Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
||||||||||
Cover Page Report | |||||||||||
Report Run Date: 02/02/2025 Last Data Refresh: 02/01/2025 Report Generated from DOPPLER | |||||||||||
District | Northwest | Type | Retail Station | ||||||||
County | Bay | Status | OPEN | ||||||||
ID | 8626356 | Latitude | 30° 10' 34.7971 | ||||||||
Name |
TEXACO FOOD STORE #4500 1512 HARRISON DR |
Longitude | 85° 39' 35.2854 | ||||||||
PANAMA CITY, FL 32402 | LL Method | DPHO | |||||||||
Contact | PAUL BAISCH | LL Status | REVIEWED | ||||||||
Phone | (770) 778-2620 | Status Date | 06/15/2023 | ||||||||
Account Owner Information | |||||||||||
Name | PANHANDLE COMMERCIAL PROPERTIES LLC PO BOX 1565 Lawrenceville, GA 30046 |
Effective Date | 07/25/2003 | ||||||||
Contact | SCOTT MOON / JUAN VALENCIA | ||||||||||
Phone | (679) 994-0632 | ||||||||||
SCOTT@MAJORSMGMT.COM | |||||||||||
Placard # / Date | 681619 - 06/05/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | PANHANDLE COMMERCIAL PROPERTIES LLC PO BOX 1565 Lawrenceville, GA 30046 |
Effective Date | 07/25/2003 | ||||||||
Contact | SCOTT MOON / JUAN VALENCIA | ||||||||||
Phone | (679) 994-0632 | ||||||||||
SCOTT@MAJORSMGMT.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
4 | 20000 | Unleaded Gas (B) | 06/01/2009 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
5 | 10000 | Vehicular Diesel (D) | 06/01/2009 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms (R) Double wall - tank jacket |
(C) Fiberglass (F) Double wall (J) Pressurized piping system (K) Dispenser liners |
(4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (L) Automatic tank gauging - USTs |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 8021 | Unleaded Gas (B) | 05/01/1990 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (G) Sacrificial anode CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(B) Steel/galvanized metal (C) Fiberglass (E) Cathodic protection (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 8021 | Unleaded Gas (B) | 05/01/1990 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (G) Sacrificial anode CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(B) Steel/galvanized metal (C) Fiberglass (E) Cathodic protection (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
3 | 8000 | Unleaded Gas (B) | 05/01/1990 | UNDERGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(A) Ball check valve (C) Steel (G) Sacrificial anode CP (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill |
(B) Steel/galvanized metal (C) Fiberglass (E) Cathodic protection (J) Pressurized piping system (K) Dispenser liners |
(2) Visual inspect pipe sumps (4) Visual inspect dispenser liners (H) Mechanical line leak detector (S) Statistical Inventory Reconcile |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 12/31/2023 | 12/31/2024 | TOKIO MARINE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 12/31/2021 | 12/31/2022 | TOKIO MARINE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 12/31/2020 | 12/31/2021 | TOKIO MARINE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 12/31/2017 | 12/31/2018 | TOKIO MARINE SPECIALTY INSURANCE COMPANY | ||||||||
INSURANCE | 12/31/2017 | 12/31/2018 | TORUS SPECIALTY INSURANCE CO | ||||||||
INSURANCE | 12/31/2015 | 12/31/2016 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
INSURANCE | 12/31/2012 | 12/31/2013 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
INSURANCE | 12/31/2012 | 12/31/2013 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
INSURANCE | 04/15/2011 | 04/15/2012 | LIBERTY SURPLUS INSURANCE CORP | ||||||||
INSURANCE | 04/15/2010 | 04/15/2011 | ZURICH-AMERICAN | ||||||||
INSURANCE | 04/15/2009 | 04/15/2010 | ZURICH-AMERICAN | ||||||||
INSURANCE | 04/23/1994 | 04/23/1995 | PLUS | ||||||||
INSURANCE | 04/23/1993 | 04/23/1994 | FPLIPA | ||||||||
Legacy Compliance Activity Information | |||||||||||
Activity Code |
Date Initiated |
Date Completed |
Results | Inspector | AST/UST Count |
Description | |||||
RRBD | 01/27/2006 | 01/30/2006 | COMPLIANCE ASSURANCE | ||||||||
RRBD | 11/07/2005 | 11/07/2005 | COMPLIANCE ASSURANCE | ||||||||
TCI | 08/30/2005 | 09/02/2005 | MINOR OUT-OF-COMPLIANCE | KHAN | 0/3 | COMPLIANCE ASSURANCE | |||||
RRBD | 11/02/2004 | 11/08/2004 | PINKOVSKY | 0/0 | COMPLIANCE ASSURANCE | ||||||
TCI | 08/31/2004 | 09/01/2004 | MINOR OUT-OF-COMPLIANCE | KHAN | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PIPING: UNKNOWN FIBERGLASS & STEEL | |||||||||||
TIN | 01/13/2004 | 01/28/2004 | IN-COMPLIANCE | PINKOVSKY | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PIPING: UNKNOWN FIBERGLASS & STEEL | |||||||||||
RRBD | 12/08/2003 | 12/08/2003 | PINKOVSKY | 0/0 | COMPLIANCE ASSURANCE | ||||||
RRBD | 09/15/2003 | 09/15/2003 | COMPLIANCE ASSURANCE | ||||||||
TCI | 08/26/2003 | 08/28/2003 | SIGNIFICANT OUT-OF-COMPLIANCE | KHAN | 0/3 | COMPLIANCE ASSURANCE | |||||
Completion Notes PIPING: UNKNOWN FIBERGLASS | |||||||||||
CRDE | 11/18/2002 | 11/18/2002 | PINKOVSKY | 0/0 | COMPLIANCE ASSURANCE | ||||||
Completion Notes PER NWD REQUEST, COMPANY BANKRUPTCY | |||||||||||
TCI | 10/17/2002 | 10/21/2002 | SIGNIFICANT OUT-OF-COMPLIANCE | KHAN | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 10/17/2001 | 10/19/2001 | IN-COMPLIANCE | PINKOVSKY | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 10/17/2000 | 10/19/2000 | IN-COMPLIANCE | BRADLEY | 0/3 | COMPLIANCE ASSURANCE | |||||
TCI | 10/19/1999 | 10/20/1999 | IN-COMPLIANCE | PINKOVSKY | 0/3 | COMPLIANCE ASSURANCE | |||||
LTR | 01/29/1999 | 03/08/1999 | PINKOVSKY | 0/0 | COMPLIANCE ASSURANCE | ||||||
UTCR | 01/12/1999 | 03/08/1999 | IN-COMPLIANCE | CAMPBELL | 0/3 | COMPLIANCE ASSURANCE | |||||
TIN | 01/11/1999 | 03/08/1999 | IN-COMPLIANCE | CAMPBELL | 0/3 | COMPLIANCE ASSURANCE | |||||
UTCI | 09/16/1998 | 09/21/1998 | MINOR OUT-OF-COMPLIANCE | COMPLIANCE ASSURANCE | |||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Site Inspection | 12/18/2024 | Major Out of Compliance | GARTIN_D | 0/2 | Routine Compliance | ||||||
Letter | 12/18/2024 | Satisfied | GARTIN_D | Compliance Assistance | |||||||
Meeting | 12/13/2024 | Satisfied | GARTIN_D | Routine Compliance | |||||||
Electronic Communication | 12/13/2024 | Satisfied | GARTIN_D | Routine Compliance | |||||||
Electronic Communication | 10/06/2023 | Satisfied | MATHERLY_H | Enforcement | |||||||
Enforcement Tracking | 10/06/2023 | Closed Without Enforcement | GILLMAN_M | Enforcement | |||||||
Letter | 04/04/2023 | Satisfied | MATHERLY_H | Enforcement | |||||||
Enforcement Referral | 03/22/2023 | Accepted | KHAN_MR_1 | Enforcement | |||||||
Record Document | 03/16/2023 | Satisfied | KHAN_MR_1 | Compliance Assistance | |||||||
Letter | 12/22/2022 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Phone Conversation | 12/21/2022 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Site Inspection | 12/21/2022 | Major Out of Compliance | KHAN_MR_1 | 0/2 | Routine Compliance | ||||||
Letter | 05/03/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Issue Document | 05/03/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Record Document | 04/29/2021 | Satisfied | KHAN_MR_1 | Compliance Assistance | |||||||
Letter | 02/01/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Issue Document | 02/01/2021 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 01/29/2021 | Major Out of Compliance | KHAN_MR_1 | 0/2 | Routine Compliance | ||||||
Phone Conversation | 01/14/2021 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Record Document | 07/25/2019 | Satisfied | WILSON_ML_1 | Closure | |||||||
Record Document | 07/25/2019 | Satisfied | WILSON_ML_1 | Installation | |||||||
Letter | 05/09/2019 | Satisfied | WILSON_ML_1 | Closure | |||||||
Issue Document | 05/09/2019 | Satisfied | WILSON_ML_1 | Closure | |||||||
TCAR | 05/09/2019 | Satisfied | PAYNE_CL_1 | Closure | |||||||
Document Management | 05/08/2019 | Satisfied | WILSON_ML_1 | Closure | |||||||
Record Document | 01/08/2019 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Letter | 01/08/2019 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Complaint | 11/16/2018 | Satisfied | KHAN_MR_1 | Complaint | |||||||
Record Document | 10/30/2018 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 10/23/2018 | Minor Out of Compliance | BROCK_SN_1 | 0/2 | Complaint | ||||||
Letter | 07/24/2018 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Issue Document | 07/24/2018 | Satisfied | WILSON_ML_1 | Compliance Assistance | |||||||
Site Inspection | 07/20/2018 | Minor Out of Compliance | KHAN_MR_1 | 0/2 | Routine Compliance | ||||||
Phone Conversation | 07/19/2018 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Enforcement Tracking | 10/25/2016 | Closed Without Enforcement | MERRITT_S | Enforcement | |||||||
Site Inspection | 10/25/2016 | In Compliance | MERRITT_S | 0/2 | Enforcement | ||||||
Enforcement Referral | 08/05/2016 | Accepted | MERRITT_S | Enforcement | |||||||
Letter | 03/07/2016 | Satisfied | WILSON_ML_1 | Non-Compliance | |||||||
Record Document | 03/01/2016 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Letter | 02/03/2016 | Satisfied | WILSON_ML_1 | Non-Compliance | |||||||
Site Inspection | 02/01/2016 | Major Out of Compliance | KHAN_MR_1 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 12/11/2013 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Electronic Communication | 12/11/2013 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Site Inspection | 10/24/2013 | Minor Out of Compliance | KHAN_MR_1 | 0/2 | Routine Compliance | ||||||
Letter | 10/24/2013 | Satisfied | DAURIA_KL_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 10/24/2013 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Electronic Communication | 07/08/2013 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Phone Conversation | 07/02/2013 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Phone Conversation | 07/02/2013 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Phone Conversation | 06/17/2013 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Letter | 01/28/2013 | Satisfied | DAURIA_KL_1 | Non-Compliance | |||||||
Site Inspection | 01/24/2013 | Minor Out of Compliance | KHAN_MR_1 | 0/2 | Routine Compliance | ||||||
Emergency Preparedness Information | 01/24/2013 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Site Inspection | 01/19/2012 | In Compliance | KHAN_MR_1 | 0/2 | Routine Compliance | ||||||
Letter | 10/08/2010 | Satisfied | PIERCE_LL_1 | Non-Compliance | |||||||
Emergency Preparedness Information | 09/24/2010 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Site Inspection | 09/23/2010 | Minor Out of Compliance | KHAN_MR_1 | 0/2 | Routine Compliance | ||||||
Emergency Preparedness Information | 09/23/2010 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 10/12/2009 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Site Inspection | 10/05/2009 | In Compliance | KHAN_MR_1 | 0/2 | Routine Compliance | ||||||
Site Inspection | 06/25/2009 | In Compliance | BRAZILE_DO_1 | 0/2 | Installation | ||||||
Record Document | 05/14/2009 | Satisfied | BRAZILE_DO_1 | Non-Compliance | |||||||
Record Document | 05/13/2009 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Letter | 05/13/2009 | Satisfied | BRAZILE_DO_1 | Non-Compliance | |||||||
Site Inspection | 05/12/2009 | Major Out of Compliance | BRAZILE_DO_1 | 0/3 | Closure | ||||||
Letter | 08/04/2008 | Satisfied | KHAN_MR_1 | Non-Compliance | |||||||
Site Inspection | 07/31/2008 | Minor Out of Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 07/30/2008 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 07/29/2008 | Satisfied | KHAN_MR_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 04/14/2008 | Satisfied | BRAZILE_DO_1 | Routine Compliance | |||||||
Site Inspection | 07/12/2007 | In Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
Emergency Preparedness Information | 02/07/2007 | Satisfied | BRAZILE_DO_1 | Routine Compliance | |||||||
Emergency Preparedness Information | 09/26/2006 | Satisfied | BRAZILE_DO_1 | Routine Compliance | |||||||
Site Inspection | 07/17/2006 | In Compliance | KHAN_MR_1 | 0/3 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
12/18/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Determine the source of the liquid in the premium double wall spill bucket interstitial space and vacuum test the premium spill bucket to proper PEI standard to confirm the integrity of the double wall spill bucket. Submit associated testing and cause of liquid in the interstitial space to Daniel.Gartin@flhealth.gov. | |||||||
12/18/2024 | 6003 | Minor | 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Have the registration information of tank 4 and tank 5 updated to reflect the proper construction of the tank system. Tank 4 will need to be updated to list ethanol gasoline blend instead of non-ethanol blend. Submit information showing the registration of these tanks was updated to Daniel.Gartin@flhealth.gov. | |||||||
12/18/2024 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | Submit annual operability testing of the overfill prevention device installed onsite (previously noted as drop tube valves) to Daniel.Gartin@flhealth.gov. | |||||||
12/18/2024 | 6057 | SNC-B | 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. | Have all sensors lowered to the correct height in the STP sump to ensure electronic monitoring of the sumps can occur as manufacturer's requirements. Submit either pictures or a detailed work invoice noting the sensors were lowered to Daniel.Gartin@flhealth.gov. | |||||||
12/18/2024 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | Have all excessive liquid and sediment removed from the dispenser sumps and double wall spill buckets. Submit the associated work invoice detailing the removal of liquid and sediment or photographs to Daniel.Gartin@flhealth.gov. | |||||||
12/18/2024 | 6043 | Minor | 4.13 Fillbox covers not marked according to requirements. | Repaint the premium and vapor recovery bucket lids for the facility and ensure they meet the April 2020 API edition. Submit photographs of the repainted spill buckets to Daniel.Gartin@flhealt.gov. | |||||||
12/18/2024 | 6063 | SNC-B | 4.1 Not repaired or isolated component or piping which has not caused a discharge or release. | Confirm and replace the damaged entry boot in dispenser sump 1/2. Submit associated work notification upon initiating the replacement and integrity testing upon completion repair to dispenser sump 1/2 to Daniel.Gartin@flhealth.gov. | |||||||
12/18/2024 | 6072 | Minor | 2.7 Integrity testing of secondary containment systems and interstitial spaces not performed per schedule. | Have vacuum testing conducted for all double wall spill buckets conducted by a certified contractor. Submit the associated testing to Daniel.Gartin@flhealth.gov. | |||||||
12/18/2024 | 6057 | SNC-B | 4.7 Release detection not installed, operated, and maintained per manufacturer's instructions and standards. | Have the spill bucket gauge replaced and submit associated testing to Daniel.Gartin@flhealth.gov. | |||||||
Discharge Information | |||||||||||
Discharge Date |
Clean Up Status |
Score | Eligibility Info | Site Manager | Phone | ||||||
12/08/1993 | ACTIVE | 10 | PETROLEUM LIABILITY AND RESTORATION INSURANCE PROGRAM-ELIGIBLE | ||||||||