1992 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector (K) Monitor dbl wall pipe space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 11/01/2019 | 11/01/2020 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 11/01/2018 | 11/01/2019 | COMMERCE & INDUSTRY INSURANCE CO | ||||||||
INSURANCE | 11/01/2017 | 11/01/2018 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 11/01/2016 | 11/01/2017 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 11/01/2015 | 11/01/2016 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 11/01/2014 | 11/01/2015 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 11/01/2013 | 11/01/2014 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 11/01/2012 | 11/01/2013 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 11/01/2012 | 11/01/2013 | COMMERCE & INDUSTRY | ||||||||
INSURANCE | 11/01/2010 | 11/01/2011 | COMMERCE & INDUSTRY | ||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 11/06/2009 | 04/30/2010 | |||||||||
INSURANCE | 11/01/2009 | 11/01/2010 | COMMERCE & INDUSTRY | ||||||||
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER | 02/13/2008 | 02/13/2009 | |||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
RRBD | 12/12/2005 | 01/30/2006 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 12/09/2005 | 12/22/2005 | MINOR OUT-OF-COMPLIANCE | FRAZIER | 0/3 | COMPLIANCE ASSURANCE | |||||
NCLI | 12/09/2005 | 12/22/2005 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||||||
LTR | 07/14/2005 | 07/18/2005 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||||||
TIN | 07/13/2005 | 07/18/2005 | IN-COMPLIANCE | FRAZIER | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes INSTALL OF 3 OPW FRP STP SUMPS | |||||||||||
LTR | 06/20/2005 | 06/20/2005 | FRAZIER | 0/0 | COMPLIANCE ASSURANCE | ||||||
TXI | 06/06/2005 | 06/20/2005 | IN-COMPLIANCE | FRAZIER | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes REMOVAL OF 3 STP SUMPS BY NORRIS & SAMON PCC046053 | |||||||||||
LTR | 12/17/2004 | 12/28/2004 | BARNETT | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 12/07/2004 | 12/28/2004 | IN-COMPLIANCE | BARNETT | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 03/16/2004 | 03/22/2004 | IN-COMPLIANCE | PINK | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes AMERON DW FRP PIPE | |||||||||||
LTR | 10/11/2002 | 10/29/2002 | STRAUSS | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 10/08/2002 | 10/29/2002 | IN-COMPLIANCE | STRAUSS | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 11/15/2001 | 11/29/2001 | MINOR OUT-OF-COMPLIANCE | TAM | 1/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 11/02/2001 | 12/19/2001 | COMPLIANCE ASSURANCE | ||||||||
RRBD | 02/05/2001 | 02/05/2001 | COMPLIANCE ASSURANCE | ||||||||
TCI | 10/13/2000 | 10/17/2000 | MINOR OUT-OF-COMPLIANCE | CASTOR | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 01/26/2000 | 02/03/2000 | IN-COMPLIANCE | CASTOR | 0/3 | COMPLIANCE ASSURANCE | |||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 04/26/2024 | Major Out of Compliance | PUHR_NM_1 | 1/0 | Routine Compliance | ||||||
Letter | 04/26/2024 | Satisfied | PUHR_NM_1 | Compliance Assistance | |||||||
Site Inspection | 01/09/2023 | Major Out of Compliance | COLSON_NJ_1 | 0/3 | Closure | ||||||
Letter | 01/09/2023 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Letter | 07/19/2022 | Satisfied | GREEN_SM | Enforcement | |||||||
Enforcement Referral | 06/28/2022 | Accepted | COLSON_NJ_1 | Enforcement | |||||||
Electronic Communication | 06/08/2022 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Site Inspection | 05/17/2022 | Major Out of Compliance | COLSON_NJ_1 | 1/3 | Routine Compliance | ||||||
Letter | 05/17/2022 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Electronic Communication | 03/30/2022 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Record Document | 09/24/2020 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Letter | 09/24/2020 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Site Inspection | 01/30/2020 | Major Out of Compliance | COLSON_NJ_1 | 1/3 | Routine Compliance | ||||||
Letter | 01/30/2020 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Phone Conversation | 01/24/2020 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Letter | 05/02/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Record Document | 05/02/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Letter | 02/02/2018 | Satisfied | COLSON_NJ_1 | Compliance Assistance | |||||||
Site Inspection | 02/01/2018 | Major Out of Compliance | COLSON_NJ_1 | 1/3 | Routine Compliance | ||||||
Electronic Communication | 01/02/2018 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Letter | 10/02/2015 | Satisfied | COLSON_NJ_1 | Non-Compliance | |||||||
Site Inspection | 10/02/2015 | Minor Out of Compliance | COLSON_NJ_1 | 1/3 | Routine Compliance | ||||||
Phone Conversation | 09/04/2015 | Satisfied | COLSON_NJ_1 | Routine Compliance | |||||||
Site Inspection | 08/28/2013 | In Compliance | STRAUSS_RH_1 | 1/3 | Routine Compliance | ||||||
Letter | 02/19/2013 | Satisfied | ROGGELIN_EM_1 | Closure | |||||||
Document Management | 02/19/2013 | Complete | ROGGELIN_EM_1 | Incident | |||||||
TCAR | 02/19/2013 | Satisfied | ROGGELIN_EM_1 | Closure | |||||||
Document Management | 02/19/2013 | Complete | ROGGELIN_EM_1 | Closure | |||||||
Incident | 02/19/2013 | Has not led to Discharge | ROGGELIN_EM_1 | Incident | |||||||
Issue Document | 02/19/2013 | Satisfied | ROGGELIN_EM_1 | Non-Compliance | |||||||
Record Document | 01/25/2013 | Satisfied | ROGGELIN_EM_1 | Non-Compliance | |||||||
Electronic Communication | 01/24/2013 | Satisfied | ROGGELIN_EM_1 | Non-Compliance | |||||||
Site Inspection | 01/23/2013 | In Compliance | ROGGELIN_EM_1 | 0/3 | Installation | ||||||
Site Inspection | 01/08/2013 | In Compliance | ROGGELIN_EM_1 | 0/3 | Closure | ||||||
Record Document | 09/15/2011 | Satisfied | STRAUSS_RH_1 | Routine Compliance | |||||||
Site Inspection | 09/07/2011 | In Compliance | STRAUSS_RH_1 | 1/3 | Routine Compliance | ||||||
Record Document | 09/10/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Site Inspection | 09/07/2010 | Major Out of Compliance | STRAUSS_RH_1 | 1/3 | Routine Compliance | ||||||
Letter | 09/07/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Issue Document | 02/02/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Record Document | 02/02/2010 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Letter | 10/19/2009 | Satisfied | STRAUSS_RH_1 | Non-Compliance | |||||||
Site Inspection | 10/19/2009 | Major Out of Compliance | STRAUSS_RH_1 | 1/3 | Routine Compliance | ||||||
Site Inspection | 10/30/2008 | In Compliance | BARNETT_JX | 1/3 | Routine Compliance | ||||||
Record Document | 04/01/2008 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Letter | 03/10/2008 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 03/10/2008 | Minor Out of Compliance | LONGEN_JL_1 | 0/1 | Non-Compliance | ||||||
Site Inspection | 03/04/2008 | Minor Out of Compliance | LONGEN_JL_1 | 1/3 | Routine Compliance | ||||||
Letter | 03/04/2008 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 07/03/2007 | In Compliance | ROGGELIN_EM_1 | 1/0 | Installation | ||||||
Letter | 05/23/2007 | Satisfied | LONGEN_JL_1 | Non-Compliance | |||||||
Site Inspection | 05/02/2007 | Minor Out of Compliance | LONGEN_JL_1 | 0/3 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
04/26/2024 | 7097 | Minor | 3.9 Requirements not met for out of service systems including registering system out-of-service and securing out-of-service system. | Facility owners and operators of out-of-service storage tank systems shall register storage tank systems as out-of-service in accordance with Rule 62-762.401, F.A.C. The tank appears to have been abandoned for a while and needs to be properly closed. | |||||||
04/26/2024 | 7101 | SNC-B | 3.12 Storage tank system not closed within 90 days in accordance with this subsection. | The tank appears abandoned and in disrepair and needs to be closed. Closure of storage tank systems shall be performed by: 1. Removing all liquids and accumulated sludges. The removal and disposal of all liquids and accumulated sludges may be required according to other federal, state, and local requirements, (provide a waste manifest for the cleaning of the AST). 2. Removing or disconnecting and capping all integral piping, 3. Removing and disposing of the storage tank (provide a tank scrap ticket) 4. Submit a Limited Closure Report Form for ASTs 5. Update registration (register tank as closed) An inspector will need to be onsite and provided notification for steps 1-3. Provide notification to this office 30-45 days prior to the date of closure and 48-72 hours prior to onsite activities. | |||||||
04/24/2024 | 7001 | Minor | 1.1 No reasonable access provided. | *Designate a representative to provide access to this facility for potential reinspection.* | |||||||
04/24/2024 | 7003 | Minor | 1.3 Registration fees not paid (not receiving fuel). | Registration fees are due from the tank or facility owner or operator, as indicated in this section, for all storage tank systems and compression vessels, required to be registered, except for: Storage tank systems and compression vessels that have been properly closed in accordance with subsections 62-762.801(2) and 62-762.802(3), F.A.C. | |||||||
01/09/2023 | 6084 | SNC-B | 4.15 Closure assessment not performed or properly completed. | Submit a Limited Closure Report Form, following the completion of UST System Closure activities in September 2022. | |||||||
01/09/2023 | 6003 | Minor | 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Submit an updated Storage Tank Registration Form with the appropriate changes to the Status of Tanks 7, 8, & 9. Update the Contact information as necessary. | |||||||
01/09/2023 | 6004 | Minor | 2.3 For Installation or Closure, Certified Contractors Form not submitted. | Submit a Certified Contractors Form, following the completion of UST System Closure activities in September 2022. | |||||||
05/05/2022 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Properly perform & document release detection inspections every month & no more than 35 days apart. Maintain records on file for at least 36 months. | |||||||
05/05/2022 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Be sure to have the rupture basin alarm system for the AST tested within 12 months of the last test date. Maintain records on file for at least 36 months. | |||||||
05/05/2022 | 7095 | Minor | 1.14 Records requiring 3 year documentation period not kept by facility. | Maintain a manual Alarm History log to record the occurrence of any fuel tank alarms & the corresponding resolution activities. | |||||||
05/05/2022 | 7001 | Minor | 1.1 No reasonable access provided. | Provide access to the AST spill bucket and the rupture basin alarm panel(s). | |||||||
05/05/2022 | 6012 | SNC-A | 2.9 No financial responsibility instrument or expired instrument for > 180 days. | Provide documentation of Financial Responsibility for the (3) USTs and (1) AST from 11/01/2020 to current. | |||||||
05/05/2022 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Be sure to have the primary overfill protection device on the AST system tested within 12 months of the last test date. Maintain records on file for at least 36 months. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
03/02/1992 | COMPLETED | 11 | PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE | ||||||||