DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Southwest   Type    Fuel user/Non-retail
 
County Pinellas   Status    OPEN
 
ID 8624687   Latitude    27° 47' 9.4096
 
Name TIMES DISTRIBUTION CENTER
1301 34TH ST N
Longitude    82° 40' 37.1932
  SAINT PETERSBURG, FL 33713-5405 LL Method    DPHO
 
Contact TIM THOMAS   LL Status    REVIEWED
 
Phone (443) 829-2013   Status Date    10/22/2003
 
Account Owner Information
 
Name TLH TAMPA BAY LLC
4010 W BOY SCOUT BLVD, SU#275
TAMPA, FL 33607
Effective Date    09/23/2021
 
Contact CARYN CARREIRO
 
Phone (904) 612-1961
 
Email CARYN.CARREIRO@CUSHWAKE.COM
  Placard # / Date    672662 - 05/09/2024
Property Owner Information
 
Name TACONIC ASSET TRUST
300 MAIN STREET FLOOR 5
STAMFORD, CO 6901-3032
Effective Date    01/18/2023
 
Contact TIM THOMAS
 
Phone (443) 829-2013
 
Email TTHOMAS@TWENTYLAKE.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
10 1200 Emerg Generator Diesel (G) 03/01/2007 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(I) Suction piping system
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Tank Tank Size Content Installed Placement Status
1 550 Emerg Generator Diesel (G) 06/01/1968 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (A) Abv, no soil contact
(B) Steel/galvanized metal
(I) Suction piping system
(I) Not required
(M) Manual tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
2 5000 Misc Petrol-Based Product (X) 07/01/1959 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (Y) Unknown (X) None
 
 
Tank Tank Size Content Installed Placement Status
3 5000 Misc Petrol-Based Product (X) 07/01/1959 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (Y) Unknown (X) None
 
 
Tank Tank Size Content Installed Placement Status
4 2000 Fuel Oil - Onsite Heat (M) 07/01/1959 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (Y) Unknown (I) Not required
 
 
Tank Tank Size Content Installed Placement Status
5 10000 Vehicular Diesel (D) 06/01/1975 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal
(I) Suction piping system
(8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
6 10000 Unleaded Gas (B) 06/01/1977 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(M) Spill containment bucket
  (B) Steel/galvanized metal
(I) Suction piping system
(8) Manually sampled wells
 
 
Tank Tank Size Content Installed Placement Status
7 10000 Unleaded Gas (B) 01/01/1992 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
8 10000 Vehicular Diesel (D) 01/01/1992 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Tank Tank Size Content Installed Placement Status
9 10000 Vehicular Diesel (D) 01/01/1992 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(E) Fiberglass
(I) Double wall
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(3) Electronic monitor pipe sumps
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(H) Mechanical line leak detector
(K) Monitor dbl wall pipe space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   11/01/2019 11/01/2020 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   11/01/2018 11/01/2019 COMMERCE & INDUSTRY INSURANCE CO
INSURANCE   11/01/2017 11/01/2018 COMMERCE & INDUSTRY
INSURANCE   11/01/2016 11/01/2017 COMMERCE & INDUSTRY
INSURANCE   11/01/2015 11/01/2016 COMMERCE & INDUSTRY
INSURANCE   11/01/2014 11/01/2015 COMMERCE & INDUSTRY
INSURANCE   11/01/2013 11/01/2014 COMMERCE & INDUSTRY
INSURANCE   11/01/2012 11/01/2013 COMMERCE & INDUSTRY
INSURANCE   11/01/2012 11/01/2013 COMMERCE & INDUSTRY
INSURANCE   11/01/2010 11/01/2011 COMMERCE & INDUSTRY
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   11/06/2009 04/30/2010
INSURANCE   11/01/2009 11/01/2010 COMMERCE & INDUSTRY
SELF-INSURANCE - LETTER FROM CHIEF FINANCIAL OFFICER   02/13/2008 02/13/2009
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
RRBD 12/12/2005 01/30/2006 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
TCI 12/09/2005 12/22/2005 MINOR OUT-OF-COMPLIANCE FRAZIER 0/3 COMPLIANCE ASSURANCE
 
NCLI 12/09/2005 12/22/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
LTR 07/14/2005 07/18/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
TIN 07/13/2005 07/18/2005 IN-COMPLIANCE FRAZIER 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes INSTALL OF 3 OPW FRP STP SUMPS
 
LTR 06/20/2005 06/20/2005 FRAZIER 0/0 COMPLIANCE ASSURANCE
 
TXI 06/06/2005 06/20/2005 IN-COMPLIANCE FRAZIER 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes REMOVAL OF 3 STP SUMPS BY NORRIS & SAMON PCC046053
 
LTR 12/17/2004 12/28/2004 BARNETT 0/0 COMPLIANCE ASSURANCE
 
TCI 12/07/2004 12/28/2004 IN-COMPLIANCE BARNETT 0/3 COMPLIANCE ASSURANCE
 
TCI 03/16/2004 03/22/2004 IN-COMPLIANCE PINK 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes AMERON DW FRP PIPE
 
LTR 10/11/2002 10/29/2002 STRAUSS 0/0 COMPLIANCE ASSURANCE
 
TCI 10/08/2002 10/29/2002 IN-COMPLIANCE STRAUSS 0/3 COMPLIANCE ASSURANCE
 
TCI 11/15/2001 11/29/2001 MINOR OUT-OF-COMPLIANCE TAM 1/3 COMPLIANCE ASSURANCE
 
RRBD 11/02/2001 12/19/2001 COMPLIANCE ASSURANCE
 
RRBD 02/05/2001 02/05/2001 COMPLIANCE ASSURANCE
 
TCI 10/13/2000 10/17/2000 MINOR OUT-OF-COMPLIANCE CASTOR 0/3 COMPLIANCE ASSURANCE
 
TCI 01/26/2000 02/03/2000 IN-COMPLIANCE CASTOR 0/3 COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 04/26/2024 Major Out of Compliance PUHR_NM_1 1/0 Routine Compliance
 
Letter 04/26/2024 Satisfied PUHR_NM_1 Compliance Assistance
 
Site Inspection 01/09/2023 Major Out of Compliance COLSON_NJ_1 0/3 Closure
 
Letter 01/09/2023 Satisfied COLSON_NJ_1 Compliance Assistance
 
Letter 07/19/2022 Satisfied GREEN_SM Enforcement
 
Enforcement Referral 06/28/2022 Accepted COLSON_NJ_1 Enforcement
 
Electronic Communication 06/08/2022 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 05/17/2022 Major Out of Compliance COLSON_NJ_1 1/3 Routine Compliance
 
Letter 05/17/2022 Satisfied COLSON_NJ_1 Non-Compliance
 
Electronic Communication 03/30/2022 Satisfied COLSON_NJ_1 Routine Compliance
 
Record Document 09/24/2020 Satisfied COLSON_NJ_1 Compliance Assistance
 
Letter 09/24/2020 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 01/30/2020 Major Out of Compliance COLSON_NJ_1 1/3 Routine Compliance
 
Letter 01/30/2020 Satisfied COLSON_NJ_1 Compliance Assistance
 
Phone Conversation 01/24/2020 Satisfied COLSON_NJ_1 Routine Compliance
 
Letter 05/02/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Record Document 05/02/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Letter 02/02/2018 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 02/01/2018 Major Out of Compliance COLSON_NJ_1 1/3 Routine Compliance
 
Electronic Communication 01/02/2018 Satisfied COLSON_NJ_1 Routine Compliance
 
Letter 10/02/2015 Satisfied COLSON_NJ_1 Non-Compliance
 
Site Inspection 10/02/2015 Minor Out of Compliance COLSON_NJ_1 1/3 Routine Compliance
 
Phone Conversation 09/04/2015 Satisfied COLSON_NJ_1 Routine Compliance
 
Site Inspection 08/28/2013 In Compliance STRAUSS_RH_1 1/3 Routine Compliance
 
Letter 02/19/2013 Satisfied ROGGELIN_EM_1 Closure
 
Document Management 02/19/2013 Complete ROGGELIN_EM_1 Incident
 
TCAR 02/19/2013 Satisfied ROGGELIN_EM_1 Closure
 
Document Management 02/19/2013 Complete ROGGELIN_EM_1 Closure
 
Incident 02/19/2013 Has not led to Discharge ROGGELIN_EM_1 Incident
 
Issue Document 02/19/2013 Satisfied ROGGELIN_EM_1 Non-Compliance
 
Record Document 01/25/2013 Satisfied ROGGELIN_EM_1 Non-Compliance
 
Electronic Communication 01/24/2013 Satisfied ROGGELIN_EM_1 Non-Compliance
 
Site Inspection 01/23/2013 In Compliance ROGGELIN_EM_1 0/3 Installation
 
Site Inspection 01/08/2013 In Compliance ROGGELIN_EM_1 0/3 Closure
 
Record Document 09/15/2011 Satisfied STRAUSS_RH_1 Routine Compliance
 
Site Inspection 09/07/2011 In Compliance STRAUSS_RH_1 1/3 Routine Compliance
 
Record Document 09/10/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 09/07/2010 Major Out of Compliance STRAUSS_RH_1 1/3 Routine Compliance
 
Letter 09/07/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Issue Document 02/02/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Record Document 02/02/2010 Satisfied STRAUSS_RH_1 Non-Compliance
 
Letter 10/19/2009 Satisfied STRAUSS_RH_1 Non-Compliance
 
Site Inspection 10/19/2009 Major Out of Compliance STRAUSS_RH_1 1/3 Routine Compliance
 
Site Inspection 10/30/2008 In Compliance BARNETT_JX 1/3 Routine Compliance
 
Record Document 04/01/2008 Satisfied LONGEN_JL_1 Non-Compliance
 
Letter 03/10/2008 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 03/10/2008 Minor Out of Compliance LONGEN_JL_1 0/1 Non-Compliance
 
Site Inspection 03/04/2008 Minor Out of Compliance LONGEN_JL_1 1/3 Routine Compliance
 
Letter 03/04/2008 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 07/03/2007 In Compliance ROGGELIN_EM_1 1/0 Installation
 
Letter 05/23/2007 Satisfied LONGEN_JL_1 Non-Compliance
 
Site Inspection 05/02/2007 Minor Out of Compliance LONGEN_JL_1 0/3 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
04/26/2024 7097 Minor 3.9 Requirements not met for out of service systems including registering system out-of-service and securing out-of-service system. Facility owners and operators of out-of-service storage tank systems shall register storage tank systems as out-of-service in accordance with Rule 62-762.401, F.A.C. The tank appears to have been abandoned for a while and needs to be properly closed.
 
04/26/2024 7101 SNC-B 3.12 Storage tank system not closed within 90 days in accordance with this subsection. The tank appears abandoned and in disrepair and needs to be closed. Closure of storage tank systems shall be performed by: 1. Removing all liquids and accumulated sludges. The removal and disposal of all liquids and accumulated sludges may be required according to other federal, state, and local requirements, (provide a waste manifest for the cleaning of the AST). 2. Removing or disconnecting and capping all integral piping, 3. Removing and disposing of the storage tank (provide a tank scrap ticket) 4. Submit a Limited Closure Report Form for ASTs 5. Update registration (register tank as closed) An inspector will need to be onsite and provided notification for steps 1-3. Provide notification to this office 30-45 days prior to the date of closure and 48-72 hours prior to onsite activities.
 
04/24/2024 7001 Minor 1.1 No reasonable access provided. *Designate a representative to provide access to this facility for potential reinspection.*
 
04/24/2024 7003 Minor 1.3 Registration fees not paid (not receiving fuel). Registration fees are due from the tank or facility owner or operator, as indicated in this section, for all storage tank systems and compression vessels, required to be registered, except for: Storage tank systems and compression vessels that have been properly closed in accordance with subsections 62-762.801(2) and 62-762.802(3), F.A.C.
 
01/09/2023 6084 SNC-B 4.15 Closure assessment not performed or properly completed. Submit a Limited Closure Report Form, following the completion of UST System Closure activities in September 2022.
 
01/09/2023 6003 Minor 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Submit an updated Storage Tank Registration Form with the appropriate changes to the Status of Tanks 7, 8, & 9. Update the Contact information as necessary.
 
01/09/2023 6004 Minor 2.3 For Installation or Closure, Certified Contractors Form not submitted. Submit a Certified Contractors Form, following the completion of UST System Closure activities in September 2022.
 
05/05/2022 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. Properly perform & document release detection inspections every month & no more than 35 days apart. Maintain records on file for at least 36 months.
 
05/05/2022 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Be sure to have the rupture basin alarm system for the AST tested within 12 months of the last test date. Maintain records on file for at least 36 months.
 
05/05/2022 7095 Minor 1.14 Records requiring 3 year documentation period not kept by facility. Maintain a manual Alarm History log to record the occurrence of any fuel tank alarms & the corresponding resolution activities.
 
05/05/2022 7001 Minor 1.1 No reasonable access provided. Provide access to the AST spill bucket and the rupture basin alarm panel(s).
 
05/05/2022 6012 SNC-A 2.9 No financial responsibility instrument or expired instrument for > 180 days. Provide documentation of Financial Responsibility for the (3) USTs and (1) AST from 11/01/2020 to current.
 
05/05/2022 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Be sure to have the primary overfill protection device on the AST system tested within 12 months of the last test date. Maintain records on file for at least 36 months.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
03/02/1992   COMPLETED 11 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE