DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 02/02/2025        Last Data Refresh: 02/01/2025        Report Generated from DOPPLER
 
District Northwest   Type    Retail Station
 
County Bay   Status    OPEN
 
ID 8626356   Latitude    30° 10' 34.7971
 
Name TEXACO FOOD STORE #4500
1512 HARRISON DR
Longitude    85° 39' 35.2854
  PANAMA CITY, FL 32402 LL Method    DPHO
 
Contact PAUL BAISCH   LL Status    REVIEWED
 
Phone (770) 778-2620   Status Date    06/15/2023
 
Account Owner Information
 
Name PANHANDLE COMMERCIAL PROPERTIES LLC
PO BOX 1565
Lawrenceville, GA 30046
Effective Date    07/25/2003
 
Contact SCOTT MOON / JUAN VALENCIA
 
Phone (679) 994-0632
 
Email SCOTT@MAJORSMGMT.COM
  Placard # / Date    681619 - 06/05/2024
Property Owner Information
 
Name PANHANDLE COMMERCIAL PROPERTIES LLC
PO BOX 1565
Lawrenceville, GA 30046
Effective Date    07/25/2003
 
Contact SCOTT MOON / JUAN VALENCIA
 
Phone (679) 994-0632
 
Email SCOTT@MAJORSMGMT.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
4 20000 Unleaded Gas (B) 06/01/2009 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
5 10000 Vehicular Diesel (D) 06/01/2009 UNDERGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(L) Compartmented
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
(P) Level gauges/alarms
(R) Double wall - tank jacket
  (C) Fiberglass
(F) Double wall
(J) Pressurized piping system
(K) Dispenser liners
(4) Visual inspect dispenser liners
(F) Monitor dbl wall tank space
(L) Automatic tank gauging - USTs
 
 
Tank Tank Size Content Installed Placement Status
1 8021 Unleaded Gas (B) 05/01/1990 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (B) Steel/galvanized metal
(C) Fiberglass
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
2 8021 Unleaded Gas (B) 05/01/1990 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (B) Steel/galvanized metal
(C) Fiberglass
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Tank Tank Size Content Installed Placement Status
3 8000 Unleaded Gas (B) 05/01/1990 UNDERGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(A) Ball check valve
(C) Steel
(G) Sacrificial anode CP
(M) Spill containment bucket
(N) Flow shut-Off
(O) Tight fill
  (B) Steel/galvanized metal
(C) Fiberglass
(E) Cathodic protection
(J) Pressurized piping system
(K) Dispenser liners
(2) Visual inspect pipe sumps
(4) Visual inspect dispenser liners
(H) Mechanical line leak detector
(S) Statistical Inventory Reconcile
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   12/31/2023 12/31/2024 TOKIO MARINE SPECIALTY INSURANCE COMPANY
INSURANCE   12/31/2021 12/31/2022 TOKIO MARINE SPECIALTY INSURANCE COMPANY
INSURANCE   12/31/2020 12/31/2021 TOKIO MARINE SPECIALTY INSURANCE COMPANY
INSURANCE   12/31/2017 12/31/2018 TOKIO MARINE SPECIALTY INSURANCE COMPANY
INSURANCE   12/31/2017 12/31/2018 TORUS SPECIALTY INSURANCE CO
INSURANCE   12/31/2015 12/31/2016 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   12/31/2012 12/31/2013 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   12/31/2012 12/31/2013 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   04/15/2011 04/15/2012 LIBERTY SURPLUS INSURANCE CORP
INSURANCE   04/15/2010 04/15/2011 ZURICH-AMERICAN
INSURANCE   04/15/2009 04/15/2010 ZURICH-AMERICAN
INSURANCE   04/23/1994 04/23/1995 PLUS
INSURANCE   04/23/1993 04/23/1994 FPLIPA
 
 
Legacy Compliance Activity Information
 
Activity
Code
Date
Initiated
Date
Completed
Results Inspector AST/UST
Count
Description
RRBD 01/27/2006 01/30/2006 COMPLIANCE ASSURANCE
 
RRBD 11/07/2005 11/07/2005 COMPLIANCE ASSURANCE
 
TCI 08/30/2005 09/02/2005 MINOR OUT-OF-COMPLIANCE KHAN 0/3 COMPLIANCE ASSURANCE
 
RRBD 11/02/2004 11/08/2004 PINKOVSKY 0/0 COMPLIANCE ASSURANCE
 
TCI 08/31/2004 09/01/2004 MINOR OUT-OF-COMPLIANCE KHAN 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes PIPING: UNKNOWN FIBERGLASS & STEEL
 
TIN 01/13/2004 01/28/2004 IN-COMPLIANCE PINKOVSKY 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes PIPING: UNKNOWN FIBERGLASS & STEEL
 
RRBD 12/08/2003 12/08/2003 PINKOVSKY 0/0 COMPLIANCE ASSURANCE
 
RRBD 09/15/2003 09/15/2003 COMPLIANCE ASSURANCE
 
TCI 08/26/2003 08/28/2003 SIGNIFICANT OUT-OF-COMPLIANCE KHAN 0/3 COMPLIANCE ASSURANCE
 
 Completion Notes PIPING: UNKNOWN FIBERGLASS
 
CRDE 11/18/2002 11/18/2002 PINKOVSKY 0/0 COMPLIANCE ASSURANCE
 
 Completion Notes PER NWD REQUEST, COMPANY BANKRUPTCY
 
TCI 10/17/2002 10/21/2002 SIGNIFICANT OUT-OF-COMPLIANCE KHAN 0/3 COMPLIANCE ASSURANCE
 
TCI 10/17/2001 10/19/2001 IN-COMPLIANCE PINKOVSKY 0/3 COMPLIANCE ASSURANCE
 
TCI 10/17/2000 10/19/2000 IN-COMPLIANCE BRADLEY 0/3 COMPLIANCE ASSURANCE
 
TCI 10/19/1999 10/20/1999 IN-COMPLIANCE PINKOVSKY 0/3 COMPLIANCE ASSURANCE
 
LTR 01/29/1999 03/08/1999 PINKOVSKY 0/0 COMPLIANCE ASSURANCE
 
UTCR 01/12/1999 03/08/1999 IN-COMPLIANCE CAMPBELL 0/3 COMPLIANCE ASSURANCE
 
TIN 01/11/1999 03/08/1999 IN-COMPLIANCE CAMPBELL 0/3 COMPLIANCE ASSURANCE
 
UTCI 09/16/1998 09/21/1998 MINOR OUT-OF-COMPLIANCE COMPLIANCE ASSURANCE
 
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 12/18/2024 Major Out of Compliance GARTIN_D 0/2 Routine Compliance
 
Letter 12/18/2024 Satisfied GARTIN_D Compliance Assistance
 
Meeting 12/13/2024 Satisfied GARTIN_D Routine Compliance
 
Electronic Communication 12/13/2024 Satisfied GARTIN_D Routine Compliance
 
Electronic Communication 10/06/2023 Satisfied MATHERLY_H Enforcement
 
Enforcement Tracking 10/06/2023 Closed Without Enforcement GILLMAN_M Enforcement
 
Letter 04/04/2023 Satisfied MATHERLY_H Enforcement
 
Enforcement Referral 03/22/2023 Accepted KHAN_MR_1 Enforcement
 
Record Document 03/16/2023 Satisfied KHAN_MR_1 Compliance Assistance
 
Letter 12/22/2022 Satisfied WILSON_ML_1 Compliance Assistance
 
Phone Conversation 12/21/2022 Satisfied KHAN_MR_1 Routine Compliance
 
Site Inspection 12/21/2022 Major Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Letter 05/03/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Issue Document 05/03/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Record Document 04/29/2021 Satisfied KHAN_MR_1 Compliance Assistance
 
Letter 02/01/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Issue Document 02/01/2021 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 01/29/2021 Major Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Phone Conversation 01/14/2021 Satisfied KHAN_MR_1 Routine Compliance
 
Record Document 07/25/2019 Satisfied WILSON_ML_1 Closure
 
Record Document 07/25/2019 Satisfied WILSON_ML_1 Installation
 
Letter 05/09/2019 Satisfied WILSON_ML_1 Closure
 
Issue Document 05/09/2019 Satisfied WILSON_ML_1 Closure
 
TCAR 05/09/2019 Satisfied PAYNE_CL_1 Closure
 
Document Management 05/08/2019 Satisfied WILSON_ML_1 Closure
 
Record Document 01/08/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Letter 01/08/2019 Satisfied WILSON_ML_1 Compliance Assistance
 
Complaint 11/16/2018 Satisfied KHAN_MR_1 Complaint
 
Record Document 10/30/2018 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 10/23/2018 Minor Out of Compliance BROCK_SN_1 0/2 Complaint
 
Letter 07/24/2018 Satisfied WILSON_ML_1 Compliance Assistance
 
Issue Document 07/24/2018 Satisfied WILSON_ML_1 Compliance Assistance
 
Site Inspection 07/20/2018 Minor Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Phone Conversation 07/19/2018 Satisfied KHAN_MR_1 Routine Compliance
 
Enforcement Tracking 10/25/2016 Closed Without Enforcement MERRITT_S Enforcement
 
Site Inspection 10/25/2016 In Compliance MERRITT_S 0/2 Enforcement
 
Enforcement Referral 08/05/2016 Accepted MERRITT_S Enforcement
 
Letter 03/07/2016 Satisfied WILSON_ML_1 Non-Compliance
 
Record Document 03/01/2016 Satisfied KHAN_MR_1 Non-Compliance
 
Letter 02/03/2016 Satisfied WILSON_ML_1 Non-Compliance
 
Site Inspection 02/01/2016 Major Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Electronic Communication 12/11/2013 Satisfied KHAN_MR_1 Non-Compliance
 
Electronic Communication 12/11/2013 Satisfied KHAN_MR_1 Non-Compliance
 
Site Inspection 10/24/2013 Minor Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Letter 10/24/2013 Satisfied DAURIA_KL_1 Non-Compliance
 
Emergency Preparedness Information 10/24/2013 Satisfied KHAN_MR_1 Routine Compliance
 
Electronic Communication 07/08/2013 Satisfied KHAN_MR_1 Non-Compliance
 
Phone Conversation 07/02/2013 Satisfied KHAN_MR_1 Non-Compliance
 
Phone Conversation 07/02/2013 Satisfied KHAN_MR_1 Non-Compliance
 
Phone Conversation 06/17/2013 Satisfied KHAN_MR_1 Non-Compliance
 
Letter 01/28/2013 Satisfied DAURIA_KL_1 Non-Compliance
 
Site Inspection 01/24/2013 Minor Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Emergency Preparedness Information 01/24/2013 Satisfied KHAN_MR_1 Routine Compliance
 
Site Inspection 01/19/2012 In Compliance KHAN_MR_1 0/2 Routine Compliance
 
Letter 10/08/2010 Satisfied PIERCE_LL_1 Non-Compliance
 
Emergency Preparedness Information 09/24/2010 Satisfied KHAN_MR_1 Routine Compliance
 
Site Inspection 09/23/2010 Minor Out of Compliance KHAN_MR_1 0/2 Routine Compliance
 
Emergency Preparedness Information 09/23/2010 Satisfied KHAN_MR_1 Routine Compliance
 
Emergency Preparedness Information 10/12/2009 Satisfied KHAN_MR_1 Routine Compliance
 
Site Inspection 10/05/2009 In Compliance KHAN_MR_1 0/2 Routine Compliance
 
Site Inspection 06/25/2009 In Compliance BRAZILE_DO_1 0/2 Installation
 
Record Document 05/14/2009 Satisfied BRAZILE_DO_1 Non-Compliance
 
Record Document 05/13/2009 Satisfied KHAN_MR_1 Non-Compliance
 
Letter 05/13/2009 Satisfied BRAZILE_DO_1 Non-Compliance
 
Site Inspection 05/12/2009 Major Out of Compliance BRAZILE_DO_1 0/3 Closure
 
Letter 08/04/2008 Satisfied KHAN_MR_1 Non-Compliance
 
Site Inspection 07/31/2008 Minor Out of Compliance KHAN_MR_1 0/3 Routine Compliance
 
Emergency Preparedness Information 07/30/2008 Satisfied KHAN_MR_1 Routine Compliance
 
Emergency Preparedness Information 07/29/2008 Satisfied KHAN_MR_1 Routine Compliance
 
Emergency Preparedness Information 04/14/2008 Satisfied BRAZILE_DO_1 Routine Compliance
 
Site Inspection 07/12/2007 In Compliance KHAN_MR_1 0/3 Routine Compliance
 
Emergency Preparedness Information 02/07/2007 Satisfied BRAZILE_DO_1 Routine Compliance
 
Emergency Preparedness Information 09/26/2006 Satisfied BRAZILE_DO_1 Routine Compliance
 
Site Inspection 07/17/2006 In Compliance KHAN_MR_1 0/3 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
12/18/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Determine the source of the liquid in the premium double wall spill bucket interstitial space and vacuum test the premium spill bucket to proper PEI standard to confirm the integrity of the double wall spill bucket. Submit associated testing and cause of liquid in the interstitial space to Daniel.Gartin@flhealth.gov.
 
12/18/2024 6003 Minor 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. Have the registration information of tank 4 and tank 5 updated to reflect the proper construction of the tank system. Tank 4 will need to be updated to list ethanol gasoline blend instead of non-ethanol blend. Submit information showing the registration of these tanks was updated to Daniel.Gartin@flhealth.gov.
 
12/18/2024 6053 Minor 4.7 Primary overfill protection not provided, registered, or tested as required. Submit annual operability testing of the overfill prevention device installed onsite (previously noted as drop tube valves) to Daniel.Gartin@flhealth.gov.
 
12/18/2024 6057 SNC-B 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. Have all sensors lowered to the correct height in the STP sump to ensure electronic monitoring of the sumps can occur as manufacturer's requirements. Submit either pictures or a detailed work invoice noting the sensors were lowered to Daniel.Gartin@flhealth.gov.
 
12/18/2024 6073 Minor 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Have all excessive liquid and sediment removed from the dispenser sumps and double wall spill buckets. Submit the associated work invoice detailing the removal of liquid and sediment or photographs to Daniel.Gartin@flhealth.gov.
 
12/18/2024 6043 Minor 4.13 Fillbox covers not marked according to requirements. Repaint the premium and vapor recovery bucket lids for the facility and ensure they meet the April 2020 API edition. Submit photographs of the repainted spill buckets to Daniel.Gartin@flhealt.gov.
 
12/18/2024 6063 SNC-B 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. Confirm and replace the damaged entry boot in dispenser sump 1/2. Submit associated work notification upon initiating the replacement and integrity testing upon completion repair to dispenser sump 1/2 to Daniel.Gartin@flhealth.gov.
 
12/18/2024 6072 Minor 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. Have vacuum testing conducted for all double wall spill buckets conducted by a certified contractor. Submit the associated testing to Daniel.Gartin@flhealth.gov.
 
12/18/2024 6057 SNC-B 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. Have the spill bucket gauge replaced and submit associated testing to Daniel.Gartin@flhealth.gov.
 
 
 
Discharge Information
 
Discharge
Date
  Clean Up
Status
Score Eligibility Info Site Manager Phone
12/08/1993   ACTIVE 10 PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE